User manual

Installation instruction

Heat Pump Neoré 

08/2016 - All rights and changes reserved

F

Содержание NEORE 11

Страница 1: ...User manual Installation instruction Heat Pump Neoré 08 2016 All rights and changes reserved F ...

Страница 2: ... after a certain time For floor heating be aware of delays thermal exchanges in the rooms due to changes in water temperature 3 6 hrs Nastavení Object section Displays mode of heating cooling object temp circulator state object state main switch operation heating cooling DHW section Displays temp of DHW DHW circulator state heating state main switch DHW heating Overview section Displays important ...

Страница 3: ...ECHNICAL INFORMATION page 5 6 PRINCIPLE OF OPERATION page 6 7 INSTALATION page 6 8 CONNECTING OF THE REFRIGERANT CIRCUIT page 7 9 FIRST START OF THE HEAT PUMP page 8 10 SETTINGS AND SERVICE OF REGULATOR NEORE UNITY COLOR page 9 11 SERVICE EXTENSION POSSIBILITIES page 15 12 MAINTENANCE page 17 13 INSTALATION page 18 14 PROTECTIVE FUNCTION page 34 15 SERVICE INFORMATION page 36 ...

Страница 4: ...HP However efficiency is worse at this temperature COP decreases Heat pump can be also used for cooling At cooling mode is output water temperature limited to condensing temperature Heat pump is not suitable for cooling with water temperature under condensing temperature e g fancoil Low temperature water causes condensation on inner equipment of indoor unit and thereby the damage Suitable cooling ...

Страница 5: ...here is a threat of a serious injury Do not impose air vaporing of the outdoor unit for a long time there is a threat of hypothermia Please follow the conditions set by standards EN 378 4 2008 art 6 5 All parts of the cooling device e g refrigerant oil filter dehydrator insulation material have to be recuperated recycled and or disposed in an ecological way in connection with maintenance repairing...

Страница 6: ...5 ...

Страница 7: ...sor and distributed to the condenser indoor unit Inside of plate condenser of indoor unit refrigerant condenses and it transfers the heat into heating medium heating water Thereafter condensed refrigerant goes into expansion valve and the cycle repeats itself 7 INSTALATION The device has to be mounted by an authorized company otherwise the device can be damaged or an injury can be caused The indoo...

Страница 8: ...y using a drainage pipe and spreading the liquid to a larger area 8 CONNECTING OF REFRIGERATION CIRCUIT Only authorized service can connect he refrigeration circuit see Instalation WARNING Do not try to connect the circuit on your own There is a threat of a serious injury The refrigerant is under pressure of 4 5MPa and temperature is up to 50 C min 300 mm min 600 mm Terén Steel base Terain min 300...

Страница 9: ... every meter height of the heating system Next it is necessary to bleed the circuit thoroughly The bleeding is done by the bleeding screw of the circuit pump or alternatively on the upper threaded piece of the board exchanger When the circuit pump is switched on the board exchanger shall be bled thoroughly After that its noise is decreased The circuit pump shall run for 10 minutes at least before ...

Страница 10: ...d temperature of object bivalent source state and more Main screen summmary Used for switch on off Heat pump DHW heating Displays the overview of most important values and allows entry to states and errors screen button More State errors and entry to screen of supplied power measure button More Calorimeter 10 Settings and service of regulator Neoré Unity Color Basic controls For basic controls of ...

Страница 11: ... is interrupted Too low temperature of outdoor air For heating is fully used bivalent source internal electric heater Economic operation Displayed when output water temp is lower than 45 C and the power is lower than 50 DHW heating is blocked by time schedule Antilegionella DHW tank is heated by electric heater because of legionella desinfection e Status icons Meaning of text shortcuts Attenuation...

Страница 12: ...ropped below safe limits 2 Insufficient water flow water flow dropped below safe limits 3 Outdoor unit disorder 4 Low water pressure water pressure dropped below 0 9 Bar 5 Faulty temperature sensor MX communication unit 2 digit 1 2 Faulty output water temperature sensor 3 4 Faulty input water temperature sensor 3 digit 1 2 Faulty pool temperature sensor 3 4 Faulty secondary circuit temperature sen...

Страница 13: ... of temperature stability without fluctations In Neore heat pump are used two tools for comfort settings of equithermal curve 1 Neo Equitherm Automatic correction write down desired adjustment of heating water temperature without you have to think about which value and how much to change 2 IQ Equitherm Automatic fine tuning of equithermal curve by difference of required and actual temperature of l...

Страница 14: ...ion must be set to ON pg 1 Required DHW temperature required DHW temperature recommended 44 48 C Required DHW hysteresis TUV required hysteresis define temperature difference when starts DHW heating DHW el heating delay define time to DHW heating by heat pump after this time is is DHW heated by electric heater and heat pump is used for object heating Desinfection switch ON OFF DHW tank desinfectio...

Страница 15: ...name webserver login name Webserver password webserver login password Saved data heat pump operation saved data access is possible only from PC Network settings ethernet network connection settings pg 3 Service access access only for service engeneer pg 1 Secondary source enable use of secondary source solid fuel boiler solar panel etc Secondary source tank temp actual temperature in secondary sou...

Страница 16: ...ter IP address of heat pump into your browser address bar The computer must be on the same physical Ethernet network If you want to control heat pump from the Internet network contact your internet provider The default IP address of a heat pump is 192 168 134 176 The username is eneore and password is eneore This address and other settings can be changed in the Settings in the heat pump controller...

Страница 17: ...a Route you have to contact yours heat pummp supplier or apply for openning an account by email at support neota eu Neota Route is a paid service After paying a one time fee you will recieve user name and password which is needed to insert to heat pump web server settings Settings Network settings IMPORTANT NOTICE That the Neota Route service is available is needed to router which is used for heat...

Страница 18: ...ger is very soft and could be damaged Before cleaning of exchanger switch off the main circuit breaker in inside unit The inside unit needs minimal maintenance Use a damp cloth for cleaning its top cover and follow caution if the heat pump is running and energized We recommend to do indoor unit maitenance outside the heating season Check an activity of circulator before the heating season Especial...

Страница 19: ...ion The pressure is 1 6x higher Using of these manometers for convection refrigerants may lead to their destruction These manometers have also different connection Service hose must be specially designed for R410A refrigerant It s used convection vacuum pump with adapter for connecting to R410A refrigerant Leak detector must be homologated for R410A refrigerant Tool s name Manometers Service hose ...

Страница 20: ...outdoor unit IPX4 indoor unit IP40 20 Refrigerant circuit refrigerant HF R410A CH F C HF 50 50 filling by type 2 2 2 5 Maximal pressure 4 2 MPa gas 1 05MPa liquid max working overpressure 2 5bar min working overpressure 0 8bar max working temperature 60 C Refrigerant exchanger freeze The basic frost protection of exchanger refrigerant water is to ensure minimal flow througth exchanger This crash o...

Страница 21: ...ust install professional company authorised by manufacturer Do not try it yourself It may lead to device destruction or injury to persons The indoor unit will hang on the wall fixed to mounting plate It s placement must be done considering possible access to regulatory and protective devices and for service See picture below The outdoor unit will be screwed to the pedestal The pedestal is necessar...

Страница 22: ...ze of pipeline Size of Crimp B mm 6 35 mm 1 4 in 9 52 mm 3 8 in 12 70 mm 1 2 in 15 88 mm 5 8 in 19 05 mm 3 4 in 9 1 13 2 16 6 19 7 24 0 Neoré 8 Attention Don t exceed maximum lenght of connecting pipeline In other case preformance parameters can t be fulfilled and the device could be destroyed ATTENTION ATTENTION Use only the insulation suitable for refrigerant circuits The temperature of pipe sur...

Страница 23: ...ve gas Pipeline to a cone of ertly 3 way valve center prop Apply alkylbenzene oil HAB for refrigerant leak prevention Don t use mineral oils Vacuum 1 Unscrew the plug of 3 way valve service access gas Connect it with manometer which is suitable for vacuum pump and measuring of vacuum 2 Run vacuum pump and evacuate for approx 15 20 minutes Don t open 3 way valves 3 Do leak test wean vacuum pump and...

Страница 24: ... s necessary to use copper pipeline with homologation for R410A refrigerant for connection of inside and outside unit If you work with refrigeration technology you should use protective equipment such as glasses gloves etc 2 This device with R410A refrigerant uses different service connection from convection refrigerants which prevents against connection of unapproved service tool The connection f...

Страница 25: ...11 14 16 Connecting the electric circuit 2 Cross section of power and communication wires mm Model Cross sec of power cable Cross sec of comm cable Breaker capacity A MAX MIN MAX MIN 6 4 2 5 1 5 DANGER DANGEROUS XL XN XC PE N actuator servo mix 2nd circuit optional external power input X1 1 XOU 1 Xobeh Xbazen Xbazen Xbazen 6 X1 1 X1 3 X1 2 XOU 1 XOU 2 XOU 3 S L2 L1 Three phase el connection Three ...

Страница 26: ...Xobeh XOAKU XB1 2 XOTUV XcircT XOBAZ XNS XGND XTven XTtopv XC 3 XTTUV XN 2 XTobj X24 X24 Xt2okr XTaku X2gnd XTbaz Xtvrat X2 10V XL 1 Terminal description indoor unit X1 L1 3 podle typu Lead 400 230V TN C S min 25A XOU1 1 3 podle typu Outdoor unit power supply 400V max 16A XB1 1 XB1 2 External bivalent source control 1 and 2 stage 230V max 2A Xoběh Circulators power 230V max 6A XOTUV DHW heating DH...

Страница 27: ...layer is breached Chipped limescale pieces get into the water and gradually clog refrigerant exchanger and regulation valves Carbon dioxide arises during the build up of limescale and causes occurence of air inside of system and surface corrosion if the conditions are good Moreover it is necessery to fill water missing That is not mostly adapted and it brings the system into further adverse effect...

Страница 28: ...fats oils residual products after welding and soldering The exact procedure is not defined and therefore we recommend for rinsing use softened water max 5 6 N0 if it is possible drinking water without treatment is usable as well add suitable not foaming degreasing detergent into water for remove of fats and oils only cold or hot water is not able to remove fats and oils set maximal water flow all ...

Страница 29: ...ler regulating elements expansion tank check the heating water quality and add chemical substance if needed at the beginning of the heating season Technical possibilities and chemical protection of hot water heating systems Influence of hard not modified water and related corrosion process in heatiting system is generally known There are a lot of manufacturers of heating chemistry and equipments f...

Страница 30: ...company with adequate training Attention desk exchanger can not be contaminated by pool water Use of exchanger is required Example 1 Standard type connection of Neoré heat pump attachement 1 Example 2 Connection with maximal equipment of Neoré heat pump attachement 2 Attention hot water above 60 C from another bivalent source can not get into desk exchanger ...

Страница 31: ...er max 2 4 kW 2 Power supply 3x2 5 mm 230 V max 10A XOTUV 5 Bivalent source impuls 2 3x1 5 mm 230 V max 2A XB1 1 first stage XB1 2 second stage indoor unit XNS XL X1 1 XOU 1 6 L2 L1 L3 XOU1 1 XOU1 3 XOU1 2 1 Legend pipeline Legend elements Input pipeline Temperature sensor NI 1000 6180 Output pipeline Control impulse Refrigerant pipeline Dimension of pipelines fot type NeoRé 8 11 28 mm NeoRé 14 16 ...

Страница 32: ...j X24 X24 XT2okr XTaku X2gnd XTbaz XTvrat X2 10V XL 1 Xobeh XOAKU XOBAZ description wiring recommended terminals 1 Indoor unit 2 Power supply 5x4 mm 2 Sazba 0 5 mm X1 L1 X1 L2 X1 L3 XNS 1 1 Outdoor temperature sensor NI 1000 6180 Sykfy 2x2x0 5 XGND XTven 2 Outdoor unit 2 Power supply 3x4 or 5x4 mm by type XOU1 1 2 3 at 3 phase type 3 1 DHW temperature sensor NI 1000 6180 Sykfy 2x2x0 5 XGND XTTUV 3...

Страница 33: ...tank into system We do not recommend to use hydraulic dynamic pressures flattener anuloid for heat pump connection to the heating system If you use it the efficiency of heat pump becomes worse because of its temperature gradient Anuloid use only for connecting bivalent source to the heating water circuit if is needed In case of use accumulation tank is necessary to ensure the same flow between pri...

Страница 34: ...ty valve 2 5 Bar 4 Manual bleeding valve 5 Pressure sensor 0 4 Bar 6 Electric heater 2kW 7 3 way valve 8 Expansion tank 8l 9 Heating water output 10 DHW heating water output 11 Input water 12 Flowmeter Indoor unit equipment P M 1 12 2 3 4 5 6 6 7 8 9 6 11 10 9 8 7 6 6 6 12 5 4 3 2 1 11 10 ...

Страница 35: ...y accumulated inside of system T freeze protect service access Error autoreset max 5 times Flow control Flow monitoring by outdoor unit power For compliance declared effectivity and ensuring safe operation sufficient water flow is necessary Minimal water flow is defined by relationship among outdoor unit power and required power of circulator Values of minimal water flow are in graph of minimal wa...

Страница 36: ...ard installation is not required to use At installations with often power cut is recommended to set compressor preheat Preheat comp service access Output water temperature limits Limitations of range of water temperature user settings default 20 to 60 C Minimal temperature of output water Maximal temperature of output water service access Compressor restart Compressor protection against frequent s...

Страница 37: ...36 15 Service information for indoor unit Note Outdoor unit service informations are located in separatee manual Content ELECTRIC SCHEMA ERRORS ...

Страница 38: ...t Mounting plates DIMENSIONS 650 mm 565 mm 305 mm A A 650 490 27 563 25 60 320 60 03 03 168 309 9 380 380 O 14 R 7 R 7 35 O 6 290 50 137 5 137 5 137 5 137 5 14 57 53 100 100 POSITION IS NOT USED COULD BE USED MIRROR ...

Страница 39: ...trot 1970 13 M8 L2 L5 L8 FA3 FA6 1 FA6 2 FA6 3 M1 K3 K6 L1 L4 L7 M2 XTUV K1 Xoaku K2 Xobaz K4 XcircT K5 XTtopv XTTUV XTAKU XTobj XTbaz XTvrat X2okr XNS AI1 AI2 AI4 AI6 AI3 AI5 AI8 DI17 Di27 RS232 GNDTX RX DI10 I2 I2 24V 24V 24V 24V XTven XGND AI0 AGNG 24V FS FA3 N FS1 DN 15 pulse PM1 0 4Bar 0 5 3 5V Ratiometric Wilo PWM 15 7 5 Out Out blue Gnd Gnd PWM signal brown COM9 COM13 TNC S 3X400V FA6 1 2 3...

Страница 40: ...r 3 4 Faulty input water temperature sensor 3 digit 1 2 Faulty pool temperature sensor 3 4 Faulty secondary circuit temperature sensor 4 digit 1 2 Faulty outdoor temperature sensor 3 4 Faulty object temperature sensor 5 6 Faulty DHW temperature sensor 7 8 Faulty accumulatice tank temperature sensor First two digits from left indicate critical error in which is heat pump operation stopped or limite...

Страница 41: ...I 4 3 way valve with pipes I0002090004 I 5 Input part I0002090005 I 6 Circulator I0002090006 I 7 Flowmeter I0002090007 I 8 Barometer I0002090008 I 9 Control unit I0002090009 I 10 Low voltage power supply I0002090010 I 11 BTP communication I0002090011 I 12 Breaker specification I0002090012 I 13 Control panel I0002090013 I 1 I 2 I 7 I 8 I 3 I 4 I 6 I 5 I 9 I 10 I 11 I 12 I 13 ...

Страница 42: ...41 ...

Страница 43: ...he heat pump must by installed and during warranty time serviced by authorised company 4 The heat pum check by authorised company is necessary once a year 5 Warranty does not cover damage caused by natural disaster lightning strike non authorised service intervention inappropriate transportation and inappropriate service contrary rules mentioned in the user manual Customer Street City zip code Pho...

Страница 44: ...ss functionality was tested and I was acquained with basic service and maintenance signature Date in Customer Device Street City zip code Phone num Email Serial number Power Bivalent source Location of out unit Addess www neota eu This part belongs to installation company Company representative signature Company Street City zip code Phone num Email Addess ...

Страница 45: ...ntral external 3 way valve If you would like to control DHW by one heat pump helps integrated 3 way valve without cascade driver control set ON Outdoor sen corr correction of value measured by outdoor sensor Indoor sen corr correction of value measured by indoor sensor T Hyster cool w lim sets hysteresis for outdoor unit operation stop when cooling water temp is under limit Comp restart 00 10 outd...