En-36
Low noise mode (CN931)
101 21 21
• This features reduces the operating sound of
the outdoor unit from the normal sound. The
air conditioner is set to the “Low noise mode”
when closing the contact input of a commercial
timer or ON/OFF switch to a connector on the
outdoor control PC board.
* Performance may drop depending on the
outside air temperature condition, etc.
Input Signal
Low noise mode
ON
ON
OFF
OFF
* Set the “Low noise mode” level, refer to
“8.2.Function settings”.
Input Signal ···ON : Low noise mode
···OFF : Normal operation
External input priority mode (CN932)
101 21 31
• It is possible to switch to cooling operation and
heating operation by using external input.
Input Signal
Priority mode
ON
Heating
OFF
Cooling
* Set the “External input priority mode” , refer to
“8.2.Function settings”.
Input Signal ···ON : Heating operation
···OFF : Cooling operation
Peak cut mode (CN933)
101 21 41
• Operation that suppressed the current value
can be performed by means of the connected
unit. The air conditioner is set to the Peak
cut mode by applying the contact input of a
commercial ON/OFF switch to a connector on
the outdoor control PC board.
Input Signal
Peak cut mode
ON
ON
OFF
OFF
* Set the “Peak cut mode” level , refer to
“8.2.Function settings”.
Input Signal ···ON : Peak cut mode
···OFF : Normal operation
Stop operation mode (CN934)
101 21 51
• It is possible to switch to Batch stop or
Emergency stop and Normal operation by using
external input.
6/4/2010 5:04:48 PM
•
When function setting is
“
Batch stop
”
mode
•
When function setting is
“
Emergency stop
”
mode
Input signal
Input signal
Indoor unit
Indoor unit
Remote controller
Remote controller
On
On
On
On
On
On
On
Off
Off
Operation
Operation
Stop
Stop
* Set the “Batch stop” or “Emergency stop”
pattern ,refer to “8.2.Function settings”.