En-13
(a) 2-wire type
DIP switch (RC AD SW)...Factory setting “00”
Since the remote controller address settings are automatically con
fi
gured, you do not
need to con
fi
gure them.
If con
fi
guring manually, it is necessary to con
fi
gure both the indoor unit and the remote
controller. For details, please refer to the remote controller installation manual.
(b) 3-wire type
DIP switch (RC AD SW)...Factory setting “00”
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from “00”.
Setting
Setting range
Switch 100
Remote controller
address
00 to 15
Setting
example 00
1
2 3
4
ON
RC AD
Example
If 4 indoor units are connected.
RC AD SW
00
RC AD SW
01
RC AD SW
02
RC AD SW
03
Indoor unit 1
Remote
controller
Indoor unit 2
Indoor unit 3
Indoor unit 4
Set the R.C. address in accordance with the table below.
Indoor unit
R.C. address
DIP SWITCH No.
1
2
3
4
1
00
OFF
OFF
OFF
OFF
2
01
ON
OFF
OFF
OFF
3
02
OFF
ON
OFF
OFF
4
03
ON
ON
OFF
OFF
5
04
OFF
OFF
ON
OFF
6
05
ON
OFF
ON
OFF
7
06
OFF
ON
ON
OFF
8
07
ON
ON
ON
OFF
9
08
OFF
OFF
OFF
ON
10
09
ON
OFF
OFF
ON
11
10
OFF
ON
OFF
ON
12
11
ON
ON
OFF
ON
13
12
OFF
OFF
ON
ON
14
13
ON
OFF
ON
ON
15
14
OFF
ON
ON
ON
16
15
ON
ON
ON
ON
NOTES:
Be sure to set consecutive R.C. address.
The indoor units cannot be operated if a number is skipped.
6. 2. Multiple remote control
Up to 2 remote controllers can be used to operate the indoor units.
CAUTION
Multiple installation method described above is prohibited to combine 3 Wired type
with 2 Wired Type.
A
I.U.
A
B
I.U.
Master
Master Slave
A, B : Remote controller cable. (Refer to 2. 4. Electrical requirement.)
A
≤
500 m, A+B
≤
500 m
7.
FUNCTION SETTING
Refer to the installation manual of remote controller for setting method.
7. 1. Function Details
■
Filter sign
Select appropriate intervals for displaying the
fi
lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
11
00
Standard (2500 hours)
01
Long interval (4400 hours)
02
Short interval (1250 hours)
03
No indication
♦
■
Ceiling height
Select the appropriate ceiling height according to the place of installation.
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
20
00
Standard (3.0 m : 18/24 type)
(3.2 m : 30/36/45/54 type)
♦
01
High ceiling (3.5 m : 18/24 type)
(4.2 m : 30/36/45/54 type)
02
Low ceiling (2.7 m)
The ceiling height values are for the 4-way outlet.
Do not change this setting in the 3-way outlet mode.
■
Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
22
00
4-way
♦
01
3-way
■
Vertical wind direction adjustment range
To prevent draft, change the setting to "Upward" (01).
Note that the air
fl
ow in certain usage conditions may leave the ceiling dirty. In such cases,
the use of the optional “PANEL SPACER KIT” is recommended.
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
23
00
Standard
♦
01
Upward
Standard
Upward
Swing range
Outlet cross section
UP
Ceiling
381798070_IM.indb 13
381798070_IM.indb 13
12/5/2018 9:39:33 AM