CUSTOMER GUIDANCE

 WARNING

(1) The rated voltage of this product is 208/230 V AC

60 Hz.

(2) Before turning on the power, check if the voltage

is within the 208 V-10% to 230V+10% range.

(3) Always use a special branch circuit and install a

special receptacle to supply power to the room
air conditioner.

(4) Use a circuit breaker and receptacle matched to

the capacity of the air conditioner.

(5) Do not extend the power cord.

(6) Perform wiring work in accordance with stand-

ards so that the air conditioner can be operated
safely and positively.

(7) Install a leakage circuit breaker in accordance with

the related laws and regulations and electric com-
pany standards.

 CAUTION

(1) The power source capacity must be the sum of

the air conditioner current and the current of other
electrical appliances. When the current contracted
capacity is insufficient, change the contracted ca-
pacity.

(2) When the voltage is low and the air conditioner is

difficult to start, contact the power company the
voltage raised.

Explain the following to the customer in accordance with the operat-
ing manual:
(1) Starting and stopping method, operation switching, temperature

adjustment, timer, air flow switching, and other remote control unit
operations.

(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation manuals to the customer.

POWER

TEST RUNNING

Perform test operation and check items 1 and 2 below.

For the test operation method, refer to the operating manual.

The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit
while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)

To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously
flash slowly.)

1. INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?

2. OUTDOOR UNIT

(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?

Fig. 18

Transmitter section

Test run button

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or
forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced
cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the

low-pressure valve slightly.

(2) Close the valve stem of 2 way valve completely.
(3) Start the cooling operation or following forced cooling operation.

When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5) Stop the operation.

• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
  (It is not necessary to press on keeping for more than 10 seconds.)

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.

Содержание ASU15RLQ/AOU15RLQ

Страница 1: ...des Connect all wiring tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall ...

Страница 2: ...o 38 bar for low pressure To increase pressure resistance the hose material and base size were changed A conventional vacuum pump can be used by installing a vacuum pump adapter Special gas leakage detector for HFC refrigerant R410A Tool name Gauge manifold Charge hose Vacuum pump Gas leakage detector Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of ...

Страница 3: ... the table below Between 49 ft 15 m and 66 ft 20 m when using a connection pipe other than that in the table charge additional refrigerant with 0 2 oz ft 20g 1 m as the criteria 2 ADDITIONALMATERIALSREQUIREDFOR INSTALLATION A Refrigeration armored tape B Insulated staples or clamps for connecting wire See your local electrical codes C Putty D Refrigeration lubricant E Clamps or saddles to secure r...

Страница 4: ...rear and both sides WARNING Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall CAUTION 1 Do not install where there is the danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the u...

Страница 5: ...ht hand side Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Fig 3 Install the piping so that the drain hose is at the bottom Wrap the pipes of the indoor unit that are visible from the outside with decorative tape For Left rear piping Left piping Interchange the drain cap and the drai...

Страница 6: ...ttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare the pipe with a flaring tool Check if L is flared uniformly and is not cracked or scratched L dimension Thin pipe 1 4 6 35 mm dia 1 16 1 4 to 1 7 mm Thick pipe 1 2 12 7 mm dia 5 64 1 9 to 2 2 mm Flare nut 1 4 6 35 mm dia 1 2 12 7 mm dia Tightening torque 11 57 to 13 02 ft lbs 160 to 180 kgf cm 36 17 ...

Страница 7: ... the end of pump down close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump 9 Slowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnected it ...

Страница 8: ...Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trade size for this unit is 1 2 12 7 mm The connec tor can be bought at a hardware store Refer to How to connect wiring to the terminals for instructions on connecting depend ing on the wire type you are using The fuse located in the outdoor unit provides power supply pro tection and...

Страница 9: ...lamp Connection cord Screw Connection cord Screw Cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using pliers bend the solid wire to form a loop suitable for the termi nal screw 4 Shape the loop ...

Страница 10: ...with cloth tape Left piping Connection cord Pipe Drain hose For connection from the left rear Connection cord Drain hose Wall pipe Connection pipe FRONT PANEL REMOVAL AND INSTALLATION THE INTAKE GRILLE REMOVAL 1 Open the intake grille 2 Pull down the knob 3 Lift the intake grille upward until the axle at the top of the intake grille is removed THE INTAKE GRILLE INSTALLATION 1 The fixing axle of th...

Страница 11: ...atched by parts or draw it hard Or it may result troubles to the air conditioner 4 Avoid place in direct sunlight 5 Select place that will not be affected by the heat from a stove etc 6 Insure the length of wire is not over the recommended maxuim length 7 Before setting up the wired remote control unit please confirm whether air conditioner can receive the signal 1 FRONT PANEL AND CONTROL UNIT REM...

Страница 12: ...wire clamper and screws to fasten wire 3 Cut off part of the control unit and thread wire through 3 FRONT PANEL AND CONTROL UNIT INSTALLATION Install Front panel and Control unit by the reverse procedures as stated in 1 FRONT PANEL AND CONTROL UNIT REMOVAL CIRCUIT BOARD SCREW CONNECTOR TO RENOTE CONNTROL UNIT CUT CLAMPER ...

Страница 13: ...ration of each button on the remote control unit normal 2 Does each lamp light normally 3 Do the air flow direction louver operate normally 4 Is the drain normal 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage Fig 18 Transmitter section Test run button PUMP DOWN OPERATION FOR...

Страница 14: ...ter unit wire harness to the terminal correctly please refer to Fig 19 to adjust the length of the part of Inter unit Wire harness ahead from conduit holder 5 1 2 140mm 15 16 25mm 15 16 25mm 4 3 16 105mm 1 1 14AWG EARTH WIRE CONDUIT PLATE CONDUIT CONNECTOR Fig 19 ...

Страница 15: ...t be affected by the heat from a stove etc 1 REMOTE CONTROL UNIT HOLDER INSTALLATION Install the remote control unit with a distance of 23 ft 7 m between the remote control unit and the photocell as the criteria However when installing the remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control ...

Отзывы: