4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity:
Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity:
Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢
Model: ASHG18KMTA
AFR
m
3
/h
980
Indoor temperature
°CDB
18
21
23
25
27
29
32
°CWB
12
15
16
18
19
21
23
Outdoor temperature
°CDB
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
kW
kW
kW
kW
kW
kW
kW
-10
3.18
2.84
0.46
3.48
3.11
0.46
3.59
3.21
0.46
3.82
3.41
0.47
3.93
3.52
0.47
4.19
3.75
0.48
4.47
3.99
0.48
-5
2.98
2.76
0.55
3.26
3.02
0.55
3.36
3.11
0.56
3.58
3.31
0.56
3.69
3.41
0.57
3.93
3.63
0.58
4.19
3.87
0.58
0
2.78
2.68
0.64
3.05
2.93
0.65
3.14
3.02
0.65
3.34
3.21
0.66
3.44
3.31
0.67
3.67
3.52
0.67
3.91
3.76
0.68
5
3.12
2.81
0.44
3.41
3.07
0.44
3.52
3.17
0.45
3.74
3.37
0.45
3.86
3.47
0.45
4.11
3.70
0.46
4.38
3.94
0.46
10
2.95
2.74
0.52
3.23
3.00
0.53
3.33
3.09
0.53
3.54
3.29
0.54
3.65
3.39
0.54
3.88
3.61
0.55
4.14
3.85
0.55
15
3.83
3.11
0.57
4.19
3.40
0.57
4.32
3.51
0.58
4.60
3.73
0.58
4.74
3.84
0.59
5.05
4.09
0.60
5.38
4.37
0.60
20
4.61
3.45
0.93
5.05
3.77
0.94
5.20
3.89
0.95
5.53
4.13
0.96
5.70
4.26
0.97
6.07
4.54
0.98
6.48
4.84
0.99
25
4.49
3.40
1.05
4.92
3.72
1.06
5.07
3.83
1.07
5.39
4.08
1.08
5.56
4.20
1.09
5.92
4.48
1.10
6.31
4.77
1.11
30
4.35
3.34
1.19
4.76
3.65
1.20
4.91
3.76
1.21
5.22
4.00
1.23
5.38
4.13
1.24
5.73
4.40
1.25
6.11
4.69
1.26
35
4.21
3.28
1.33
4.60
3.59
1.35
4.74
3.69
1.36
5.04
3.93
1.38
5.20
4.05
1.39
5.54
4.32
1.40
5.91
4.60
1.42
40
3.92
3.14
1.42
4.29
3.44
1.44
4.42
3.54
1.45
4.70
3.77
1.47
4.85
3.88
1.48
5.17
4.14
1.50
5.51
4.41
1.51
46
3.45
2.91
1.47
3.78
3.18
1.48
3.90
3.28
1.50
4.14
3.48
1.51
4.27
3.59
1.53
4.55
3.83
1.55
4.85
4.08
1.56
¢
Model: ASHG24KMTA
AFR
m
3
/h
1,170
Indoor temperature
°CDB
18
21
23
25
27
29
32
°CWB
12
15
16
18
19
21
23
Outdoor temperature
°CDB
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
kW
kW
kW
kW
kW
kW
kW
-10
4.34
3.72
0.68
4.75
4.07
0.69
4.90
4.20
0.70
5.21
4.46
0.70
5.37
4.60
0.71
5.72
4.90
0.72
6.10
5.23
0.72
-5
4.07
3.61
0.82
4.46
3.95
0.83
4.59
4.07
0.84
4.88
4.33
0.84
5.03
4.46
0.85
5.36
4.76
0.86
5.72
5.07
0.87
0
3.80
3.50
0.96
4.16
3.83
0.97
4.28
3.95
0.98
4.56
4.20
0.99
4.70
4.33
1.00
5.01
4.61
1.01
5.34
4.92
1.02
5
4.26
3.68
0.65
4.66
4.02
0.66
4.80
4.14
0.67
5.11
4.41
0.67
5.27
4.54
0.68
5.61
4.84
0.69
5.98
5.16
0.69
10
4.03
3.59
0.78
4.41
3.92
0.79
4.54
4.04
0.80
4.83
4.30
0.81
4.98
4.43
0.81
5.30
4.72
0.82
5.65
5.04
0.83
15
5.23
4.07
0.85
5.73
4.45
0.85
5.90
4.59
0.86
6.27
4.88
0.87
6.47
5.03
0.88
6.89
5.36
0.89
7.35
5.71
0.90
20
6.29
4.51
1.39
6.89
4.94
1.41
7.10
5.09
1.42
7.55
5.41
1.44
7.78
5.58
1.45
8.29
5.95
1.46
8.84
6.34
1.48
25
6.14
4.45
1.56
6.71
4.87
1.58
6.92
5.02
1.60
7.36
5.34
1.61
7.59
5.50
1.63
8.08
5.86
1.65
8.62
6.25
1.66
30
5.94
4.37
1.78
6.50
4.78
1.80
6.70
4.93
1.82
7.12
5.24
1.84
7.34
5.40
1.86
7.82
5.75
1.87
8.34
6.13
1.89
35
5.74
4.29
2.00
6.28
4.69
2.02
6.48
4.83
2.04
6.89
5.14
2.06
7.10
5.30
2.08
7.57
5.65
2.10
8.07
6.02
2.12
40
5.36
4.11
2.13
5.86
4.50
2.15
6.04
4.63
2.18
6.42
4.93
2.20
6.62
5.08
2.22
7.05
5.41
2.24
7.52
5.77
2.26
46
4.72
3.80
2.20
5.16
4.16
2.22
5.32
4.29
2.24
5.66
4.56
2.27
5.83
4.70
2.29
6.21
5.01
2.31
6.62
5.34
2.34
- 7 -
4-1. Cooling capacity
4. Capacity table
WALL MOUNTED
ASHG18, 24KMTA
WALL MOUNTED
ASHG18, 24KMTA