6-2. Model: AOHG24KMTA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
25
30
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
25
—
—
—
—
—
0.893
0.877
20
—
—
—
—
0.917
0.900
0.885
10
—
—
0.966
0.947
0.932
0.914
0.899
7.5
—
0.979
0.970
0.951
0.936
0.918
0.903
5
0.992
0.983
0.974
0.955
0.939
0.922
0.906
0
1.000
0.991
0.981
0.963
0.946
0.930
0.914
Indoor unit is lower than
outdoor unit *2
-5
1.000
0.991
0.981
0.963
0.946
0.930
0.914
-7.5
—
0.991
0.981
0.963
0.946
0.930
0.914
-10
—
—
0.981
0.963
0.946
0.930
0.914
-20
—
—
—
—
0.946
0.930
0.914
-25
—
—
—
—
—
0.930
0.914
HEATING
Pipe length (m)
5
7.5
10
15
20
25
30
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
25
—
—
—
—
—
0.871
0.855
20
—
—
—
—
0.887
0.871
0.855
10
—
—
0.952
0.903
0.887
0.871
0.855
7.5
—
0.976
0.952
0.903
0.887
0.871
0.855
5
1.000
0.976
0.952
0.903
0.887
0.871
0.855
0
1.000
0.976
0.952
0.903
0.887
0.871
0.855
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.971
0.947
0.899
0.883
0.866
0.850
-7.5
—
0.969
0.945
0.897
0.881
0.865
0.849
-10
—
—
0.942
0.894
0.879
0.863
0.847
-20
—
—
—
—
0.869
0.854
0.838
-25
—
—
—
—
—
0.850
0.834
- 48 -
6-2. Model: AOHG24KMTA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG18, 24KMTA
OUTDOOR UNIT
AOHG18, 24KMTA