6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Models: AOHG07KMCC and AOHG09KMCC
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15
—
—
—
0.872
0.910
10
—
—
0.961
0.886
0.925
7.5
—
0.979
0.965
0.890
0.929
5
0.992
0.983
0.969
0.893
0.933
0
1.000
0.991
0.976
0.901
0.940
Indoor unit is lower than
outdoor unit *2
-5
1.000
0.991
0.976
0.901
0.940
-7.5
—
0.991
0.976
0.901
0.940
-10
—
—
0.976
0.901
0.940
-15
—
—
—
0.901
0.940
HEATING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15
—
—
—
0.832
0.822
10
—
—
0.917
0.832
0.822
7.5
—
0.961
0.917
0.832
0.822
5
1.000
0.961
0.917
0.832
0.822
0
1.000
0.961
0.917
0.832
0.822
Indoor unit is lower than
outdoor unit *2
-5
0.955
0.956
0.912
0.828
0.818
-7.5
—
0.954
0.910
0.826
0.816
-10
—
—
0.908
0.824
0.814
-15
—
—
—
0.815
0.805
- 49 -
6-1. Models: AOHG07KMCC and AOHG09KMCC
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG07-14KMCC
OUTDOOR UNIT
AOHG07-14KMCC