3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 3.
However, after the compressor is driven, the indoor unit shall run at operation frequency of
70Hz (for AS*A07/09LGC) or 56Hz (for AS*A12LGC) or 40Hz (for AS*A14LGC), for a minute.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table 3 : Compressor frequency )
( Table 4 : Indoor fan speed )
( Fig.3 : Compressor Control based on Room Temperature )
( Fig.4 : Indoor Fan Control )
05-03
Operating
frequency
37Hz
28Hz
0Hz
07LGC
09LGC
X zone
J zone
Y zone
Operating
frequency
J zone
Y zone
X zone
33Hz
25Hz
0Hz
12LGC
Operating
frequency
J zone
Y zone
X zone
27Hz
20Hz
0Hz
14LGC
Room Room
temperature temperature
X zone
J zone
Y zone
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 4)
S-Lo
OFF
10
30
60
180
60
180
60
10
30
(SEC)
X zone
J, Y zone
AS*A07/ 09LGC
620rpm
590rpm
AS*A12LGC
AS*A14LGC
620rpm
590rpm
760rpm
730rpm
Содержание ASYA12LGC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...Models AS A14LGC AO R14LGC 02 02 unit mm INDOOR UNIT OUTDOOR UNIT 260 198 790 790 67 298 620 20 ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 15: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 41: ......
Страница 66: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 77: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2008 Printed in Japan ...