background image

- (01-20) -

4-2. NEEDS FOR VENTILATION

4-2-1. OBJECTIVES AND EFFECTS OF VENTILATION

EFFECTS OF VENTILATION

Ventilation is not simply designed to exhaust stale air. It also 

has deodorizing, dust removal, dehumidification, and room 

temperature adjustment functions, in addition to exchanging 

air.

(1)  Ventilation function

 

 Ventilation  supplies  fresh  air  required  to  sustain  our 

normal  breathing  and  exhausts  stale  air;  as  well  as 

supplies oxygen required for combustion and prevents 

imperfect combustion.

(2)  Deodorizing function

 

 A ventilation fan can quickly exhaust unpleasant odor 

derived from various sources, and create comfortable 

environment.

(3)  Dust removal function

 

 Dust floating in the air may accompany invisibly tiny various 

harmful bacteria, etc. Dust and dirt should thus be exhausted 

from room to create hygienic and comfortable environment.

(4)  Dehumidification function

 

 Humidity in a house is not limited to the bathroom. Moisture is 

also emitted from human bodies and combustion appliances. 

Particularly,  in  recent  years,  heating  in  a  highly  airtight 

structure has caused dew condensation, resulting in mold 

growth and even damaging floors and walls, etc. Eliminating 

interior humidity through ventilation will create comfortable and 

healthy conditions for both human bodies and buildings.

(5)  Room temperature adjustment function

 

 At summer nights, ventilation accompanied by refrigeration 

air  conditioning  can  eliminate  warm  room  air  by  the 

ventilator, and let in cool outdoor air. Circulation-type 

ventilators  can  also  maintain  the  room  temperatures, 

realizing highly efficient heating in winter.

EFFECTS OF STALE AIR ON 

BUILDING

Stains on interior surfaces

Brand new white ceilings, walls, furniture, and decorative items 

may turn yellowish in a year or two, due to tar contained in 

cigarettes and floating dust.

Beware of humidity

Humidity emitted from one human body is said to amount to 

about two liters a day. In highly airtight modern structures, in 

addition to bathrooms, which are almost always humid, many 

places can remain highly humid, such as living rooms, closets, 

storerooms, and under-floor areas, etc. If left unattended, 

mold and ticks will soon appear, and the wood may be more 

likely to be rotted. In addition, heating will also accelerate dew 

condensation, which may further damage portions behind walls 

and floors, which are not readily visible.

NEEDS FOR AIR SUPPLY

Ventilation is to exchange indoor air with outdoor air. When 

ventilation is performed by a ventilating fan (generally for the 

exhausting function), if air inlet is limited (in a room or a building), 

the capabilities of the ventilator may be greatly reduced, or the 

indoor pressure may be lowered, causing drafts and noises, as 

well as making it difficult to open or close doors.

Sizes and locations of inlets

(1)  Sizes of air inlets

 

 Required sizes of inlets may vary, depending on the sizes of apertures 

and openings of the buildings. The effective opening area (cm

2

) should 

be 0.7 times the ventilation airflow (m

3

/h), with the internal and external 

pressure difference set at 10Pa.

 

     Effective opening area  

α

A(cm

2

) = 0.7 x airflow (m

3

/h)

 

 As a reference, the following computation formulas are proposed 

in the ventilation/air-conditioning engineering standards.

 

α

A= 0.68V - S    

α

A’ (in the case of  

Pmax = 10Pa)

 

α

A= 0.39V - S    

α

A’ (in the case of  

Pmax = 30Pa)

 

    

α

A: Effective opening area (cm

2

) of dedicated inlets

 

                 V: Effective ventilation air volume (m

3

/h)

 

    S: Gross floor area of a building (m

2

)

 

                 

α

A’: Air-tightness of a building (cm

2

/m

2

)

 

 A ventilating fan has an exhaust capability specified in the catalog, 

for which, however, the amount of air exhausted by the fan needs to 

be supplied from the inlet. 

 

 In other words, if the air-inlet is small, sufficient air cannot be 

supplied indoors, resulting in insufficient ventilation capacities. The 

air-inlet should generally be larger than the installation area for the 

ventilation fan. As the inlet area gets bigger, the air velocity there 

will be reduced, making it less uncomfortable for people near it.

Ex-

haust

Ex-

haust

 Smooth airflows

Slow air supply

velocity

H

ig

ai

r

su

pp

ly

ve

lo

ci

ty

,

ca

us

in

g

un

co

m

fo

rta

bl

e

fe

el

in

g

N

oi

sy

In

su

ffi

ci

en

t

ve

nt

ila

tio

n

ca

pa

ci

ty

Fig. 2-2

Fig. 2-1

For  a  large  room, air-inlets  should

be dispersed  and  as  far  distanced

from the ventilating fans as possible,

so that air can be ventilated evenly.

Air-inlet

Many portions of the

room remain unven-

tilated.

A bad example

Fewer

portions

of the

room

remain

unventi-

lated.

Air-inlet

 A good example

Ventilating fans  should  also

be dispersed.

 A good ex-

ample

Air-inlet

Fig. 2-3

Ex-

haust

Ex-

haust

 Smooth airflows

Slow air supply

velocity

H

ig

ai

r

su

pp

ly

ve

lo

ci

ty

,

ca

us

in

g

un

co

m

fo

rta

bl

e

fe

el

in

g

N

oi

sy

In

su

ffi

ci

en

t

ve

nt

ila

tio

n

ca

pa

ci

ty

Fig. 2-2

Fig. 2-1

For  a  large  room, air-inlets  should

be dispersed  and  as  far  distanced

from the ventilating fans as possible,

so that air can be ventilated evenly.

Air-inlet

Many portions of the

room remain unven-

tilated.

A bad example

Fewer

portions

of the

room

remain

unventi-

lated.

Air-inlet

 A good example

Ventilating fans  should  also

be dispersed.

 A good ex-

ample

Air-inlet

Fig. 2-3

Air-inlet

Air-inlet

Ex-

haust

Ex-

haust

 Smooth airflows

Slow air supply

velocity

H

ig

ai

r

su

pp

ly

ve

lo

ci

ty

,

ca

us

in

g

un

co

m

fo

rta

bl

e

fe

el

in

g

N

oi

sy

In

su

ffi

ci

en

t

ve

nt

ila

tio

n

ca

pa

ci

ty

Fig. 2-2

Fig. 2-1

For  a  large  room, air-inlets  should

be dispersed  and  as  far  distanced

from the ventilating fans as possible,

so that air can be ventilated evenly.

Air-inlet

Many portions of the

room remain unven-

tilated.

A bad example

Fewer

portions

of the

room

remain

unventi-

lated.

Air-inlet

 A good example

Ventilating fans  should  also

be dispersed.

 A good ex-

ample

Air-inlet

Fig. 2-3

(2)  Locations of exhausts (ventilation fans) and air-inlets

 

 In the case of general ventilation, air-inlets should be located as 

far detached from ventilating fans as possible. On the other hand, 

in the case of local ventilation, the air-inlet should be as close 

to the ventilating fans to minimize any effects to the surrounding 

areas.

(3)  In bathrooms,…

 

 When ventilating fans are installed in bathrooms, etc., air-inlets should 

always be installed (except for simultaneous exhaust/supply systems). 

Otherwise, ventilating air volumes may be reduced, or the sealing 

water may be disrupted in shallow traps, causing the sewage stench 

to flow into the room.

(4) 

In rooms where half-enclosed combustion apparatus are used

 

 In a cold region, when a stove with a chimney is installed without 

proper air-inlets, and ventilation fan is put into operation, the chimney 

may function as an air-inlet and let the exhaust into the room, causing 

a dangerous situation.

Содержание UTZ-BD025B

Страница 1: ...DTO_ERV002E_01 2013 04 26 DESIGN TECHNICAL MANUAL UTZ BD025B UTZ BD035B UTZ BD050B UTZ BD080B UTZ BD100B ENERGY RECOVERY VENTILATORS ...

Страница 2: ...NS 2 1 UTZ BD025B 01 03 2 2 UTZ BD035B 01 05 2 3 UTZ BD050B 01 07 2 4 UTZ BD080B 01 09 2 5 UTZ BD100B 01 11 3 WIRING DIAGRAMS 3 1 UTZ BD025B 01 13 3 2 UTZ BD035B UTZ BD050B 01 13 3 3 UTZ BD080B UTZ BD100B 01 14 3 4 INTERLOCKED CONNECTION TO AIR CONDITIONER 01 15 ...

Страница 3: ...IGN PRECAUTIONS 01 22 4 4 1 CAUTION ON SAFETY 01 22 4 4 2 INSPECTION OPENING AND INSTALLATION MODELS 01 23 4 4 3 USE ENVIRONMENTS 01 24 4 4 4 HEAT EXCHANGE EFFICIENCY 01 25 4 4 5 DUST COLLECTION EFFICIENCY 01 27 4 4 6 NOISE 01 28 4 4 7 NOISE CONTROL 01 29 4 5 VENTILATION DESIGN 01 31 4 5 1 QUANTITY DYNAMIC PRESSURE STATIC PRESSURE 01 31 4 5 2 HOW TO CALCULATE REQUIRED VENTILATION VOLUME 01 32 4 6 ...

Страница 4: ...185 168 175 182 190 178 185 168 175 Air Volume m3 h 350 350 240 350 350 240 External Static Pressure Pa 140 60 45 140 60 45 Sound Pressure Level dB 32 5 33 0 30 5 31 0 22 5 25 5 32 5 33 0 30 5 31 0 22 5 25 5 Temperature Exchange Efficiency 75 75 78 Dimensions mm H x W x D Net 317 x 1050 x 804 Gross 396 x 1250 x 1000 Weight kg Net 49 Gross 57 Outlet Duct Diameter mm 150 Operation Range C 10 to 40 M...

Страница 5: ...m UTZ BD100B Power Source 220 240V 50Hz Ventilation Mode Heat Exchange Ventilation Normal Ventilation Notch Extra high High Low Extra high High Low Input W 437 464 416 432 301 311 437 464 416 432 301 311 Air Volume m3 h 1000 1000 700 1000 1000 700 External Static Pressure Pa 105 80 75 105 80 75 Sound Pressure Level dB 37 5 38 5 37 0 37 5 33 5 34 5 39 5 40 5 39 0 39 5 35 5 36 5 Temperature Exchange...

Страница 6: ...n c u r v e Dry bulb temperature C Absolite humidity kg kg C C B B A REFERENCE SKETCH Pipe Hood Outside Intake Duct Ceilling Suspension Bolts Supply Air Duct EA Exhaust Air OA OutsideintakeAir RA RoomAir SA SupplyAir Inside Supply Opening Supply Exhaust Air Grill Room Intake Opening Supply Exhaust Air Grill Room Intake Duct Heat Insulation Material Exhaust Air Duct The two outside ducts the Outsid...

Страница 7: ...Same as the indoor air conditions Indoor air here means air in air conditioned living rooms Its use in refrigerators or other places where temperature can fluctuate greatly is prohibited even if a temperature range is acceptable Example Indoor air conditions During cooling period Temperature 27 C Relative humidity 50 During heating period Temperature 20 C Relative humidity 40 The Input the current...

Страница 8: ... r v e Dry bulb temperature C Absolite humidity kg kg C C B B A REFERENCE SKETCH Pipe Hood Outside Intake Duct Ceilling Suspension Bolts Supply Air Duct EA Exhaust Air OA OutsideintakeAir RA RoomAir SA SupplyAir Inside Supply Opening Supply Exhaust Air Grill Room Intake Opening Supply Exhaust Air Grill Room Intake Duct Heat Insulation Material Exhaust Air Duct The two outside ducts the Outside Int...

Страница 9: ...uirements Same as the indoor air conditions Indoor air here means air in air conditioned living rooms Its use in refrigerators or other places where temperature can fluctuate greatly is prohibited even if a temperature range is acceptable Example Indoor air conditions During cooling period Temperature 27 C Relative humidity 50 During heating period Temperature 20 C Relative humidity 40 The Input t...

Страница 10: ... n c u r v e Dry bulb temperature C Absolite humidity kg kg C C B B A REFERENCE SKETCH Pipe Hood Outside Intake Duct Ceilling Suspension Bolts Supply Air Duct EA Exhaust Air OA OutsideintakeAir RA RoomAir SA SupplyAir Inside Supply Opening Supply Exhaust Air Grill Room Intake Opening Supply Exhaust Air Grill Room Intake Duct Heat Insulation Material Exhaust Air Duct The two outside ducts the Outsi...

Страница 11: ...me as the indoor air conditions Indoor air here means air in air conditioned living rooms Its use in refrigerators or other places where temperature can fluctuate greatly is prohibited even if a temperature range is acceptable Example Indoor air conditions During cooling period Temperature 27 C Relative humidity 50 During heating period Temperature 20 C Relative humidity 40 The Input the current a...

Страница 12: ... n c u r v e Dry bulb temperature C Absolite humidity kg kg C C B B A REFERENCE SKETCH Pipe Hood Outside Intake Duct Ceilling Suspension Bolts Supply Air Duct EA Exhaust Air OA OutsideintakeAir RA RoomAir SA SupplyAir Inside Supply Opening Supply Exhaust Air Grill Room Intake Opening Supply Exhaust Air Grill Room Intake Duct Heat Insulation Material Exhaust Air Duct The two outside ducts the Outsi...

Страница 13: ...ance Curve P Q Curve 220 240V 50Hz Efficiency Curve Temperature Enthalpy in heating Enthalpy in cooling Extra High Equivalent pipe length High Low When friction coefficient of pipe duct 0 02 100m 60 40 250 20 350 80 90 450 500 Use conditions Outdoor air conditions Temperature range 10 C 40 C Relative humidity 85 or less Indoor air conditions Temperature range 10 C 40 C Relative humidity 85 or less...

Страница 14: ...n c u r v e Dry bulb temperature C Absolite humidity kg kg C C B B A REFERENCE SKETCH Pipe Hood Outside Intake Duct Ceilling Suspension Bolts Supply Air Duct EA Exhaust Air OA OutsideintakeAir RA RoomAir SA SupplyAir Inside Supply Opening Supply Exhaust Air Grill Room Intake Opening Supply Exhaust Air Grill Room Intake Duct Heat Insulation Material Exhaust Air Duct The two outside ducts the Outsid...

Страница 15: ...istance Curve P Q Curve 220 240V 50Hz Efficiency Curve Temperature Enthalpy in heating Enthalpy in cooling Extra High Equivalent pipe length High Low When friction coefficient of pipe duct 0 02 100m 60 40 250 20 350 80 90 500 450 Use conditions Outdoor air conditions Temperature range 10 C 40 C Relative humidity 85 or less Indoor air conditions Temperature range 10 C 40 C Relative humidity 85 or l...

Страница 16: ...tion of each switch refer to Page 7 of the Owner s manual Air Flow Switch 3 High 1 Low Operation Switch 3 ON 1 OFF UTZ BD025B 3 2 UTZ BD035B UTZ BD050B SW1 Switch Low Damper High Power Source 220 240V single phase 50Hz Power Source Line Power Source Neutral Second main body High Main unit L N SW1 SW2 Common Low Damper Terminal board Grey White White Blue Black Black Red Red White Black Brown Blue ...

Страница 17: ...w Blue Supply Air Fan Connector Connector White White Extra high White Black Black Capacitor Yellow Red Blue High Orange Orange Red Yellow Blue Exhaust Air Fan Yellow Yellow White White Black Black Blue Blue Connector Connector Micro switch Damper Motor Power Source Line Power Source Neutral High Main unit L N SW1 SW2 Common Low Damper Terminal board Grey White White Blue Black Black Red Red White...

Страница 18: ... power source The type is different depending on the model The allowable voltage current of the external output circuit from the air conditioner varies depending on the model Check it with the air conditioner technical manual Do not connect the energy recovery ventilator power source AC220 240V to the external output terminals from the air conditioner Regarding the relay circuit select the necessa...

Страница 19: ...he air conditioner is in the stopped state Do not make connections to multiple indoor units by duct direct connection system Dust may be dispersed depending on the operation condition of the air conditioner Energy recovery ventilator Dust Room air Room air Stopped External air Operating Power source AC220 240V 50Hz Energy recovery ventilator terminal Indoor unit PC board Relay circuit Provided at ...

Страница 20: ...eat exchange element By adopting nonwoven fabric filter with excellent dust collection efficiency and improving the air course shapes a long life heat exchange system has been realized which does not require regular cleaning of the heat exchange element cross flow element After cleaning the cross flow element The counter flow element Heat exchange element with extended life The cross flow element ...

Страница 21: ...MOUNTED INTERNAL STRUCTURE HEAT EXCHANGE VENTILATION Bypass air course Heat exchange element Filter for RA Filter for OA HEAT EXCHANGE UNIT CEILING MOUNTED INTERNAL STRUCTURE NORMAL VENTILATION Bypass air course Heat exchange element Filter for RA Filter for OA ...

Страница 22: ...ATTENTION When the heating function is on during winter do no use normal ventilation The dew condensation will take place in the unit which may result in stains on the ceiling etc Stale indoor air to be ex hausted EA Fresh external air to be supplied indoors SA Outdoor Indoor Total heat exchanger Stale indoor air RA Fresh external air OA Fresh external air to be supplied indoors SA Stale indoor ai...

Страница 23: ...ion air conditioning engineering standards αA 0 68V S αA in the case of Pmax 10Pa αA 0 39V S αA in the case of Pmax 30Pa αA Effective opening area cm2 of dedicated inlets V Effective ventilation air volume m3 h S Gross floor area of a building m2 αA Air tightness of a building cm2 m2 A ventilating fan has an exhaust capability specified in the catalog for which however the amount of air exhausted ...

Страница 24: ... air Exter nal air Positive pressure Exhaust outlet Indoor Ventilating fan Indoor Fig 3 3 Negative pressure Air supply inlet Ventilating fan Fig 3 4 To be applied for clean rooms and cooling machinery etc To be applied for kitchens toilets rooms where hot water heaters can be utilized in residences and copying rooms etc Class 1 Ventilation Method Exhaust Mechanical exhaust Air supply Mechanical ai...

Страница 25: ...be present e g acidic alkali or ganic solvent paint gasses etc from machinery or chemical plants etc Installation in such a location could cause a gas poisoning and a fire Carry out GND work Never connect the GND wire to a gas pipe a water supply pipe a lightning conductor or a GND line of a telephone c An incomplete GND wire likely to cause an electric shock et is If the unit is accompanied by wa...

Страница 26: ...ilter once or twice a year If not cleaned they are likely to get clogged resulting in deteriorated performance Installation Model Inspection Opening Exhaust Air Outside Air Room Air Supply Air Inspection Opening 450 For Filter Heat Exchange Element Motor Damper Inside Supply Opening Ceiling Suspension Bold Pipe Hood Supply Air Duct Outside Intake Duct Supply Air Room Intake Duct Room Intake Openin...

Страница 27: ...e occasions As the emergence of insects may depend on various natural conditions we recommend users to apply medium performance filters to be purchased separately in environments where there are many insects or where insects are likely to swarm as the exhaust intake openings are close to street lamps etc In addition it is also recommended that the unit should be turned off in the Heat Exchange Ven...

Страница 28: ...t If the temperature and humidity of the internal air and external air are determined and if the exchange efficiency of the heat exchange ventilating unit to be utilized is determined air conditions of the air supplied indoors and exhausted outdoors after passing through the heat exchange unit can be calculated in the following formula Intake Side Temperature Internal Supply Air Temperature C Exte...

Страница 29: ...heat exchange In the case of sensible heat exchange ventilation the recovered calorie can be calculated in the following formula Recovered Sensible Heat Calorie qT w Air Specific Gravity 1 2 kg m3 in the normal condition x Process Airflow m3 h x Isobaric Specific Heat of Dry Air 1 006 kJ kg C x External Air Temperature C Internal Air Temperature C x Sensible Heat Exchange Efficiency x 0 28 w h kJ ...

Страница 30: ...erformance The measuring methods for dust collection efficiencies are divided into JIS colorimetric method NBS colorimetric method counting method DOP method and mass ratio method AFI High values recorded in the mass ratio method may be lowered when converted in the colorimetric method Please refer to the indication of the measuring method Please refer to the correlation graph below for different ...

Страница 31: ...tances in anechoic chambers as specified in JIS etc The following points should be considered in selecting proper products 1 Changeable due to environmental conditions The measured values were determined in anechoic chambers In real settings echoes will take place from walls floors ceilings etc The measurements may also increase due to the materials used and the surrounding space It is thus necess...

Страница 32: ...ers should be used EFFECTS OF NOISE CONTROL MEASURES Points 1 The noise reduction duct not less than 2m should always be used at the exit of the unit on the internal supply side 2 Spiral ducts galvanized steel tubes and aluminum flexible ducts should not be connected to the unit exit opening General Comparison of Effects 1 Great Effects 4 Small Effects 1 Noise reduction duct installed for 6m 2 Noi...

Страница 33: ...ly Particularly the bending immediately after the exit opening of the unit body 3 Do not make unnecessary openings on the ceilings 4 Do not suspend the unit under members with insufficient strength 2 The following control measures may be taken 1 Ceiling materials should be of high sound insulation quality with large transmission losses Note Specifically low frequency noises cannot be significantly...

Страница 34: ... follows V Flow velocity m sec g Gravity acceleration m sec2 Specific weight of air kg m3 HOW TO INTERPRET STATIC PRESSURE QUANTITY CHARACTERISTIC CURVE P Q CURVE A graphic presentation of the relationship between the quantity and the static pressure of a ventilating fan is referred to as P Q Curve which can indicate the performance of the fan Fig 6 2 illustrate a case in which a small intake open...

Страница 35: ...ON THE NUMBER OF VENTILATION OPERATIONS REQUIRED FOR A ROOM Required Ventilation Volume m3 h Number of Ventilation Operations Required in an Hour times h x Cubic Capacity of Room m3 The ventilation volume can be determined by calculating the cubic capacity of the room and using the number of ventilation operations indicated in Table 6 2 Example Location Bathroom Required Number of Ventilation Oper...

Страница 36: ...haracteristic Curve Fig 7 1 CALCULATION BASED ON EQUAL PRESSURE METHOD 1 Circular Duct 1 Duct resistance can be calculated from the following formula To determine the pressure loss caused in air flowing through a straight duct ΔP the following formula is generally used Duct Resistance ΔP Pa Friction Coefficient of Duct 0 01 0 25 g Gravitational Acceleration 9 8m sec2 Air Density kg m3 1 20kg m3 L ...

Страница 37: ...bend with rectangular cross section 0 5 1 30 72d 0 75 0 52 29d 1 0 0 25 14d 1 5 0 20 11d 1 0 5 1 20 67d 0 75 0 44 24d 1 0 0 21 12d 1 5 0 17 9d CALCULATION IN SIMPLIFIED METHOD A case in which a model is selected based on straight pipe corresponding length and airflow quantity A model is selected based on the following conditions Required ventilation quantity 120 m3 h Duct system Fig 7 5 60Hz Examp...

Страница 38: ...l Please refer to the electric facility engineering standards and the internal regulations Heat Insulation Material to insulate the Adapter and Aluminum Tape Outside Intake Duct Exhaust Air Duct Gradient Aluminum Tape Aluminum Tape Fig 3 Ceiling Suspen sion Bolt Ceiling Suspen sion Bolt Nut Washer Ceiling Suspension Fixture Washer Nut Fig 1 Anti Vibration Ceiling Suspension Fixture Unit Body Fig 2...

Отзывы: