1-7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in Table 7.
Cooling / Dry Heating
Min
Max
Min
Max
(Table 7 : Compressor Operation Frequency Range)
01-10
12rps
10rps 120rps
120rps
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Fig.9.
(Fig.9 : Compressor Control at Start-up)
Normal start-up
35rps
53rps
66rps
82rps
106rps
(Frequency)
(Time)
Time 1
Time 2
Time 3
Time 4
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time 5
Frequency
Frequency
Frequency
80sec
160sec
300sec
440sec
500sec
Time 1
Time 2
Time 3
Time 4
Time 5