- (01-02) -
Model No.
Item
UTZ-BD080B
Power Source
220–240V~ 50Hz
Ventilation Mode
Heat Exchange Ventilation
Normal Ventilation
Notch
(Extra high)
High
Low
(Extra high)
High
Low
Input (W)
387-418
360-378
293-295
387-418
360-378
293-295
Air Volume (m
3
/h)
800
800
630
800
800
630
External Static Pressure (Pa)
140
110
55
140
110
55
Sound Pressure Level (dB)
37.0-37.5
36.5-37.0
33.5-34.5
37.0-37.5
36.5-37.0
33.5-34.5
Temperature Exchange
Efficiency (%)
75
75
76
—
—
—
Dimensions (mm)
(H x W x D)
Net
388 x 1322 x 884
Gross
467 x 1552 x 1170
Weight (kg)
Net
71
Gross
82
Outlet Duct Diameter (mm)
250
Operation Range (°C)
-10 to 40
Maximum Humidity (%)
85
Model No.
Item
UTZ-BD100B
Power Source
220–240V~ 50Hz
Ventilation Mode
Heat Exchange Ventilation
Normal Ventilation
Notch
(Extra high)
High
Low
(Extra high)
High
Low
Input (W)
437-464
416-432
301-311
437-464
416-432
301-311
Air Volume (m
3
/h)
1000
1000
700
1000
1000
700
External Static Pressure (Pa)
105
80
75
105
80
75
Sound Pressure Level (dB)
37.5-38.5
37.0-37.5
33.5-34.5
39.5-40.5
39.0-39.5
35.5-36.5
Temperature Exchange
Efficiency (%)
75
75
76
—
—
—
Dimensions (mm)
(H x W x D)
Net
388 x 1322 x 1134
Gross
467 x 1552 x 1420
Weight (kg)
Net
83
Gross
98
Outlet Duct Diameter (mm)
250
Operation Range (°C)
-10 to 40
Maximum Humidity (%)
85
(Note) This noise of the product is the value which was measured at the acoustic room.
Actually, in the established condition, that undergo influence by the echoing of the room and so that become bigger
than the display numerical value.