Line
Function
Setting range or display
Setting
increment
Basic setting
850
I
Off
-Off : Early interruption of the current programme, programme inactive
-Functional heating
-Curing heating
-Functional h curing heating
-Curing h functional heating
-Manually
Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after
25 days.
851
I
Floor curing setp manually
(if line 850 = manual)
0... 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying programme stops automatically after running for 25 days.
856
I
Floor curing day current
0... 32
857
I
Days complete.current
0... 32
900
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort, Automatic
1
Protection
mode
Operating mode at end of concrete slab drying period
"
Please comply with the
standards and instructions
of the manufacturer of the
building! A good performance
of this function is only possible
with an installation correctly
implemented
(hydraulic,
electricity and adjustments)!
This function can be stopped
by anticipation when setting
the adjustment on "Stop"
50
45
40
35
30
20
5
0
25
55
1
1
5
7
X
10
18
25
15
1
figure 15 - Diagram of the concrete slab drying programmes
Heating flow temperature °C
Functional h Curing heating
Curing heating
Day
Functional
heating
Installation and operating manual "1395 - EN"
- 19 -
Control Box