9. ERROR 

CODES

If you use a wireless remote controller, the lamp on the photo detector unit will output error 
codes by way of blinking patterns. If you use a wired remote controller, error codes will ap-
pear on the remote control display. Refer to the lamp blinking patterns and error codes in 
the table. An error display is displayed only during operation.

Error display

Error code

Description

OPERATION 

lamp 

(green)

TIMER 

lamp 

(orange)

ECONOMY 

lamp 

(green)

(1)

(1)

11

Serial communication error

(1)

(2)

12

• Wired remote controller 

communication error

• Server room control 

communication error

(1)

(5)

15

Check run unfinished 
Automatic airflow adjustment error

(1)

(6)

16

Peripheral unit transmission PCB 
connection error

(1)

(8)

18

External communication error

(2)

(1)

21

Unit number or Refrigerant circuit 
address setting error 
[Simultaneous Multi]

(2)

(2)

22

Indoor unit capacity error

(2)

(3)

23

Combination error

(2)

(4)

24

• Connection unit number 

error (indoor secondary unit) 
[Simultaneous Multi]

• Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(2)

(6)

26

Indoor unit address setting error

(2)

(7)

27

Primary unit, secondary unit setup 
error [Simultaneous Multi]

(2)

(9)

29

Connection unit number error in 
wired remote controller system

(3)

(1)

31

Power supply interruption error

(3)

(2)

32

Indoor unit PCB model 
information error

(3)

(3)

33

Indoor unit motor electricity 
consumption detection error

(3)

(5)

35

Manual auto switch error

(3)

(9)

39

Indoor unit power supply error for 
fan motor 

(3)

(10)

3A

Indoor unit communication circuit 
(wired remote controller) error

(4)

(1)

41

Room temp. sensor error 

(4)

(2)

42

Indoor unit heat ex. middle temp. 
sensor error

(4)

(4)

44

Human sensor error

(5)

(1)

51

Indoor unit fan motor error

(5)

(3)

53

Drain pump error

(5)

(4)

54

Electric air cleaner reverse VDD 
error

(5)

(5)

55

Filter set error

Error display

Error code

Description

OPERATION 

lamp 

(green)

TIMER 

lamp 

(orange)

ECONOMY 

lamp 

(green)

(5)

(7)

57

Damper error 

(5)

(8)

58

Intake grille error

(5)

(9)

59

Indoor unit fan motor 2 error
(Left side fan)

(5)

(10)

5A

Indoor unit fan motor 3 error
(Right side fan)

(5)

(15)

5U

Indoor unit error

(6)

(1)

61

Outdoor unit reverse/missing 
phase and wiring error

(6)

(2)

62

Outdoor unit main PCB 
model information error or 
communication error

(6)

(3)

63

Inverter error 

(6)

(4)

64

Active filter error, PFC circuit error 

(6)

(5)

65

Trip terminal L error

(6)

(8)

68

Outdoor unit rush current limiting 
resister temp. rise error

(6)

(10)

6A

Display PCB microcomputers 
communication error

(7)

(1)

71

Discharge temp. sensor error

(7)

(2)

72

Compressor temp. sensor error

(7)

(3)

73

Outdoor unit Heat Ex. liquid temp. 
sensor error

(7)

(4)

74

Outdoor temp. sensor error

(7)

(5)

75

Suction Gas temp. sensor error

(7)

(6)

76

• 2-way valve temp. sensor error
• 3-way valve temp. sensor error

(7)

(7)

77

Heat sink temp. sensor error

(8)

(2)

82

• Sub-cool Heat Ex. gas inlet 

temp. sensor error

• Sub-cool Heat Ex. gas outlet 

temp. sensor error

(8)

(3)

83

Liquid pipe temp. sensor error

(8)

(4)

84

Current sensor error

(8)

(6)

86

• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error

(9)

(4)

94

Trip detection

(9)

(5)

95

Compressor rotor position 
detection error (permanent stop) 

(9)

(7)

97

Outdoor unit fan motor 1 error

(9)

(8)

98

Outdoor unit fan motor 2 error

(9)

(9)

99

4-way valve error

(9)

(10)

9A

Coil (expansion valve) error

(10)

(1)

A1

Discharge temp. error

(10)

(3)

A3

Compressor temp. error

(10)

(4)

A4

High pressure error

9387603095_IM.indb   11

9387603095_IM.indb   11

2019/11/18   15:54:55

2019/11/18   15:54:55

Содержание ASUG09LZAS

Страница 1: ... death Earth Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner c...

Страница 2: ...pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are special Refer to the following table Especially when replacing a conventional refrigerant R22 model with a new refriger ant R410A model always replace the conventional piping and flare nuts with the R...

Страница 3: ...where connection to the outdoor unit or branch box is easy 6 Install the unit where the drain pipe can be easily installed 7 Take servicing etc into consideration and leave the spaces shown in 3 1 1 Installation dimensions Also install the unit where the filter can be removed Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Insta...

Страница 4: ...removing or installing the front panel If the front panel falls there is a risk of injury 3 2 3 Uninstalling the indoor unit Remove the indoor unit from the wall hook bracket as follows 1 Remove the under covers Refer to 3 2 2 Front panel control cover removal and installation 2 Insert your fingers in the opening shown in the figure While pushing down on the lower part of the opening release the h...

Страница 5: ...ith pliers etc No gap Hexagonal wrench Drain cock Drain cap Removing the drain hose Remove the screw at the left of drain hose and pull out drain hose Installing the drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed sc...

Страница 6: ... with the pipe in order to tighten the flare nut correctly Tighten the flare nuts with a torque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servic ing when ...

Страница 7: ... until only the clock is dis played on the remote controller display 2 Press MODE for at least 5 seconds to display the cur rent custom code initially set to A 3 Press TEMP to change the custom code between A B C D Match the code on the display to the air conditioner custom code 4 Press MODE again to return to the clock display The custom code will be changed If no buttons are pressed within 30 se...

Страница 8: ...tion Wire with connector accessory for option Connector CN13 Cable clamp accessory for option Wired remote controller cable Screw large accessory for option Terminal block Tab 7 Replace the control cover front panel and Intake grille 5 FUNCTION SETTING Perform the Function setting according to the installation conditions using the remote controller CAUTION Confirm whether the wiring work for outdo...

Страница 9: ...door unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Function number Setting value Setting description 49 00 Disable 01 Enable 02 Remote controller 00 When the outdoor unit is stopped the indoor unit fan operates continuously following the setting on the remote controller 01 When the outdoor unit is stopped the indoor unit fan operates intermittently at ...

Страница 10: ...trol unit normal 2 Does each lamp light normally 3 Do air flow direction louvers operate normally 4 Is the drain normal 5 Do not have an abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time Operation method Before starting the test run wait for 1 minute after connecting the power supply By the wireless remote controller To start the test run ...

Страница 11: ...eat ex middle temp sensor error 4 4 44 Human sensor error 5 1 51 Indoor unit fan motor error 5 3 53 Drain pump error 5 4 54 Electric air cleaner reverse VDD error 5 5 55 Filter set error Error display Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 5 7 57 Damper error 5 8 58 Intake grille error 5 9 59 Indoor unit fan motor 2 error Left side fan 5 10 5A Indoor unit ...

Страница 12: ...re error 13 2 J2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Error display on the indoor unit OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indicator lamp green 9387603095_IM indb 12 9387603095_IM indb 12 2019 11 18 15 54 55 2019 11 18 15 54 55 ...