11. Safety devices
Type of protection
Protection form
Model
AOUH09LPAS1
Circuit protection
Current fuse (Main PCB)
250 V, 15 A
250 V, 5 A
Fan motor
protection
Thermal protection
Activate
217±32 °F (103±18 °C)
Fan motor stop
Reset
203±32 °F (95±18 °C)
Fan motor restart
Compressor
protection
Terminal protection program
(Discharge temp.)
Activate
230 °F (110 °C)
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection program
(Outdoor temp.)
(Only in COOL or DRY mode)
Activate
5 °F (-15°C)
Compressor stop
Reset
14 °F (-10°C)
Compressor restart
Type of protection
Protection form
Model
AOUH12LPAS1
Circuit protection
Current fuse (Main PCB)
250 V, 15 A
250 V, 5 A
Fan motor
protection
Thermal protection program
Activate
217±32 °F (103±18°C)
Fan motor stop
Reset
203±32 °F (95±18°C)
Fan motor restart
Compressor
protection
Thermal protection program
(Discharge temp.)
Activate
230 °F (110 °C)
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection program
(Outdoor temp.)
(Only in COOL or DRY mode)
Activate
5 °F (-15°C)
Compressor stop
Reset
14 °F (-10°C)
Compressor restart
- 79 -
11. Safety devices
OUTDOOR UNIT
AOUH09-12LPAS1