RX4770 M2
Operating Manual
53
Hardware installation
Installation requirements for AC redundant configurations
The AC redundant configuration is with two PSU plugged into a main AC source
and two other PSUs plugged into a separate AC source (e.g. UPS).
Installation requirements for AC non redundant configurations
For systems not requiring AC redundancy, the power supply subsystem can be
installed with up to 4 PSUs. The PSUs can be connected to a single or multiple
AC sources.
PSU Configuration
Max. DC Loading
DC Redundancy
1+1 (2 PSUs)
1200W (100-127V): 1023W
1200W (200-240V): 1200W
1600W (200-240V): 1600W
Yes
2+2 (4 PSUs)
1200W (100-127V): 1956W
1200W (200-240V): 2310W
1600W (200-240V): 3040W
Yes
Table 2: Maximum DC Loading Requirements
PSU Configuration
Max. DC Loading
DC Redundancy
1+1 (2 PSUs)
1200W (100-127V): 1023W
1200W (200-240V): 1200W
1600W (200-240V): 1600W
Yes
2+1 (3 PSUs)
1200W (100-127V): 1956W
1200W (200-240V): 2310W
1600W (200-240V): 3040W
Yes
3+1 (4 PSUs)
1200W (100-127V): 2919W
1200W (200-240V): 3450W
1600W (200-240V): 4480W
Yes
Table 3: Maximum DC Loading Requirements
Содержание PRIMERGY RX4770 M2
Страница 1: ...Operating Manual English FUJITSU Server PRIMERGY RX4770 M2 Operating Manual Edition April 2015 ...
Страница 6: ...Operating Manual RX4770 M2 ...
Страница 10: ...Operating Manual RX4770 M2 Contents ...
Страница 14: ...14 Operating Manual RX4770 M2 Preface ...
Страница 28: ...28 Operating Manual RX4770 M2 Functional overview ...
Страница 42: ...42 Operating Manual RX4770 M2 Important information ...
Страница 47: ...RX4770 M2 Operating Manual 47 Hardware installation Figure 2 Mechanical requirements 735 770 mm 100 mm 1 6mm ...
Страница 78: ...78 Operating Manual RX4770 M2 Property and data protection ...
Страница 84: ...84 Operating Manual RX4770 M2 Troubleshooting and tips ...