1-6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
F
Zone control (rps:Compressor frequency)
1) Cool / Heat (Normal)
ollow
S-Hi2
S-Hi1
Hi3
Hi2
Hi1
Me2
Me1
Lo2
Lo1
ing table shows the fan speed of the outdoor unit.
01-09
( Table 6
-
1100
1100
1100
1050
1050
780
720
590
590
480
1100
530
430
370
300
-
1100
870
870
720
500
500
: Fan speed of the outdoor unit )
Cooling
Normal
Normal
Heating
Ambient Temperature zone
2) Dry (Nomal)
F zone G zone
D zone(Normal 1)
D zone(Normal 2)
F zone
G zone
21°
C
12°
C
2°
C
19°
C
10°
C
0°
C
68rps
40rps
35rps
24rps
15rps
72rps
43rps
37rps
27rps
15rps
Hi2
Hi1
19rps and over [ Hi 1 ]
16rps and over [ Me 1 ]
16rps under [ Lo 1 ]
Me2
Me1
Lo2
Lo1
3) Cool / Dry / F zone
51rps and over [ Hi 1 ]
43rps and over [ Me 1 ]
43rps under [ Lo 1 ]
4) Cool / Dry / G zone
51rps and over [ Hi 1 ]
43rps and over [ Me 1 ]
43rps under [ Lo 1 ]
43rps and over [ Hi 1 ]
34rps and over [ Me 1 ]
34rps under [ Lo 1 ]
Low ambient cooling / Dry
Normal
Dry
-
-
-
-
-
530
530
-
-
-
-
-
-
-
-
-
-
-
-
-
-
350
300
260
-
-
250
250
200
-
-
H zone
H zone
-8°
C
-10°
C
5) Cool / Dry / H zone
AMP Air Conditioning