( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
minimum
frequency
maximum
frequency
maximum
frequency
AS*A07/ 09LGC
22Hz
76Hz
79Hz
AS*A12LGC
18Hz
80Hz
96Hz
AS*A14LGC
18Hz
70Hz
80Hz
Outside air Outside air
temperature temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi
Me
Lo
Quiet
A zone
79Hz
61Hz
52Hz
37Hz
B zone
79Hz
61Hz
52Hz
37Hz
C zone
79Hz
61Hz
52Hz
38Hz
07LGC
09LGC
D zone
52Hz
43Hz
37Hz
28Hz
E zone
64Hz
55Hz
49Hz
36Hz
F zone
64Hz
55Hz
49Hz
36Hz
A zone
96Hz
61Hz
51Hz
33Hz
B zone
96Hz
61Hz
51Hz
33Hz
C zone
96Hz
61Hz
51Hz
33Hz
12LGC
14LGC
D zone
57Hz
42Hz
36Hz
27Hz
E zone
57Hz
42Hz
36Hz
27Hz
F zone
57Hz
42Hz
36Hz
27Hz
A zone
80Hz
49Hz
38Hz
27Hz
B zone
80Hz
49Hz
38Hz
27Hz
C zone
80Hz
49Hz
38Hz
27Hz
D zone
54Hz
38Hz
30Hz
22Hz
E zone
54Hz
38Hz
30Hz
22Hz
F zone
54Hz
38Hz
30Hz
22Hz
( Table 1 : Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
05-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is b2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be
stopped.
Содержание ASYA12LGC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...Models AS A14LGC AO R14LGC 02 02 unit mm INDOOR UNIT OUTDOOR UNIT 260 198 790 790 67 298 620 20 ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 15: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 41: ......
Страница 66: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 77: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...