En-10
Outdoor units installation in multi row
31 31 31
(Unit: mm(in.))
(1) Single parallel unit arrangement
(2) Multiple parallel unit arrangement
150(5-29/32)
600(23-5/8)
1000(39-3/8)
2000(78-3/4) or more
500(19-11/16)
600(23-5/8)
1500(59-1/16)
3000(118-1/8) or more
Transportation of the unit
31 41
WARNING
Do not touch the fins. Otherwise, personal injury could result.
•
CAUTION
When carrying the unit, hold the handles on the right and left sides and be careful.
•
If the outdoor unit is carried from the bottom, hands or fingers may be pinched.
Be sure to hold the handles on the sides of the unit. Otherwise, holding the suction grille on the sides of the unit
•
may cause deformation.
Handle
Handle
Handle
Suction grille
Installation of the unit
31 51
Install 4 anchor bolts at the locations indicated with arrows in
•
the figure.
To reduce vibration, do not install the unit directly on the
•
ground. Install it on a secure base (such as concrete blocks).
The foundation shall support the legs of the unit and have a
•
width of 50mm(1-31/32in.) or more.
Depending on the installation conditions, the outdoor unit may
•
spread its vibration during operation, which may cause noise
and vibration. Therefore, attach damping materials (such as
damping pads) to the outdoor unit during installation.
Install the foundation, making sure that there is enough space
•
for installing the connection pipes.
Secure the unit to a solid block using foundation bolts. (Use
•
4 sets of commercially available M10(3/8in.) bolts, nuts, and
washers.)
The bolts should protrude 20mm(25/32in.). (Refer to the
•
figure.)
If overturning prevention is required, purchase the necessary
•
commercially available items.
(Unit : mm(in.))
166(6-17/32)
AIR
650(25-19/32)
154(6-1/16)
50(1-31/32)
50(1-31/32)
16(5/8)
410(16-5/32)
Bolt
20(25/32)
Nut
Base
9379069342-02_IM.indb 10