When the Service Processor Is Initialized, ILOM
May Fails to Start With an Error Message
Displayed (CR 6856163)
This issue is resolved by updating the system firmware to 7.2.7.b or later.
If the service processor is initialized (*1) with the LAN cable disconnected from the
ILOM network port, the ILOM firmware serial console window displays an error
message (*2) indicating a failure to start an ILOM internal process. As a result, ILOM
fails to start.
(*1) Service processor initialization has the following meaning:
■
For ILOM
-> set /SP reset_to_defaults=all
or
factory
-> reset /SP
■
For ALOM CMT compatible shell
sc> setdefaults
sc> resetsc
Example of failure:
Workaround: Initialize the service processor with the LAN cable connected to the
ILOM network port.
As long as the network port is linked up, the service processor can be initialized,
even without ILOM network settings.
SUNSP-BEL07482AU login:
root
Password:
Waiting for daemons to initialize...
Timed out waiting for daemons to start
<-- (*2)
sccd daemon has shutdown
<-- (*2)
Integrated Lights Out Manager
Version 3.0.3.20.e
Copyright 2009 Sun Microsystems, Inc. All rights reserved.
Use is subject to license terms.
Warning: password is set to factory default.
->
Содержание SPARC Enterprise T5440 Server
Страница 4: ......
Страница 18: ...8 SPARC Enterprise T5440 Server Product Notes December 2010 ...
Страница 38: ...28 SPARC Enterprise T5440 Server Product Notes December 2010 ...
Страница 58: ...48 SPARC Enterprise T5440 Server Product Notes December 2010 ...
Страница 66: ...56 SPARC Enterprise T5440 Server Product Notes December 2010 ...
Страница 92: ...82 SPARC Enterprise T5440 Server Product Notes December 2010 ...