Split system (Single phase and 3-phase type)
20
Maintenance
Document
1544-1
Clear 15: Current trip (permanent stoppage)
Hydraulic Unit LED: Green 9 flashes / Red 4 flashes
Outdoor Unit LED: 13 flashes
Probable causes:
Connection failure
.
Outdoor Heat Exchanger clogged
.
Outdoor Fan operation failure
.
Compressor failure.
Main PCB failure.
Check:
1.
Check connections condition in control unit
:
- Check if the terminal connection is loose.
- Check if connector is removed.
- Check if connector is erroneous connection.
- Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
OK
3.
Check Outdoor Fan
:
- Check Outdoor Fan Motor. (Refer to Clear 18)
If the Fan Motor is failure, replace it.
OK
4. Check Compressor:
Refer to “Service parts information 2 : Inverter compressor
If it is abnormal, replace compressor.
OK
2. Check Outdoor Heat Exchanger:
- Is there any obstructing the air flow route?
- Is there any clogging of outdoor unit Heat Exchanger?
If clogged, clear the clog.
5. Replace Inverter PCB:
If Check Point 1 ~ 4 do not improve the symptom, replace Inverter PCB.
OK