5.2 Member objects
5.2.1 Type: Gateway
Object-name
Description
Object-type
Object-instance
UTY-VBGX
BACnet Gateway for VRF System
Device
144
Gateway_ES_Status
-
BI
0
Gateway_Error_Status
-
BI
1
Gateway_ES_Setting
-
BO
0
Gateway_ErrorCode_Status
-
MI
0
5.2.2 Type: Batch objects
Object-name
Object-type
Object-instance
Batch_SetTemp_Setting
AO
0
Batch
_Operation_Setting
BO
1
Batch_OperationMode_Setting
MO
0
Batch_FanSpeed_Setting
MO
1
Batch_RC_Prohibition_Setting
MO
2
5.2.3 Type: Indoor Unit
Object-name
Object-type
Object-instance
IU_rr_uu_SetTemp_Status
AI
10rruu
IU_rr_uu_SpaceTemp_Status
AI
11rruu
IU_rr_uu_AutoTempLoLim_Status
AI
12rruu
IU_rr_uu_AutoTempHiLim_Status
AI
13rruu
IU_rr_uu_CoolTempLoLim_Status
AI
14rruu
IU_rr_uu_CoolTempHiLim_Status
AI
15rruu
IU_rr_uu_HeatTempLoLim_Status
AI
16rruu
IU_rr_uu_HeatTempHiLim_Status
AI
17rruu
IU_rr_uu_SetTemp_Setting
AO
10rruu
IU_rr_uu_AutoTempLoLim_Setting
AO
11rruu
IU_rr_uu_AutoTempHiLim_Setting
AO
12rruu
IU_rr_uu_CoolTempLoLim_Setting
AO
13rruu
IU_rr_uu_CoolTempHiLim_Setting
AO
14rruu
IU_rr_uu_HeatTempLoLim_Setting
AO
15rruu
IU_rr_uu_HeatTempHiLim_Setting
AO
16rruu
IU_rr_uu_Exists_Status
BI
10rruu
IU_rr_uu_Operation_Status
BI
11rruu
IU_rr_uu_ThermostatOFF_Status
BI
12rruu
IU_rr_uu_FilterSign_Status
BI
13rruu
IU_rr_uu_Emergency_Status
BI
14rruu
IU_rr_uu_Error_Status
BI
15rruu
IU_rr_uu_TempLimValid_Status
BI
16rruu
IU_rr_uu_
Operation_Setting
BO
10rruu
IU_rr_uu_
ThermostatOFF_Setting
BO
11rruu
IU_rr_uu_
Reset_Filter_Setting
BO
12rruu
IU_rr_uu_
TempLimValid_Setting
BO
13rruu
IU_rr_uu_OperationMode_Status
MI
10rruu
IU_rr_uu_FanSpeed_Status
MI
11rruu