(1) Cut a 3-2/16’’(80 mm) diameter hole in the wall at the position shown

in (Fig.1).

(2) When cutting the wall hole at the inside of the wall hook bracket,

cut the hole within the range of the left and right center marks
3/8’’(10 mm) below the installation frame.

     When cutting the wall hole at the outside of the wall hook bracket,

cut the hole at least 3/8’’(10 mm) below less.

(3) Cut the hole so that the outside end is lower 3/16’’ to 3/8’’ (5 to 10 mm)

than the inside end.

(4) Always align the center of the wall hole. If misaligned, water leak-

age will occur.

(5) Cut the wall pipe to match the wall thickness, stick it into the wall

cap, fasten the cap with vinyl tape, and stick the pipe through the
hole. (The connection pipe is supplied in the installation set.)
(Fig.1)

(6) For left piping and right piping, cut the hole a little lower so that

drain water will flow freely. (Fig.1)

Fig. 1

(1) Install the wall hook bracket so that it is correctly positioned hori-

zontally and vertically. If the wall hook bracket is titled, water will
drip to the floor.

(2) Install the wall hook bracket so that it is strong enough to with-

stand the weight of an adult.

Fasten the wall hook bracket to the wall with 6 or more screws
through the holes near the outer edge of the bracket.

Check that there is no rattle at the wall hook bracket.

Fig. 2

2.

 INSTALLING THE WALL HOOK BRACKET

INDOOR UNIT

1.

 CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING

3.

 FORMING THE DRAIN HOSE AND PIPE

Wall hook
bracket

Counter weight

Wall hook bracket

Tapping screw

Center notch

String

Hook

 CAUTION

Install the wall hook bracket horizontally and perpen-
dicularly.

 WARNING

If the wall pipe is not used, the cord interconnecting
the indoor and outdoor units may touch metal and
cause electric leakage.

Fasten with
vinyl tape

(Wall cap)

(Wall pipe)

(Inside)

Wall

(Outside)

Lower

3-2/16’’(80 mm)
dia. hole

Center mark

3/8’’(10 mm)
or over

3/16’’ to 3/8’’
(5 to 10 mm)
low

3/8’’(10 mm)
or over

Lower

3-2/16’’(80 mm) dia. hole
(A 2-9/16’’(65mm)
diameter hole is
possible for the right-
hand side.)

[Rear piping, Right piping, Bottom piping]

Install the indoor unit piping in the direction of the wall hole and
bind the drain hose and pipe together with vinyl tape. (Fig. 3)

Install the piping so that the drain hose is at the bottom.

Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

Fig. 3

Drain cap

Indoor unit
drain hose

Remove the drain cap by pulling
at the projection at the end of
the cap with pliers, etc.

For left outlet piping, cut off the
piping outlet cutting groove
with a hacksaw.

Right piping

Bind with vinyl tape

Indoor unit drain hose
(bottom)

Pipe (top)
Rear piping

Bottom

piping

Removal method of drain
hose

Remove the screw at the left of
drain hose and pull out drain
hose.

Installation method of
drain hose

Vertically insert the drain hose
toward the inside, so that the
drain fixture (blue) can accu-
rately align with the screw hole
around the drain cock.
After inserting and before re-
placing, please reinstall and fix
the removed screws.

●   

Be sure to install around the drain hose connector.

●   

As the screw is inside, be sure to use screwdriver treated with magnet.

Screw

Drain hose

Drain fixture
(blue)

Screw hole

Drain hose

Screw

Drain cock

Drain fixture (blue)

 CAUTION

(1)

  

In order to align the drain hose and drain cap, be

sure to insert securely and vertically. Incline in-
sertion will cause water leakage.

(2)

  

When inserting, be sure not to attach any mate-

rial besides water. If any other material is attached,
it will cause deterioration and water leakage.

(3)

  

After removing drain hose, be sure not to forget

mounting drain cap.

(4)

  

Be sure to fix the drain hose with tape to the bot-

tom of piping.

(5)

  

Prevent drain water frozen under low tempera-

ture environment.

When installing indoor unit's drain hose outdoors,
necessary measure for frost protection should be
taken to prevent drain water frozen.

  

 Under low temperature environment (when out-

door temperature under 32 °F), after cooling op-
eration is executed, water in the drain hose could
be frozen.
Once drain water is frozen, the drain hose will
be blocked and water leakage may be resulted
for indoor unit.

Содержание ASU15RLQ/AOU15RLQ

Страница 1: ...des Connect all wiring tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall ...

Страница 2: ...o 38 bar for low pressure To increase pressure resistance the hose material and base size were changed A conventional vacuum pump can be used by installing a vacuum pump adapter Special gas leakage detector for HFC refrigerant R410A Tool name Gauge manifold Charge hose Vacuum pump Gas leakage detector Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of ...

Страница 3: ... the table below Between 49 ft 15 m and 66 ft 20 m when using a connection pipe other than that in the table charge additional refrigerant with 0 2 oz ft 20g 1 m as the criteria 2 ADDITIONALMATERIALSREQUIREDFOR INSTALLATION A Refrigeration armored tape B Insulated staples or clamps for connecting wire See your local electrical codes C Putty D Refrigeration lubricant E Clamps or saddles to secure r...

Страница 4: ...rear and both sides WARNING Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall CAUTION 1 Do not install where there is the danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the u...

Страница 5: ...ht hand side Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Fig 3 Install the piping so that the drain hose is at the bottom Wrap the pipes of the indoor unit that are visible from the outside with decorative tape For Left rear piping Left piping Interchange the drain cap and the drai...

Страница 6: ...ttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare the pipe with a flaring tool Check if L is flared uniformly and is not cracked or scratched L dimension Thin pipe 1 4 6 35 mm dia 1 16 1 4 to 1 7 mm Thick pipe 1 2 12 7 mm dia 5 64 1 9 to 2 2 mm Flare nut 1 4 6 35 mm dia 1 2 12 7 mm dia Tightening torque 11 57 to 13 02 ft lbs 160 to 180 kgf cm 36 17 ...

Страница 7: ... the end of pump down close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump 9 Slowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnected it ...

Страница 8: ...Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trade size for this unit is 1 2 12 7 mm The connec tor can be bought at a hardware store Refer to How to connect wiring to the terminals for instructions on connecting depend ing on the wire type you are using The fuse located in the outdoor unit provides power supply pro tection and...

Страница 9: ...lamp Connection cord Screw Connection cord Screw Cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using pliers bend the solid wire to form a loop suitable for the termi nal screw 4 Shape the loop ...

Страница 10: ...with cloth tape Left piping Connection cord Pipe Drain hose For connection from the left rear Connection cord Drain hose Wall pipe Connection pipe FRONT PANEL REMOVAL AND INSTALLATION THE INTAKE GRILLE REMOVAL 1 Open the intake grille 2 Pull down the knob 3 Lift the intake grille upward until the axle at the top of the intake grille is removed THE INTAKE GRILLE INSTALLATION 1 The fixing axle of th...

Страница 11: ...atched by parts or draw it hard Or it may result troubles to the air conditioner 4 Avoid place in direct sunlight 5 Select place that will not be affected by the heat from a stove etc 6 Insure the length of wire is not over the recommended maxuim length 7 Before setting up the wired remote control unit please confirm whether air conditioner can receive the signal 1 FRONT PANEL AND CONTROL UNIT REM...

Страница 12: ...wire clamper and screws to fasten wire 3 Cut off part of the control unit and thread wire through 3 FRONT PANEL AND CONTROL UNIT INSTALLATION Install Front panel and Control unit by the reverse procedures as stated in 1 FRONT PANEL AND CONTROL UNIT REMOVAL CIRCUIT BOARD SCREW CONNECTOR TO RENOTE CONNTROL UNIT CUT CLAMPER ...

Страница 13: ...ration of each button on the remote control unit normal 2 Does each lamp light normally 3 Do the air flow direction louver operate normally 4 Is the drain normal 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage Fig 18 Transmitter section Test run button PUMP DOWN OPERATION FOR...

Страница 14: ...ter unit wire harness to the terminal correctly please refer to Fig 19 to adjust the length of the part of Inter unit Wire harness ahead from conduit holder 5 1 2 140mm 15 16 25mm 15 16 25mm 4 3 16 105mm 1 1 14AWG EARTH WIRE CONDUIT PLATE CONDUIT CONNECTOR Fig 19 ...

Страница 15: ...t be affected by the heat from a stove etc 1 REMOTE CONTROL UNIT HOLDER INSTALLATION Install the remote control unit with a distance of 23 ft 7 m between the remote control unit and the photocell as the criteria However when installing the remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control ...

Отзывы: