22
ATTENTION
Hold torque wrench at the right angles to the pipe.
This is the only way to the correct function.
rozměr potrubí utahovací moment
6,35 mm (1/4 in.) dia.
9,52 mm (3/8 in.) dia.
12,70 mm (1/2 in.) dia.
15,88 mm (5/8 in.) dia.
19,05 mm (3/4 in.) dia.
14 to 18 N·m (140 to 180 kgf·cm)
33 to 42 N·m (330 to 420 kgf·cm)
50 to 62 N·m (500 to 620 kgf·cm)
63 to 77 N·m (630 to 770 kgf·cm)
100 to 110 N·m (1000 to 1100 kgf·cm)
20 to 25 N·m (200 to 250 kgf·cm)
20 to 25 N·m (200 to 250 kgf·cm)
25 to 30 N·m (250 to 300 kgf·cm)
30 to 35 N·m (300 to 350 kgf·cm)
35 to 40 N·m (350 to 400 kgf·cm)
10 to 12 N·m (100 to 120 kgf·cm)
Torque of stopper plug
Lo
Hi
manometer
service hosepipe
vacuum pump
pipeline
stopper plug
hex key
3-way valvel
service port
stopper plug
service hosepipe
R410A
Outdoor unit
use 4 mm
hex key
3-way
valve
6,35 mm (1/4 in.)
9,52 mm (3/8 in.)
12,70 mm (1/2 in.)
15,88 mm (5/8 in.)
19,05 mm (3/4 in.)
Service port
ATTENTION
t
3-way valve
(liquid)
3-way valve
(gas)
Pipeline to a cone of
ertly!
3-way valve center prop
Apply alkylbenzene oil (HAB)
for refrigerant leak prevention.
Don´t use mineral oils!
Vacuum
(1) Unscrew the plug of 3-way valve service access (gas). Connect it with manometer
which is suitable for vacuum pump and measuring of vacuum.
(2) Run vacuum pump and evacuate for approx. 15-20 minutes. Don´t open 3-way valves!
(3) Do leak test - wean vacuum pump and control manometer after 60 minutes.
(4) If it is necessary add requested amount of the refrigerant.
(5) If you added refrigerant, disconnect service hose (beware refrigerant leaks -
use protective equipment). If you didn´t add any refrigerant, open a 3-way valve
slowly and carefully (liquid) and fill a pipeline by pressure from the unit for
pressure equalization (check a manometer).
Then you can disconnect service hose and screw a plug of service port.
(6) Open both 3-way valve (liquid first). Reinsert plugs to the original post and tighten
it according to the requested moments shown in the table.
(7) Do leak test of refrigerant circuit with a leak detector.
Do not disconnect
vacuum circuit before
you reach at least
refrigerant pressure.