BACnet
®
Gateway for VRF System
INSTRUCTION MANUAL r1.3.2 eng
49/103
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
5.3.26 IU_rr_uu_Exists_Status (Binary Input Object Type)
Check the presence of the specified indoor units in the AC system.
Property Identifier
Property Datatype
Value
ASHRAE UTY-
VBGX
Object_Identifier
BACnetObjectIdentifier
(Binary Input, 10rruu)
R
R
Object_Name
CharacterString
“IU_rr_uu_Exists_Status”
R
R
Object_Type
BACnetObjectType
BINARY_INPUT (3)
R
R
Present_Value
BACnetBinaryPV
INACTIVE (0) / ACTIVE (1)
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Polarity
BACnetPolarity
NORMAL (0)
R
R
Inactive_Text
CharacterString
"Not Exists"
O
R
Active_Text
CharacterString
“Exists”
O
R
Change_Of_State_Time
BACnetDatetime
-
O
R
Change_Of_State_Count
Unsigned
-
O
R
Time_Of_State_Count_Reset
BACnetDatetime
-
O
R
Elapsed_Active_Time
Unsigned
-
O
R
Time_Of_Active_Time_Reset
BACnetDatetime
-
O
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
Alarm_Value
BACnetBinaryPV
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured