BACnet Gateway for VRF System
INSTRUCTION MANUAL r1.4.0 eng
159/159
Copyright© 2021 Fujitsu General Limited - All rights reserved
12.2 RC Prohibition
Remote Control Prohibit commands can be set/read using the values in the following correspondence table.
Note: “ON” and “OP” may not be set at the same time.
State Text
Description
FL
Filter display reset operation prohibited
ON
Start operation prohibited (S/V Series do not have this function)
OP
Start/stop operation prohibited
MD
Operation mode operation prohibited
TP
Set temperature operation prohibited
TR
Timer setting prohibited
ALL
All prohibited
Pesent_Value
Contents displayed in State_Text
Pesent_Value
Contents displayed in State_Text
1
-/-/-/-/-/-/-
34
-/TR/-/-/-/-/FL
2
-/-/-/-/-/-/FL
35
-/TR/-/-/-/ON/-
3
-/-/-/-/-/ON/-
36
-/TR/-/-/-/ON/FL
4
-/-/-/-/-/ON/FL
37
-/TR/-/-/OP/-/-
5
-/-/-/-/OP/-/-
38
-/TR/-/-/OP/-/FL
6
-/-/-/-/OP/-/FL
39
-/TR/-/-/OP/ON/-
7
-/-/-/-/OP/ON/-
40
-/TR/-/-/OP/ON/FL
8
-/-/-/-/OP/ON/FL
41
-/TR/-/MD/-/-/-
9
-/-/-/MD/-/-/-
42
-/TR/-/MD/-/-/FL
10
-/-/-/MD/-/-/FL
43
-/TR/-/MD/-/ON/-
11
-/-/-/MD/-/ON/-
44
-/TR/-/MD/-/ON/FL
12
-/-/-/MD/-/ON/FL
45
-/TR/-/MD/OP/-/-
13
-/-/-/MD/OP/-/-
46
-/TR/-/MD/OP/-/FL
14
-/-/-/MD/OP/-/FL
47
-/TR/-/MD/OP/ON/-
15
-/-/-/MD/OP/ON/-
48
-/TR/-/MD/OP/ON/FL
16
-/-/-/MD/OP/ON/FL
49
-/TR/TP/-/-/-/-
17
-/-/TP/-/-/-/-
50
-/TR/TP/-/-/-/FL
18
-/-/TP/-/-/-/FL
51
-/TR/TP/-/-/ON/-
19
-/-/TP/-/-/ON/-
52
-/TR/TP/-/-/ON/FL
20
-/-/TP/-/-/ON/FL
53
-/TR/TP/-/OP/-/-
21
-/-/TP/-/OP/-/-
54
-/TR/TP/-/OP/-/FL
22
-/-/TP/-/OP/-/FL
55
-/TR/TP/-/OP/ON/-
23
-/-/TP/-/OP/ON/-
56
-/TR/TP/-/OP/ON/FL
24
-/-/TP/-/OP/ON/FL
57
-/TR/TP/MD/-/-/-
25
-/-/TP/MD/-/-/-
58
-/TR/TP/MD/-/-/FL
26
-/-/TP/MD/-/-/FL
59
-/TR/TP/MD/-/ON/-
27
-/-/TP/MD/-/ON/-
60
-/TR/TP/MD/-/ON/FL
28
-/-/TP/MD/-/ON/FL
61
-/TR/TP/MD/OP/-/-
29
-/-/TP/MD/OP/-/-
62
-/TR/TP/MD/OP/-/FL
30
-/-/TP/MD/OP/-/FL
63
-/TR/TP/MD/OP/ON/-
31
-/-/TP/MD/OP/ON/-
64
-/TR/TP/MD/OP/ON/FL
32
-/-/TP/MD/OP/ON/FL
65
ALL/-/-/-/-/-/-
33
-/TR/-/-/-/-/-