background image

FINISHING

(1) Insulate between pipes.

For rear, right, and bottom piping, overlap the connection pipe insulation and indoor
unit pipe insulation and bind them with vinyl tape so that there is no gap.

For left and left rear piping, butt the connection pipe insulation and indoor unit pipe
insulation together and bind them with and vinyl tape so that there is no gap.

For left and left rear piping, wrap the area which accommodates the rear piping storage
section with cloth tape.

For left and left rear piping, bind the connection cord to the top of the pipe with vinyl
tape.

For left and left rear piping, bundle the piping and drain hose together by wrapping
them with cloth tape over within the range of which they fit into the rear piping storage
section.

(2) Temporarily fasten the connection cord along the connection pipe with vinyl tape. (Wrap

to about 1/3 the width of the tape from the bottom of the pipe with tape so that water
does not enter.)

(3) Fasten the connection pipe to the outside wall with saddles, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealant so that rain

water and wind cannot blow in.

(5) Fasten the drain hose to the outside wall, etc.

Fig. 16

Fig. 15

Pipe

(Saddle)

(Outside wall cap)

(Sealant)

(Outdoors)

Pipe

Drain hose

Cloth tape

Wrap with cloth tape

Left piping

Connection cord

Pipe

Drain hose

For connection from the left rear

Connection cord

Wall pipe

Connection
pipe

Check the following:

GOOD

Lifted up

Wave

End in water

Overlap the insulation

Bind the pipes together so
that there is no gap.

Connection pipe
(insulation)

Vinyl tape

Wall

Indoor unit pipe
(insullation)

Drain hose

BAD

BAD

BAD

1.

Check if the piping connections are secure.

2.

Check that the stems of 2-way valve and 3-way valve are closed
fully.

3.

Connect the gauge manifold charge hose to the charging port
of the 3-way valve (side with the projection for pushing in the
valve core).

4.

Open the low pressure side valve of the gauge manifold fully.

5.

Operate the vacuum pump and start pump down.

6.

Slowly loosen the flare nut of the 3-way valve and check if air
enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)

OUTDOOR UNIT

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the
outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do
not operate it during the following work.

Set the unit on a strong stand such as thing made of concrete blocks
to minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trou-
ble.

Connector cover removal

Remove the tapping screws.

Installing the connector cover

(1) After inserting the four hooks, then push upward.
(2) Tighten the tapping screws.

7.

Pump down the system for at least 15 minutes, then check if the
compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

8.

At the end of pump down, close the low pressure side gauge of
the gauge manifold fully and stop the vacuum pump.

9.

Slowly loosen the valve stem of the 3-way valve. When the
compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose
from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)

10. Fully open the valve stems of the 2-way valve and 3-way valve

using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.9 N

 • 

m (30 kgf

 • 

cm) until it

stops turning.)

11. Firmly tighten the 2-way valve and 3-way valve blank cap and

the charging port cap.

Fig. 11

 

CAUTION

(1) R e f r i g e r a n t   m u s t   n o t   b e   d i s c h a r g e d   i n t o

atmosphere.

(2) After connecting the piping , check the joints for

gas leakage with gas leak detector.

OUTDOOR UNIT WIRING

(1) Remove the outdoor unit connector cover.
(2) Bend the end of the cord as shown in the figure.
(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the sheath with a cord clamp.
(5) Install the connector cover.

(1) Match the terminal block numbers and connection

cord colors with those of the indoor unit.
Erroneous wiring may cause burning of the electric
parts.

(2)

Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.

(3) Always fasten the outside covering of the connec-

tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)

(4) Securely earth the power cord plug.

(5)

Do not use the earth screw for an external connector.
Only use for interconnection between two units.

 

CAUTION

35mm

12mm

5mm

5mm

12mm

25mm

Fig. 13

Sheath

Cord clamp

Earth screw

Outdoor unit terminal block

Indoor unit terminal block

Connection cord

Earth screw

Earth screw

Table 4

Tightening torque

Blank cap

19.6 to 24.5 N

 • 

m (200 to 250 kgf

 • 

cm)

Charging port cap

12.3 to 15.7 N

 • 

m (125 to 160 kgf

 • 

cm)

TEST RUNNING

Perform test operation and check items 1 and 2 below.

For the test operation method, refer to the operating manual.

The outdoor unit, may not operate, depending on the room temperature. In this case, press the TEST RUN button on the remote control unit
while the air conditioner is running. (Point the transmitter section of the remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)

To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously
flash slowly.)

1. INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the airflowdirection louver operate normally?
(4) Is the drain normal?

2. OUTDOOR UNIT

(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?

 

WARNING

(1) Install the unit where it will not be tilted by more

than 5°.

(2) When installing the outdoor unit where it may ex-

posed to strong wind, fasten it securely.

Connector cord

Cord clamp

Control box

Fig. 14

Connector cord

Connection cord wiring

Run the connection cord to the rear of the outdoor unit within the 

A

range of the arrows shown in the figure.
(The connector cover becomes difficult to install.)

Fig. 12

Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor
unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.

Pipe length

Additional refrigerant

Table 5

15 m

None

20 m

100 g

Tapping screw

Rear hooks

Connector cover

 

CAUTION

(1) When adding refrigerant, add the refrigerant from

the charging port at the completion of work.

(2) The maximum length of the piping is 20 m. If

the units are further apart than this, correct
operation can not be guaranteed.

Between 15 m and 20 m, when using a connection pipe other than
that in the table, charge additional refrigerant with 20g/1 m as the
criteria.

Control box cover

Transmitter section

Test run button

Fig. 17

P/N 9317265003-01

L    N

3

Drain hose
Saddle

INDOOR UNIT

CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING

(1) Cut a 65 mm diameter hole in the wall at the position shown in (Fig.

5).

(2) When cutting the wall hole at the inside of the installation frame, cut

the hole within the range of the left and right center marks of the
installation frame.
When cutting the wall hole at the outside of the installation frame,
cut the hole at least 10 mm lower.

(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the

inside end.

(4) Always align the center of the wall hole. If misaligned, water leakage

will occur.

(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap,

fasten the cap with vinyl tape, and stick the pipe through the hole.
(The connection pipe is supplied in the installation set.) (Fig. 5)

(6) For left piping and right piping, cut the hole a little lower so that drain

water will flow freely. (Fig. 5)

Fig. 5

Fasten with
vinyl tape

(Wall cap)

(Wall pipe)

(Inside)

Wall

(Outside)

(1) Remove the cord clamp.
(2) Bend the end of the connection cord as shown in the figure.

(1) Match the terminal block numbers and connection

cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the elec-
tric parts.

(2)

Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.

(3) Always fasten the outside covering of the connec-

tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)

(4) Securely earth the power cord plug.

(5)

Do not use the earth screw for an external connector.
Only use for interconnection between two units.

Fig. 10

 CAUTION

(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the connection cord with a cord clamp.

INDOOR UNIT WIRING

Connection cord

40 m

m

12 m

m

60 m

m

12 m

m

5 m

m

5 m

m

Wire cover

Cord clamp

Screw

Connection cord

Insert the tab into the square hole of the
indoor unit and fasten with a screw.

INSTALLING THE WALL HOOK BRACKET

(1) Install the wall hook bracket so that it is correctly positioned horizon-

tally and vertically. If the wall hook bracket is tiled, water will drip to

the floor.

(2) Install the wall hook bracket so that it is strong enough to withstand

the weight of an adult.

Fasten the wall hook bracket to the wall with 6 or more screws through

the holes near the outer edge of the bracket.

Check that there is no rattle at the wall hook bracket.

FORMING THE DRAIN HOSE AND PIPE

 

WARNING

If the wall pipe is not used, the cord interconnecting
the indoor and outdoor units may touch metal and
cause electric leakage.

[Rear piping, Right piping, Bottom piping]

Install the indoor unit piping in the direction of the wall hole and bind
the drain hose and pipe together with vinyl tape. (Fig. 7)

Install the piping so that the drain hose is at the bottom.

Wrap the pipe of the indoor unit that visible from the outside with
decorative tape.

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

Fig. 6

Fig. 7

 

CAUTION

●  

In order to align the drain hose and drain cap, be
sure to insert securely and vertically. ncline insertion
will cause water leakage.

●  

When inserting, be sure not to attach any material
besides water. If any other material is attached, it
will cause deterioration and water leakage.

●  

After removing drain hose, be sure not to forget

mounting drain cap.

●  

Be sure to fix the drain hose with tape to the bottom

of piping.

 

CAUTION

Install the wall hook bracket horizontally and
perpendicularly.

Removal method of drain
hose

 

Remove the screw at the left of
drain hose and pull out drain
hose.

Installation method of
drain hose

 

Vertically insert the drain hose
toward the inside, so that the
drain fixture can accurately
align with the screw hole
around the drain cock.
After inserting and before
replacing, please reinstall and
fix the removed screws.

Right piping

Bind with vinyl tape

Indoor unit drain hose (bottom)

Pipe (top)
Rear piping

Bottom
piping

●   

Be sure to install around the drain hose connector.

●   

As the screw is inside, be sure to use screwdriver treated with

magnet.

Screw

Drain hose

Drain fixture

Screw hole

Drain hose

Screw

Drain cock

Drain fixture

For left piping and left rear piping, align the marks on the wall hook
bracket and shape the connection pipe.

Bend the connection piping at the bend radius of 70 mm or more and
install no more than 35 mm from the wall.

After passing the indoor piping and drain hose through the wall hole,
hang the indoor unit on the hooks at the top and bottom of the wall
hook bracket.

[Installing the indoor unit]

Hang the indoor unit from the hooks at the top of the wall hook bracket.

Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.

Fig. 8

After hooking the indoor unit to the top hook, hook the fittings of the
indoor unit to the two bottom hooks while lowering the unit and
pushing it against the wall.

CONNECTION

(1) Install the outdoor unit wall cap (supplied with the optional installation set

or procured at the site) to the wall pipe.

(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the flare surface and tightening the nut hand

tight, tighten the nut to the specified tightening torque with a torque wrench.
(Table 2)

FLARING

(1) Cut the connection pipe to the necessary

length with a pipe cutter.

(2) Hold the pipe downward so that cuttings

will not enter the pipe and remove the
burrs.

(3) Insert the flare nut onto the pipe and flare

the pipe with a flaring tool.

Insert the flare nut (always use the flare nut
attached to the indoor and outdoor units
respectively) onto the pipe and perform the
flare processing with a flare tool.
Use the special R410A  flare tool, or the conv-
entional (for R22) flare tool.
When using the conventional flare tool, always
use an allowance adjustment gauge and secure
the A dimension shown in table 3 .

CONNECTING THE PIPING

Check if [L] is flared uniformly
and is not cracked or scratched.

Fig. 9

Die

A

Pipe

Top hooks

Indoor unit

Bottom hooks

Wall hook bracket

Indoor unit

Wall hook bracket

(Spacer)

Table 2

Flare nut tightening torque

Tighten with two wrenches.

Torque
wrench

Wrench (fixed)

Flare nut

Indoor unit pipe

Connection pipe

To prevent gas leakage, coat the flare
surface with refrigerator oil.

Table 3

Pipe outside diameter

Flare nut

6.35  mm dia.

9.52  mm dia.

Tightening torque

15.7  to 17.6 N

 • 

m

(160 to 180 kgf

 • 

cm)

29.4 to 41.1 N

 • 

m

(300 to 420 kgf

 • 

cm)

A (mm)

Pipe outside

diameter

ø 6.35 mm (1/4”)

ø 9.52 mm (3/8”)

Flare tool for

R410A, clutch type

0 to 0.5

0 to 0.5

Conventional (R22) flare tool

Clutch type

1.0 to 1.5

1.0 to 1.5

Wing nut type

1.5 to 2.0

1.5 to 2.0

 

CAUTION

(1) Fasten a flare nut with a torque wrench as instructed in this manual. If

fastened too tight, the flare nut may be broken after a long period of time
and cause a leakage of refrigerant.

(2) During installation, make sure that the refrigerant pipe is attached firmly

before you run the compressor. Do not operate the compressor under the
condition of refrigerant piping not attached properly with 2-way or 3-way
valve open. This may cause abnormal pressure in the refrigeration cycle
that leads to breakage and even injury.

Installation method of Drain cap

Use a hexagonal wrench (4mm at op-
posite side) to insert the drain cap, till
the drain cap contacts the tip of drain
cock.

No gap

Hexagonal
wrench

Drain cock

Drain cap

Drain cap

Indoor unit
drain hose

Remove the drain cap by pulling
at the projection at the end of
the cap with pliers, etc.

For left outlet piping, cut off the
piping outlet cutting groove
with a hacksaw.

Center mark

at least 10 mm lower

Center mark

65 mm dia. hole

65 mm dia. hole

at least 10 mm lower

5 to 10 mm low

Wall hook bracket

Tapping screw

Connection pipe
(6.35  mm dia.)

Connection
pipe (9.52 mm dia.)

Align the marks.

Bend (R70) with
a pipe bender

Screw

Wire cover

Screw

Screw

Cord clamp

Connection

cord

Содержание ASYA12LGC

Страница 1: ...SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype Models Indoor unit Outdoor unit AS A07LGC AS A09LGC AS A12LGC AS A14LGC AO R07LGC AO R09LGC AO R12LGC AO R14LGC INVERTER SERVICE INSTRUCTION R410A ...

Страница 2: ... CONTROL 8 COMPRESSOR CONTROL 11 TEST OPERATION CONTROL 10 ELECTRONIC EXPANSION VALVE CONTROL 13 FOUR WAY VALVE EXTENSION SELECT 12 PREVENT TO RESTART FOR 3 MINUTES 3 MINUTES ST 15 MANUAL AUTO OPERATION Indoor unit body operation 14 AUTO RESTART 16 FORCED COOLING OPERATION 18 COIL DRY OPEARTION CONTROL 17 COMPRESSOR PREHEATING 19 DEFROST OPERATION CONTROL 21 10 C HEAT OPERATION 20 OFF DEFROST OPER...

Страница 3: ... DIAGNOSIS FUNCTION 8 APPENDING DATA 9 REPLACEMENT PARTS 10 INSTALLATION MANUAL 4 SELF DIAGNOSIS FUNCTION AND CHECKING POINTS 5 SERIAL SIGNAL DIAGNOSIS 6 IPM PROTECTION 7 TROUBLE SHOOTING OF REFRIGERANT CYCLE 06 01 06 02 06 04 06 05 06 08 1 Function setting 3 Outdoor unit Pressure Value and Total Electric Current Curve 2 Jumper setting of Outdoor unit 5 Capacity Input Data 4 Thermistor Resistance ...

Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...

Страница 5: ... m3 h 750 m3 h AS A07LGC AO R07LGC 2 10 kW 3 00 kW 230 V 50 Hz 2 4 A 3 2 A 6 0 A 7 5 A 0 470 kW 0 660 kW 4 47 kW kW 4 55 kW kW 1 0 L h 750 m3 h 750 m3 h FAN MOTOR POWER SOURCE 230 V High speed INDOOR UNIT Middle speed Low speed Quiet High speed Middle speed Low speed Quiet Cool 1 440 r p m Heat 1 440 r p m Cool 1 500 r p m Heat 1 500 r p m Cool 1 300 r p m Heat 1 300 r p m Cool 1 020 r p m Heat 1 ...

Страница 6: ...th 15 m FULL CHARGE 20 m 900 g R410A 1000 g 1000 g 9 0 kg 1100 g 750 g MAXIMUM PIPING HEIGHT 15m ADDITIONAL REFRIGERANT 20 g m WEIGHT INDOOR UNIT Gross Net Gross Net 10 kg 7 5 kg OUTDOOR UNIT 35 kg 32 kg 44 kg 40 kg 28 kg 25 kg INDOOR UNIT H x W x D H x W x D 260 x 790 x 198 mm OUTDOOR UNIT 540 x 660 x 290 mm 620 x 790 x 298mm DIMENSIONS TYPE Cool heat inverter INDOOR UNIT AS A12LGC OUTDOOR UNIT A...

Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...

Страница 8: ...D I M E N S I O N S Models AS A07LGC AO R07LGC AS A09LGC AO R09LGC AS A12LGC AO R12LGC 02 01 unit mm INDOOR UNIT OUTDOOR UNIT 260 540 198 790 660 290 ...

Страница 9: ...Models AS A14LGC AO R14LGC 02 02 unit mm INDOOR UNIT OUTDOOR UNIT 260 198 790 790 67 298 620 20 ...

Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...

Страница 11: ...Strainer Strainer 3 Way valve Muffler Muffler 4 Way valve Expansion valve Refrigerant direction Heat exchanger indoor unit Heat exchanger outdoor unit Compressor Cooling Heating For AS A07 09 12LGC Refrigerant pipe diameter Liquid 1 4 6 35 mm Gas 3 8 9 52 mm For AS A14LGC Refrigerant pipe diameter Liquid 1 4 6 35 mm Gas 1 2 12 7 mm ...

Страница 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...

Страница 13: ...50V 20A REACTOR REACTOR or THERMISTOR PIPE TEMP THERMISTOR DISCHARGE PIPE TEMP THERMISTOR OUTDOOR TEMP CONTROLLER PCB ASSEMBLY BLACK BLACK BLACK BLACK ORANGE RED YELLOW PINK BLUE BROWN BLUE RED WHITE WHITE WHITE WHITE WHITE WHITE BLUE YELLOW WHITE BLACK RED GRAY GRAY BLACK WHITE RED GREEN GREEN YELLOW 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 5 6 1 2 1 2 1 2 3 4 5 1 2 3 4 1 2 3...

Страница 14: ... or THERMISTOR PIPE TEMP THERMISTOR DISCHARGE PIPE TEMP THERMISTOR OUTDOOR TEMP CONTROLLER PCB ASSEMBLY BLACK BLACK BLACK BLACK ORANGE RED YELLOW PINK BLUE BROWN BLUE RED WHITE WHITE WHITE WHITE WHITE WHITE BLUE YELLOW WHITE BLACK RED GRAY GRAY BLACK WHITE RED GREEN GREEN YELLOW 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 5 6 1 2 1 2 1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 4 5 ...

Страница 15: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...

Страница 16: ...e 52Hz 43Hz 37Hz 28Hz E zone 64Hz 55Hz 49Hz 36Hz F zone 64Hz 55Hz 49Hz 36Hz A zone 96Hz 61Hz 51Hz 33Hz B zone 96Hz 61Hz 51Hz 33Hz C zone 96Hz 61Hz 51Hz 33Hz 12LGC 14LGC D zone 57Hz 42Hz 36Hz 27Hz E zone 57Hz 42Hz 36Hz 27Hz F zone 57Hz 42Hz 36Hz 27Hz A zone 80Hz 49Hz 38Hz 27Hz B zone 80Hz 49Hz 38Hz 27Hz C zone 80Hz 49Hz 38Hz 27Hz D zone 54Hz 38Hz 30Hz 22Hz E zone 54Hz 38Hz 30Hz 22Hz F zone 54Hz 38H...

Страница 17: ...oor temperature Table 2 Compressor Frequency Range Fig 2 Limit of Maximum Frequency based on Outdoor Temperature The room temperature is controlled 2 C higher than the setting temperature for 60 minutes after starting the operation After 60 minutes it is controlled based on the normal setting temperature 05 02 minimum frequency maximum frequency AS A07 09LGC 22Hz 99Hz AS A12LGC 18Hz 130Hz AS A14LG...

Страница 18: ...e Ts 0 5 C Ts 1 5 C Ts 0 5 C Ts 1 5 C Table 3 Compressor frequency Table 4 Indoor fan speed Fig 3 Compressor Control based on Room Temperature Fig 4 Indoor Fan Control 05 03 Operating frequency 37Hz 28Hz 0Hz 07LGC 09LGC X zone J zone Y zone Operating frequency J zone Y zone X zone 33Hz 25Hz 0Hz 12LGC Operating frequency J zone Y zone X zone 27Hz 20Hz 0Hz 14LGC Room Room temperature temperature X z...

Страница 19: ...ic dry Cooling automatic dry TS 2 C TB TS 2 C Monitoring Monitoring Monitoring TB TS 2 C Heating Heating Monitoring When COOING was selected at the air conditioner operates as follow The same operation as COOLING OPERATION of item 1 above is performed When the room temperature has remained at set temperature 1 C for 8 minutes operation is automatically switched to DRY and the same operation as DRY...

Страница 20: ...0 1300 1080 Cooling Hi Hi 840 600 480 1500 Me Me Me Heating Lo Lo 1300 1020 Quiet Quiet 760 Dry S Lo X zone 760 J zone 730 Cool air prevention 3 COOLING OPERATION Switch the airflow AUTO and the indoor fan motor will run according to a room temperature as shown in Figure 6 On the other hand if switched in HIGH QUIET the indoor motor will run at a constant airflow of COOL operation modes QUIET LOW ...

Страница 21: ...ng to a room temperature as shown in Figure 7 On the other hand if switched in HIGH QUIET the indoor motor will run at a constant airflow of HEAT operation modes QUIET LOW MED HIGH as shown in Table 6 6 COOL AIR PREVENTION CONTROL Heating mode 4 DRY OPERATION Refer to the Table 6 During the dry mode operation the fan speed setting can not be changed Fig 7 Airflow change over Heating AUTO TR Ts 1 5...

Страница 22: ...ntrol is operated on the heating mode the fan speed keeps at the higher speed as table 9 without relating to the compressor frequency 05 07 A C D E F A C D E F ZONE 150 730 470 760 470 230 230 200 330 150 650 470 760 680 470 AS A14LGC 870 720 530 870 720 530 300 250 200 300 A C D E F 530 250 200 300 780 720 590 480 Refer to Fig1 rpm Outdoor temperature falls and if it becomes E and F zone Refer to...

Страница 23: ...modes do not set the Air Flow Direction Louver in the Heating range for long period of time since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner During the Cooling and Dry modes if the Air Flow Direction Louvers are left in the heating range for more than 30minutes they will automatically return to position During Monitor operation in AUTO CHA...

Страница 24: ...119Hz AS A14LGC 40Hz 59Hz 72Hz 85Hz 101Hz 110Hz 80sec 60sec 60sec 180sec 60sec 60sec 80sec 60sec 60sec 180sec 60sec 60sec Table 10 Compressor Operation Frequency Range 2 OPEARTION FREQUENCY CONTROL AT START UP The compressor frequency soon after the start up is controlled as shown in the figure 10 Fig 10 Compressor Control at Start up Time Time Time Time Time Time Frequency Time Frequency Frequenc...

Страница 25: ...will be turned on Operation mode Stop mode Set time of timer The program timer allows the OFF timer and ON timer to be used in combination one time Operation mode Operation will start from the timer setting either OFF timer or ON timer whichever is closest to the clock s current timer setting The order of operations is indicated by the arrow in the remote control unit s display SLEEP timer operati...

Страница 26: ...ion In the cooling operation mode When the sleep timer is set the setting temperature is increased 1 C It increases the setting temperature another 1 C after 1 hour After that the setting temperature is not changed and the operation is stopped at the time of timer setting Ts 1 C 2 C Set 60min In the heating operation mode When the sleep timer is set the setting temperature is decreased 1 C It decr...

Страница 27: ...ll continue to run regardless of whether the room temperature sensor detects The test operation mode is released if 60 minutes have passed after setting up the test operation The compressor won t enter operation status for 2 minutes and 20 seconds after the compressor is stopped even if any operation is given At the time when the air conditioner is switched from the cooling mode to heating mode th...

Страница 28: ...NG 18 COIL DRY OPERATION CONTROL The coil dry operation functions by pressing COIL DRY button on the remote controller The coil dry operation is consisted of Fan operation 50 minutes Heating operation 3 minutes and Fan operates for 30 minutes at last before ending the air conditioner operation Table 13 COIL DRY Operating Functions Indoor Fan Speed Compressor Frequency Louver Position Main Unit Ind...

Страница 29: ...Operation AS A07 09 12 14LGC Less than 25 minutes 25 minutes to 4 hours Does not operate Compressor operating time After 4 hours 6 C 3 C 2 CONDITION OF THE DEFROST OPERATION COMPLETION Defrost operation is released when the conditions become as shown in Table 15 Table 15 Defrost Release Condition Release Condition Outdoor heat exchanger temperature sensor value is higher than 16 C or Compressor op...

Страница 30: ... later compressor ON Heating operation start Compressor ON Outdoor heat exchanger temperature Over 16 C or Compressor ON time Over 15 minutes 05 15 Compressor integrating operation Over 25 minutes to below 240 minutes Compressor integrating operation Over 240 minutes Outdoor heat exchanger temperature Below 6 C Outdoor heat exchanger temperature Below 3 C Defrost start Defrost Indicator Operation ...

Страница 31: ...A09 12LGC OFF Defrost Flow Chart Heating operation stop Outdoor heat exchanger temperature Below 4 C and Compressor integrating operation Over 30 minutes Defrost start Defrost Indicater Operation lamp 7 sec ON 2 sec OFF Outdoor heat exchanger temperature Over 16 C or Compressor ON time Over 15 minutes Defrost end 2 OFF DEFROST END CONDITION Release Condition Outdoor heat exchanger temperature sens...

Страница 32: ...ture 2 CURRENT RELEASE CONTROL The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit velue that was set up with the outdoor temperature The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value Table 18 Current Release Operation Value Release Value 05...

Страница 33: ...mode the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor 05 18 AS A07 09LGC AS A12LGC 52Hz or greater 49Hz 48Hz or greater 45Hz 43 49Hz 45Hz 34 40Hz 28Hz 27 36Hz 18Hz 22 28Hz OFF OFF Indoor heat exchange temperature Control System Refer to below It returns to the normal operation Compressor Operation 25Hz 39 Frequency dow...

Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...

Страница 35: ...ng hose side and the ser vice port side are possible to open and close at the same time Thermistor vacuum gauge Fig 4 15 To remove moisture from the refrigerating cycle complete ly it is necessary to perform appropriate vacuum drying For that reason vacuum conditions can be confirmed cer tainly Vacuum valve Fig 4 16 This valve builts in a check valve and it is easily possible to vacuum a refrigera...

Страница 36: ...el with HFC R407C R410A model If you use existing pipes it may cause resolution of compressor oil by remaining mineral oil 3 8 15 88mm R410A 22 29 19 7 25 R22 R407C R22 R407C R22 R407C 19 4 23 20 27 3 4 19 05mm R410A 24 36 24 29 R22 R407C 23 7 29 24 Material Nominal diameter in 1 4 3 8 1 2 5 8 3 4 7 8 1 1 8 1 1 4 1 1 2 1 3 8 1 6 35 9 52 12 70 15 88 19 05 22 22 28 58 31 75 38 10 34 92 25 40 Outside...

Страница 37: ...efrigerant charge Do it always from the liquid phase side Don t charge from the gas phase side Compressor oil is changed Be careful to handle synthetic oil since it resolves easily by moisture and contamination Don t mix new synthetic oil and mineral oil It may cause trouble We developed new synthetic oil since HFC refrigerant doesn t dissolve in mineral for R22 oil 06 03 ...

Страница 38: ...It is necessary to use the vacuum pump which can obtain the high vacuum condition Precaution on Tools Feature 2 New Refrigerant has Approx 1 6 times higher pressure than previous refrigerant R410A High Pressure Different point from previous one Diameter of Service port has been changed from 1 4 Flare to 5 16 Flare It requires the gauge manifold and charge hose exclusively for R410A It requires the...

Страница 39: ...ase out schedule of HCFC according to Montreal protocol 1996 2010 2000 2004 2015 2020 2030 60 40 20 100 Year 80 HCFC consumption of 1989 CFC consumption of 1989 x 2 8 65 35 10 0 5 started control only service use total abolition 100 0 06 05 ...

Страница 40: ...emical compound including chlorine and hydrogen ODP 0 02 01 HCFC Hydro Chloro Fluoro Carbon For example R22 for air conditioner R134a for Car air conditioner HFC3 Hydro Fluoro Carbon R407C for air conditioner Refrigerant characteristics R22 Composition wt R22 100 Boiling Point 40 8 Behavior Pressure at 54 5 C kPa 2 151 Temperature Glide deg 0 ODP 0 055 R407C R32 R125 R134a 23 25 52 43 6 zeotrope 2...

Страница 41: ......

Страница 42: ...del when replacing CAUTION Check if the compressor is suitable for the refrigerant model when replacing Complete welding within 15 minutes after opening the cap when replacing COMPRESSOR Use better grade of material for sliding parts for securing good lubrication of sliding part as HFC refrigerant does not contain chloride Review insulating materials Increase pressure resistance strength CAUTION D...

Страница 43: ...eration lamp and Timer lamp do not light up 2 Self Diagnosis Function Either Operation lamp or Timer lamp is blinking How to operate the self diagnosis function Self diagnosis table and Check points 3 Trouble shooting method Serial signal check IPM protection check Refrigeration cycle diagnosis ...

Страница 44: ... Check if each connector is inserted securely Checking Flow Chart YES AC220 230V YES AC220 230V YES AC260 400V IC5 T1 or IC8 11 defective YES DC5Vp p Pulse wave of 50Hz or 60Hz Controller PCB defective NO NO NO NO NO IC8 T1 or IC6 defective 07 01 Does not connected cable do wrong wiring 3 C9 DC 5V 0 25V YES C10 DC15V 1 5V Is AC input voltage from AC outlet normal Fault of an input power supply Is ...

Страница 45: ...ration lamp Green and Timer lamp Orange 2 Upon pulling out and inserting the AC plug the starts to operates from remote control At this state a normal operation indication is performed 3 By pressing TEST button of remote control Error Indication is indicated only during 3 minutes ST 3 minutes ST 2 minutes 20 seconds from the timing AC plug is ON Lamp display 3 minutes delay Turn off Operating Indi...

Страница 46: ...tdoor cable connection in order If the cable wiring is not abnormal measure the voltage of the outdoor unit terminals and diagnose the defective location Refer to the after mentioned Serial Signal Diagnosis for the voltage measuring method and diagnosis method Diagnosis Point Check the indoor outdoor cable connection in order If the cable wiring is not abnormal measure the voltage of the outdoor u...

Страница 47: ...cally releases when the normal value is detected Diagnosis Point Check thermistor resistance value Refer to Themistor characteristics table Controller PCB defective Diagnosis Point Check thermistor resistance value Refer to Themistor characteristics table Controller PCB defective Diagnosis Point Check thermistor resistance value Refer to Themistor characteristics table Controller PCB defective For...

Страница 48: ...after mentioned refrigerant cycle diagnosis Either the outdoor fan motor abnormal current or location error was detected Permanent stop Diagnosis Point Fan motor connector loose defective contact Fan motor defective Controller PCB defective Compressor location error Outdoor fan error DC motor 0 5 sec 2 times 0 5 sec 3 times 0 5 sec 5 times 0 5 sec 6 times 0 5 sec 5 times 0 5 sec 2 times The indoor...

Страница 49: ...efer to after mentioned refrigerant cycle disagnosis Excessive voltage of DC voltage on PFC circuit in inverter PCB is detected or the excessive current in the circuit is detected Permanent stop Diagnosis Point Controller PCB defective Refer to after mentioned PFC circuit diagnosis PFC circuit error 0 5 sec 2 times 0 5 sec 3 times 0 5 sec 4 times 0 5 sec 7 times 0 5 sec 2 times 0 5 sec 3 times 0 5...

Страница 50: ...rmal Check outdoor unit control unit Check cable wiring of terminal base of indoor and outdoor unit correctly connected as numbered Does voltage AC220 to 230V appear between terminal L and N of indoor unit terminal base Check cable wiring of terminal base Does indoor unit start to operate Conduct the inspection on no operation at all Outdoor unit controller PCB board failure Measure voltage betwee...

Страница 51: ...nd recheck Parts broken Change the broken part Check point 3 Turn on the power and press TEST button on Remote Control Is the outdoor fan rotating Yes Rotating No Not rotating PCB or Compressor defective Check point 4 Operate the unit for certain time and check if the compressor is operating Yes Operating The unit is normal No Not operating IPM or PCB defective Replace PCB Yes Normal No Abnormal I...

Страница 52: ...between U V V W W U If any of the resistance value between U V V W W U is not same as others the compressor is defective Compressor Failure NORMAL AS A07 09LGC Compressor Case Temperature at 20 C 0 740 ohm AS A12LGC Compressor Case Temperature at 20 C 0 710 ohm AS A14LGC Compressor Case Temperature at 25 C 0 477 ohm 2 Checking method of EEV failure Insert the AC plug and start up the operation Che...

Страница 53: ...ING DATA R410A WALL MOUNTED type INVERTER 1 Function setting 2 Jumper setting of Outdoor unit 3 Outdoor unit Pressure Value and Total Electric Current Curve 4 Thermistor Resistance Values 5 Capacity Input Data ...

Страница 54: ...tting Value Standard Lower control 30 00 01 Depending on the installed environment the room temperature sensor may require a correction The settings may be selected as shown in the table below 1 3 Setting Other Functions Factory setting Setting Description Function Number Setting Value Yes No 40 00 01 The following settings are also possible depending on the operating conditions Auto Restart Facto...

Страница 55: ...plicable only to the signals in the FUNCTION SETTING For details on how to set the signal codes through the normal process refer to SELECTING THE REMOTE CONTROL UNIT SIGNAL CODE 1 Press the SET TEMP buttons to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and pro...

Страница 56: ...urn it on again CAUTION After turning off the power wait 10 seconds or more before turning on it again The FUNCTION SETTING doesn t become effective if it doesn t do so Function number Setting value 3 Press the SET TEMP buttons to select the setting the value Press the MODE button to switch between the left and right digits 10 c HEAT Outdoor Unit JP JM2 JM103 JM102 JM101 Normal Preheat 09LGC Highe...

Страница 57: ...ic Current Curve Measure the low pressure with the pressure meter at the service valve Measure the outdoor unit overall current with the current clamp meter at Power Cable In outdoor ambient temparature degC In outdoor ambient temparature degC Low pressure of outdoor unit MPa Low pressure of outdoor unit MPa In outdoor ambient temparature degC In outdoor ambient temparature degC Outdoor total elec...

Страница 58: ...of operation Test mode is released automatically 1 Indoor Outdoor Temperature Outdoor Low Pressure Curve AS A14LGC AS A14LGC 2 Indoor Outdoor Temperature Outdoor Total Electric Current Curve Measure the low pressure with the pressure meter at the service valve Measure the outdoor unit overall current with the current clamp meter at Power Cable In outdoor ambient temparature degC Low pressure of ou...

Страница 59: ...c Current Curve Outdoor ambient temparature degC Outdoor ambient temparature degC High pressure of outdoor unit MPa High pressure of outdoor unit MPa Outdoor ambient temparature degC Outdoor ambient temparature degC Outdoor total electric current A Outdoor total electric current A length 08 06 Measure the high pressure with the pressure meter at the service valve Measure the outdoor unit overall c...

Страница 60: ...omatically 1 Indoor Outdoor Temperature Outdoor High Pressure Curve AS A14LGC AS A14LGC 2 Indoor Outdoor Temperature Outdoor Total Electric Current Curve Outdoor ambient temparature degC High pressure of outdoor unit MPa Outdoor ambient temparature degC Outdoor total electric current A length 08 07 Measure the high pressure with the pressure meter at the service valve Measure the outdoor unit over...

Страница 61: ...2 1 91 15 00 15 96 3 53 40 00 27 09 1 62 20 00 6 090 2 19 20 00 12 59 3 76 45 00 22 20 1 85 25 00 4 869 2 47 25 00 10 00 3 96 50 00 18 29 2 08 30 00 3 918 2 74 30 00 7 990 4 14 55 00 15 15 2 31 35 00 3 173 3 00 35 00 6 423 4 28 60 00 12 62 2 54 40 00 2 586 3 24 40 00 5 192 4 40 65 00 10 56 2 76 45 00 2 120 3 46 45 00 4 222 4 50 70 00 8 878 2 97 50 00 1 747 3 66 50 00 3 451 4 59 75 00 7 498 3 17 55...

Страница 62: ...35 0 39 0 44 0 48 0 48 0 48 1 40 1 33 1 26 1 18 1 05 0 98 0 33 0 37 0 41 0 45 0 45 0 45 Outdoor temperature 18 21 23 25 12 15 16 18 32 23 AFR 12 5 27 19 29 21 CDB 20 25 30 35 40 43 CDB CDB CWB TC PI TC PI TC PI TC PI TC PI 15 16 2 25 2 56 2 93 3 47 4 05 4 41 4 64 4 81 0 99 1 02 1 05 1 09 1 15 1 17 1 19 1 18 2 19 2 50 2 86 3 39 3 96 4 31 4 53 4 69 1 01 1 04 1 07 1 12 1 17 1 20 1 21 1 20 2 14 2 43 2...

Страница 63: ... 0 64 0 64 0 64 1 60 1 52 1 44 1 35 1 20 1 12 0 44 0 50 0 55 0 61 0 61 0 61 Outdoor temperature 18 21 23 25 12 15 16 18 32 23 AFR 12 5 27 19 29 21 CDB 20 25 30 35 40 43 CDB CDB CWB TC PI TC PI TC PI TC PI TC PI 15 16 2 25 2 56 2 93 3 47 4 05 4 41 4 64 4 81 0 99 1 02 1 05 1 09 1 15 1 17 1 19 1 18 2 19 2 50 2 86 3 39 3 96 4 31 4 53 4 69 1 01 1 04 1 07 1 12 1 17 1 20 1 21 1 20 2 14 2 43 2 79 3 31 3 8...

Страница 64: ... 0 91 0 85 0 85 2 20 2 09 1 98 1 86 1 57 1 45 0 61 0 70 0 78 0 86 0 80 0 80 Outdoor temperature 18 21 23 25 12 15 16 18 32 23 AFR 12 5 27 19 29 21 CDB 20 25 30 35 40 43 CDB CDB CWB TC PI TC PI TC PI TC PI TC PI 15 16 3 40 3 76 4 18 4 68 5 05 5 36 5 55 5 54 1 72 1 72 1 72 1 72 1 52 1 51 1 51 1 41 3 32 3 67 4 08 4 57 4 93 5 23 5 42 5 41 1 76 1 76 1 76 1 76 1 55 1 54 1 54 1 44 3 24 3 58 3 98 4 46 4 8...

Страница 65: ... 1 10 1 09 1 07 2 58 2 46 2 34 2 19 1 93 1 76 0 75 0 85 0 94 1 04 1 03 1 01 Outdoor temperature 18 21 23 25 12 15 16 18 32 23 AFR 13 3 27 19 29 21 CDB 20 25 30 35 40 43 CDB CDB CWB TC PI TC PI TC PI TC PI TC PI 15 16 3 26 3 72 4 21 4 85 5 33 5 57 5 66 5 72 1 69 1 77 1 85 1 97 1 91 1 92 1 83 1 77 3 19 3 63 4 11 4 74 5 21 5 43 5 53 5 59 1 72 1 81 1 89 2 02 1 95 1 96 1 87 1 81 3 11 3 54 4 01 4 62 5 0...

Страница 66: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...

Страница 67: ...lter Air Filter Front Panel Receiver Window Clamper Grille Clamper Grille Intake Grille Panel Cover Remote Control Remote Control Holder REPLACEMENT PARTS 09 01 Models AS A07LGC AS A09LGC AS A12LGC AS A14LGC ...

Страница 68: ...Evaporator Assy Joint Pipe Assy Filter Guide Evaporator Holder R Evaporator Holder L Rear Bracket 09 02 REPLACEMENT PARTS Models AS A07LGC AS A09LGC AS A12LGC AS A14LGC ...

Страница 69: ... B Fan Guard Fan Motor Crossflow Fan Assy Shaft Holder C Louver U Louver Z Bracket Panel Casing Motor Cover Louver Gear Holder Louver Gear Motor Step Drain Hose Assy Drain Cap 09 03 REPLACEMENT PARTS Models AS A07LGC AS A09LGC AS A12LGC AS A14LGC ...

Страница 70: ...Display PCB Assy Display Case Power Cord Assy Controller PCB Assy Control Box Box Shield Control Cover Cover Shield 09 04 REPLACEMENT PARTS Models AS A07LGC AS A09LGC AS A12LGC AS A14LGC ...

Страница 71: ...Net Cabinet Left Assy Emblem Switch Cover Valve Bracket Cabinet Right Assy Valve Bracket Cover Motor Bracket Propeller Fan REM Plate Assy Reactor Assy Separator Assy Fan Motor 09 05 REPLACEMENT PARTS Models AO R07LGC AO R09LGC AO R12LGC Fan Ring ...

Страница 72: ...ase Assy Condenser Assy Entrance Pipe Assy Cond 09 06 REPLACEMENT PARTS Models AO R07LGC AO R09LGC Models AO R12LGC Separate Pipe Assy Cond Exit Pipe Compressor Assy 3 way Valve Assy Pulse Motor Valve Assy Expansion Valve Coil Joint Pipe Assy Cond Suction Pipe Assy Muffler 4 way Valve Cushion 2 way Valve Assy Base Assy Condenser Assy Entrance Pipe Assy Cond Discharge Pipe Assy ...

Страница 73: ...Terminal Terminal Cover Controller PCB Assy Sealed Panel Inverter Case Assy PCB Holder 09 07 REPLACEMENT PARTS Models AO R07LGC AO R09LGC AO R12LGC Bracket Terminal Heat sink A Heat sink B ...

Страница 74: ...Top Panel Assy Front Panel Assy Protective Net Condenser Assy Emblem Switch Cover Base Assy Motor Bracket Propeller Fan Fan Motor 09 08 REPLACEMENT PARTS Models AO R14LGC Fan Ring Separate Wall Sub Assy ...

Страница 75: ... Bracket Valve Cover Expansion Valve Coil Bracket Valve 2 Way Valve Assy Pulse Motor Valve Assy Suction Pipe Assy 3 Way Valve Assy Discharge Pipe Assy 4 Way Valve Muffler 3 Way Valve Pipe Cond Sepa Assy Entrance Pipe Assy Compressor Assy Pipe Cond Ex Assy ...

Страница 76: ...09 10 REPLACEMENT PARTS Models AO R14LGC PCB Holder Inverter Case Terminal OUTDOOR UNIT Inverter Case Cover Controller PCB Assy ...

Страница 77: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...

Страница 78: ...e operating and installat ion manuals to the customer CUSTOMER GUIDANCE CAUTION Install the front panel and in take grille securely If installa tion is imperfect the front panel or intake grille may fall off and cause injury Be sure that the top hole of the front panel is hooked securely to the hook of the base Bottom holes six position Front panel Indoor unit Bottom hooks two position PUMP DOWN O...

Страница 79: ...of the installation frame cut the hole within the range of the left and right center marks of the installation frame When cutting the wall hole at the outside of the installation frame cut the hole at least 10 mm lower 3 Cut the hole so that the outside end is lower 5 to 10 mm than the inside end 4 Always align the center of the wall hole If misaligned water leakage will occur 5 Cut the wall pipe ...

Страница 80: ...nt panel is hooked securely to the hook of the base Bottom holes six position Front panel Indoor unit Bottom hooks two position PUMP DOWN OPERATION FORCED COOLING OPERATION To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the cooling operation or forced cooling operation according to the following procedure When the cooling ope...

Страница 81: ... IN THE WALL FOR THE CONNECTING PIPING 1 Cut a 65 mm diameter hole in the wall at the position shown in Fig 5 2 When cutting the wall hole at the inside of the installation frame cut the hole within the range of the left and right center marks of the installation frame When cutting the wall hole at the outside of the installation frame cut the hole at least 10 mm lower 3 Cut the hole so that the o...

Страница 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...

Отзывы: