26
Operating Manual
RX4770 M2
Functional overview
Electrical data (hot-plug power supply unit)
*
Depending on PSU model inserted. Please, refer to your system`s rating plate.
Connection to the mains
The server is connected to the mains with 2 cords as a minimum or up to 4 cords
as a maximum for redundant operation. Each cord connection requires an
appropriate fuse in building installation (see above). Earthed socket outlets
have to be used (protection class I device).
Electrical ratings
*
100 – 240 V / 24 – 16 A or
200 – 240 V / 20 A
Frequency
50 Hz / 60 Hz
Current (basic configuration)
3.7 A (200 V)
Max. current
24 A / 16 A (100 V / 200 V)
Active power min. (typical configuration
1800 W
Active power max. (typical configuration) 1800 W
Apparent power (typical configuration)
1830 VA
Active power max. (max. configuration)
2100 W
Heat emmission
750 W = 2559 Btu/h
1800 W = 6142 Btu/h
2100 W = 7560 Btu/h
Main power fuse
16 A (200 - 240 V) or
20A (100 - 120 V)
Protection class
I
Содержание PRIMERGY RX4770 M2
Страница 1: ...Operating Manual English FUJITSU Server PRIMERGY RX4770 M2 Operating Manual Edition April 2015 ...
Страница 6: ...Operating Manual RX4770 M2 ...
Страница 10: ...Operating Manual RX4770 M2 Contents ...
Страница 14: ...14 Operating Manual RX4770 M2 Preface ...
Страница 28: ...28 Operating Manual RX4770 M2 Functional overview ...
Страница 42: ...42 Operating Manual RX4770 M2 Important information ...
Страница 47: ...RX4770 M2 Operating Manual 47 Hardware installation Figure 2 Mechanical requirements 735 770 mm 100 mm 1 6mm ...
Страница 78: ...78 Operating Manual RX4770 M2 Property and data protection ...
Страница 84: ...84 Operating Manual RX4770 M2 Troubleshooting and tips ...