En-24
Additional charging
71 31
CAUTION
Do not turn on the power unless all operations are complete.
•
Do not charge the system with a refrigerant other than R410A.
•
Do not reuse recovered refrigerant.
•
Use an electronic scale to measure the charging amount of refrigerant.
•
Adding more refrigerant than the specified amount will cause a malfunction.
Charge refrigerant using the liquid pipe.
•
Adding refrigerant through the gas pipe will cause a malfunction.
Add refrigerant by charging the system with the refrigerant in the liquid state. If the refrigerant cylinder is
•
equipped with a siphon, it is not necessary to place the cylinder upright.
Procedure for charging the system with refrigerant
71 31 11
Remove the charging cap from the liquid pipe.
1)
Attach a charging hose to the refrigerant cylinder, and connect it to the charging port.
2)
Add refrigerant by calculating the additional refrigerant volume in accordance with the calculation formula
3)
indicated below.
Remove the charging hose and install the charging cap.
4)
Remove the blank caps (gas pipe, liquid pipe), and open the valves.
5)
Close the blank caps.
6)
After adding refrigerant, indicate the added charging volume on the unit.
7)
Tighten the blank caps and charging caps to the torque values specified.
*
To open and close the valves, use an M4(5/32in.) hexagon wrench for liquid and gas pipes.
Calculating the amount of refrigerant charge to be added
71 31 21
Round up the value to 2 decimal places.
•
Diameter of liquid
pipe
(mm (in1))
Additional amount for
pipe length
(kg/m (oz1/ft))
Φ6.35 (1/4)
0.021 (0.224)
Φ9.52 (3/8)
0.058 (0.624)
Calculation of additional amount for pipe length
L =
Total length of
Φ9.52mm
(Φ3/8in.)
liquid pipe
× 0.058
kg/m
(0.624
oz./ft)
m (ft)
kg (oz.)
+
Total length of
Φ6.35mm
(Φ1/4in.)
liquid pipe
× 0.021
kg/m
(0.224
oz./ft)
m (ft)
kg (oz.)
=
Total
kg (oz.)
<Example>
If liquid pipe piping length is the following
Φ9.52 (3/8") : 20m, Φ6.35 (1/4") : 15m
Additional charge volume L=20(m)×0.058(kg/m)+15(m)×0.021(kg/m)
=1.475kg
≒
1.48kg
Φ9.52 (3/8") : 78ft, Φ6.35 (1/4") : 110ft
Additional charge volume L=78(ft)×0.624(oz./ft)+110(ft)×0.224(oz./ft)
=48.672oz.+24.64oz.=73.312oz.
≒
73.31oz.