Heat pump, split, single service
Holidays programme, circuit 1
641
Preselection
Period 1 to 8
Period 1
642
Date holidays start (Day / Month)
01.01… 31.12
1
643
Date holidays end (Day / Month)
01.01… 31.12
1
648
Heating schedule during the holidays
Frost protection, Reduced
F r o s t
protection
Holidays programme, circuit 2
If the installation consists of 2 heating circuits (only with the 2nd circuit kit option)
651
Preselection
Period 1 to 8
Period 1
652
Date holidays start (Day / Month)
01.01… 31.12
1
653
Date holidays end (Day / Month)
01.01… 31.12
1
658
Heating schedule during the holidays
Frost protection, Reduced
F r o s t
protection
Heating adjustment, circuit 1
710
Comfort ambient temperature setpoint
from reduced
temperature to 35°C
0,5 °C
20 °C
712
Reduced ambient temperature setpoint
from frost-free temp… to
comfort temperature
0,5 °C
18 °C
714
Frost-free ambient temperature setpoint
from 4°C…
to reduced temperature
0,5 °C
8 °C
Cooling adjustment circuit 1
If the installation is fitted with the cooling kit (only with the cooling kit option)
901
Operating mode
Off, Automatic
Off
902
Comfort ambient temperature setpoint
17...40 °C
0,5 °C
24 °C
907
Release
24h/day, Time
programme HC, Time
programme 5 / Refresh
24h/day
If the installation is fitted with a DHW tank, set the parameter 907 to "Time programme 5 / Cooling" (in order to
activate cooling only during the day and leave the DHW system to operate during the night).
Heating adjustment, Circuit 2
If the installation consists of 2 heating circuits (only with the 2nd circuit kit option)
1010
Comfort ambient temperature setpoint
from reduced
temperature to 35°C
0,5 °C
20 °C
1012
Reduced ambient temperature setpoint
from frost-free temp… to
comfort temperature
0,5 °C
18 °C
1014
Frost-free ambient temperature setpoint
from 4°C… to reduced
temperature
0,5 °C
8 °C
DHW setting (domestic hot water) (only with the DHW kit option)
1610
Comfort setting
reduced setting (line 1612)…
to 65 °C
1
60 °C
The backup electrical system is required to reach this level.
1612
Reduced setting
8 °C...to
comfort setting (line 1610)
1
40 °C
Line
Function
Setting range
or display
Setting
increment
B a s i c
setting