Item
ETERNUS DX8700 S3
Environmental condi-
tions
Temperature
Operating
10 – 35°C
Not operating
0 – 50°C
Shipping
-25 – 60°C
Temperature gradient
15°C/h or less
Humidity
Operating
20 – 80%RH
Not operating
8 – 80%RH
Shipping
8 – 90%RH
Humidity gradient
30%/d or less
Maximum wet bulb temperature
29°C
Altitude above sea level
0 – 3,000m
Airborne dust
0.15mg/m
3
or less
Gas concentration tolerance level
Cl
2
: 3.4ppb or less, H
2
S: 7.1ppb or less,
SO
2
: 37ppb or less, NH
3
: 420ppb or less,
NO
2
: 52ppb or less, O
3
: 5ppb or less,
HCl: 6.6ppb or less, HF: 3.6ppb or less
Oil vapor
0.2mg/m
3
or less
Seawater (salt corrosion)
If the ETERNUS DX is installed on the ocean or
premises within 0.5km from the coast, necessary
measures must be taken to prevent salt corro-
sion.
Vibration limit
Operating
400gal
Not operating
1,000gal
Noise emission (*6)
Sound pressure level
60dB (A)
Sound power level
7.7B
*1: For power distribution units, there are multiple types of exteriors. For details, refer to
Optional Power Supply Products" (page 39)
*2: These values are for product ID ETSPDHU / ETSPDHU-L.
*3: These values are for product ID ETSPDJU / ETSPDJU-L.
*4: These values are for product ID ETSPDVU / ETSPDVU-L.
*5: These are values for when 24 drives are installed in a 2.5" type drive or when 12 drives are installed in a
3.5" type drive.
*6: These values are measured when a single frontend enclosure, two controller enclosures, and four drive en-
closures are configured in an environment in which the temperature is 23 ± 2 °C at 0 meters above sea
level.
1. ETERNUS DX Installation
Installation Specifications
13
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide
Copyright 2020 FUJITSU LIMITED
P3AM-9422-13ENZ0
Содержание ETERNUS DX8100 S3
Страница 81: ......