 5.1. Function details

 

Filter sign

Select appropriate intervals for displaying the 

fi

 lter sign on the indoor unit according to the 

estimated amount of dust in the air of the room.
If the indication is not required, select “No indication” (03).

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

11

00

Standard (400 hours)

01

Long interval (1000 hours)

02

Short interval (200 hours)

03

No indication

 

Auto restart

Enable or disable automatic restart after a power interruption.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

40

00

Enable

01

Disable

* Auto restart is an emergency function such as for power outage etc. Do not attempt to 

use this function in normal operation. Be sure to operate the unit by remote controller or 
external device.

 

Room temperature sensor switching

(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” (01).

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

42

00

Indoor unit

01

Both

00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller

 

Remote controller custom code

(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

44

00

A

01

B

02

C

03

D

 

External input control

“Operation/Stop” mode or “Forced stop” mode can be selected.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

46

00

Operation/Stop mode 1 (R.C. enabled)

01

(Setting prohibited)

02

Forced stop mode

03

Operation/Stop mode 2 (R.C. disabled)

 

Room temperature sensor switching (Aux.)

To use the temperature sensor on the wired remote controller only, change the setting to “Wired 
remote controller” (01). This function will only work if the function setting 42 is set at “Both” (01)

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

48

00

Both

01

Wired remote controller

 

Indoor unit fan control for energy saving for cooling

Enables or disables the power-saving function by controlling the indoor unit fan rotation when 
the outdoor unit is stopped during cooling operation.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

49

00

Disable

01

Enable

02

Remote controller

00: When the outdoor unit is stopped, the indoor unit fan operates continuously following 

the setting on the remote controller.

01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very 

low speed.

02: Enable or disable this function by remote controller setting.

*When using a wired remote controller without Indoor unit fan control for energy saving for 

cooling function, or when connecting a single split converter, the setting cannot be made 

by using the remote controller. Set to (00) or (01). 

 To con

fi

 rm if the remote controller has this function, refer to the operating manual of each 

remote controller.

 

Setting record

Record any changes to the settings in the following table.

Function 

number

Setting description

Setting value

11

Filter sign

40

Auto restart

42

Room temperature sensor switching

44

Remote controller custom code

46

External input control
The rotary switch on the “External input and output PCB”

48

Room temperature sensor switching (Aux.)

49

Indoor unit fan control for energy saving for cooling

After completing the Function Setting, be sure to disconnect the power supply and then recon-
nect it.

 5.2. Temperature correction

NOTES:

When changing Function 95, perform this setting before other Room temp. control settings 
(Function 30, 31, 35, 36).
If Function 95 is not set 

fi

 rst, Room temperature control settings (Function 30, 31, 35, 36) 

will be reset and you must re-do them again.

 

Heat Insulation condition (building insulation)

Heat insulation conditions differ according to the installed environment.
“Standard insulation” (00) allows system to rapidly respond to the cooling or heating load 
changes.
“High insulation” (01) is when the heat insulation structure of the building is high and does 
not require system to rapidly respond to cooling or heating load changes.
When “High insulation” (01) is selected;
•  Overheating (overcooling) is prevented at the start-up.
•  All room temp. control settings (Function 30, 31, 35, 36) will reset to “No correction” [0.0°F 

(0.0°C)].

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

95

00

Standard insulation

01

High insulation

9387603095_IM.indb   9

9387603095_IM.indb   9

2019/11/18   15:54:55

2019/11/18   15:54:55

Содержание ASUG09LZAS

Страница 1: ... death Earth Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner c...

Страница 2: ...pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are special Refer to the following table Especially when replacing a conventional refrigerant R22 model with a new refriger ant R410A model always replace the conventional piping and flare nuts with the R...

Страница 3: ...where connection to the outdoor unit or branch box is easy 6 Install the unit where the drain pipe can be easily installed 7 Take servicing etc into consideration and leave the spaces shown in 3 1 1 Installation dimensions Also install the unit where the filter can be removed Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Insta...

Страница 4: ...removing or installing the front panel If the front panel falls there is a risk of injury 3 2 3 Uninstalling the indoor unit Remove the indoor unit from the wall hook bracket as follows 1 Remove the under covers Refer to 3 2 2 Front panel control cover removal and installation 2 Insert your fingers in the opening shown in the figure While pushing down on the lower part of the opening release the h...

Страница 5: ...ith pliers etc No gap Hexagonal wrench Drain cock Drain cap Removing the drain hose Remove the screw at the left of drain hose and pull out drain hose Installing the drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed sc...

Страница 6: ... with the pipe in order to tighten the flare nut correctly Tighten the flare nuts with a torque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servic ing when ...

Страница 7: ... until only the clock is dis played on the remote controller display 2 Press MODE for at least 5 seconds to display the cur rent custom code initially set to A 3 Press TEMP to change the custom code between A B C D Match the code on the display to the air conditioner custom code 4 Press MODE again to return to the clock display The custom code will be changed If no buttons are pressed within 30 se...

Страница 8: ...tion Wire with connector accessory for option Connector CN13 Cable clamp accessory for option Wired remote controller cable Screw large accessory for option Terminal block Tab 7 Replace the control cover front panel and Intake grille 5 FUNCTION SETTING Perform the Function setting according to the installation conditions using the remote controller CAUTION Confirm whether the wiring work for outdo...

Страница 9: ...door unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Function number Setting value Setting description 49 00 Disable 01 Enable 02 Remote controller 00 When the outdoor unit is stopped the indoor unit fan operates continuously following the setting on the remote controller 01 When the outdoor unit is stopped the indoor unit fan operates intermittently at ...

Страница 10: ...trol unit normal 2 Does each lamp light normally 3 Do air flow direction louvers operate normally 4 Is the drain normal 5 Do not have an abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time Operation method Before starting the test run wait for 1 minute after connecting the power supply By the wireless remote controller To start the test run ...

Страница 11: ...eat ex middle temp sensor error 4 4 44 Human sensor error 5 1 51 Indoor unit fan motor error 5 3 53 Drain pump error 5 4 54 Electric air cleaner reverse VDD error 5 5 55 Filter set error Error display Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 5 7 57 Damper error 5 8 58 Intake grille error 5 9 59 Indoor unit fan motor 2 error Left side fan 5 10 5A Indoor unit ...

Страница 12: ...re error 13 2 J2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Error display on the indoor unit OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indicator lamp green 9387603095_IM indb 12 9387603095_IM indb 12 2019 11 18 15 54 55 2019 11 18 15 54 55 ...

Отзывы: