25
Indoor unit
actuator (servo)
mix. 2nd
(optional ESBE VRG131, ARA639)
DHW tank
max 2000W
If the heat pump heats DHW,
connection of electric heater
is needed. It is used for tank
desinfection and as a backup
heat source.
Otherwise software will not
work correctly and might
completely exhausted
hot water!
M
=
Y
T
N
Y
indoor unit
5X4(6) Cu mm
5X2,5 Cu
3X4 Cu
3X1,5 Cu
XNS
XL
PE
PE
N
N
6*
X1:L1
X1:L3
X1:L2
XOU1:1
XOU1:3
XOU1:2
1* Outdoor temperature sensor
(must be connected; if is not, output water temperature will be
regulated to the default value of equithermal regulation 20°C)
2* Heating water temperature sensor (internal)
3* DHW temperature sensor
(sensor is placed inside of DHW tank; needed for direct DHW heating)
4* Indoor temperature sensor (reference room)
If you would like to use regulation by object temperature,
you have to activate it (Object -> Use an object sensor).
Then the heat pump corrects equithermal curve by indoor temperature.
Sensor types - all of the system ni1000 - 6180ppm/K
1* 2* 3* 4*
*
outdoor unit
XOTUV
X2-10V
XGND
X24+
- by type
*
XB1.1
Xobeh
XOAKU
XB1.2
XOTUV
XcircT
XOBAZ
XNS
XGND
XTven
XTtopv
XC-3
XTTUV
XN-2
XT
obj
X24+
X24-
Xt2okr
XT
aku
X2gnd
XTbaz
Xtvrat
X2-10V
XL-1
Terminal description - indoor unit
X1:L1 - 3 (podle typu)
Lead 400/230V TN-C-S min 25A
XOU1:1 - 3 (podle typu)
Outdoor unit power supply 400V max 16A
XB1.1; XB1.2
External bivalent source control (1. and 2.
stage). 230V max 2A
Xoběh
Circulators power 230V max 6A
XOTUV
DHW heating - DHW tank electric heater power
supply 230V max 10A
XcircT DHW circulation output 230V max 1A
XOAKU
Output for use of secondary source (accu. tank
e.g. solar) 230V max 2A
XOBAZ
Output for 3-way valve and pool circulation
control 230V max 2A
XNS
Input for rate of cost- N, current 200mA
X24+
Output 24V+ ss
X24-
Output 24V - ss
Xgnd
Com for sensors Ni1000.
XTven
Outdoor temperature sensor
XTobj
Indoor temperature sensor
XTtopv
Output water temperature sensor (internal)
XTvrat
Input water temperature sensor (internal)
XTTUV
DHW temperature sensor
XTaku
Secondary source accu. tank temperature sensor
XTbaz
Pool heating water temperature sensor
Xt2okr
Secondary circuit heating water temperature
sensor
XL-1,XN-2,XC-3
Outdoor unit communication
X2gnd
GND pin of actuator (servo) 0-10V 2nd circuit
X2-10V
Signal pin of actuator (servo) 0-10V 2nd circuit