Required Number of Outlets/Sockets
The number of power outlets/sockets required to install the ETERNUS DX depends on the number of enclosures
and power distribution units.
It is recommended that the power cords of the enclosures are connected to the power distribution units that are
installed in the same rack. Secure the necessary number of power outlets within the same rack to avoid connect-
ing power cords to power outlets in different racks. It may be necessary to purchase additional power distribu-
tion units depending on the installation locations of enclosures.
■
Without Power Distribution Units
Four power sockets are required for each frontend enclosure.
Two power sockets are required for every controller enclosure, 2.5" type drive enclosure, and 3.5" type drive en-
closure.
■
With Power Distribution Units
Two power sockets are required for each power distribution unit.
Circuit Protectors
Protection coordination must be secured between the distribution board circuit protectors and the ETERNUS DX
or power distribution units to protect the ETERNUS DX by blocking the failed circuit immediately when a power
supply input error occurs.
Distribution board circuit protectors must satisfy the following required conditions and breaking characteristics.
■
Required Conditions
The distribution board circuit protectors must satisfy the required conditions that are listed below.
Table 16 Required Conditions for Distribution Board Circuit Protectors
Connected device
Power supply voltage
Current capacity
Regions other than
the EMEIA, Central
American, and Car-
ibbean regions
The EMEIA, Central
American, and Car-
ibbean regions
Power distribution unit (AC200-240V, horizontal type)
AC 200 – 240V
30A
—
Power distribution unit (AC200-240V, vertical type)
AC 200 – 240V
30A
—
ETERNUS DX (without power distribution units)
AC 100 – 120V
AC 200 – 240V
15A
16A
1. ETERNUS DX Installation
Outlet/Socket Specifications