6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Model: AOUH09LPAS1
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5
7.5
10
15
20
ft
16
25
33
49
66
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
—
—
—
0.880
0.918
10
33
—
—
0.970
0.894
0.933
7.5
25
—
0.988
0.974
0.898
0.937
5
16
1.001
0.992
0.978
0.901
0.941
0
0
1.009
1.000
0.985
0.909
0.949
Indoor unit is lower than outdoor
unit *2
-5
-16
1.009
1.000
0.985
0.909
0.949
-7.5
-25
—
1.000
0.985
0.909
0.949
-10
-33
—
—
0.985
0.909
0.949
-15
-49
—
—
—
0.909
0.949
HEATING
Pipe length
m
5
7.5
10
15
20
ft
16
25
33
49
66
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
—
—
—
0.866
0.855
10
33
—
—
0.954
0.866
0.855
7.5
25
—
1.000
0.954
0.866
0.855
5
16
1.041
1.000
0.954
0.866
0.855
0
0
1.041
1.000
0.954
0.866
0.855
Indoor unit is lower than outdoor
unit *2
-5
-16
0.994
0.995
0.949
0.862
0.851
-7.5
-25
—
0.993
0.947
0.860
0.849
-10
-33
—
—
0.944
0.857
0.847
-15
-49
—
—
—
0.848
0.838
- 72 -
6-1. Model: AOUH09LPAS1
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOUH09-12LPAS1
OUTDOOR UNIT
AOUH09-12LPAS1