Fujitsu AOU36RLXFZH Скачать руководство пользователя страница 7

En-6

Capacity of indoor 

unit

Gas pipe size 

(thickness)

 in. (in.) [mm (mm)]

Liquid pipe size

(thickness) 

 in. (in.) [mm (mm)]

7 – 12

ø3/8 (0.032) [ø9.52 (0.8)]

ø1/4 (0.032) [ø6.35 (0.8)]

15, 18

ø1/2 (0.032) [ø12.70 (0.8)]

ø1/4 (0.032) [ø6.35 (0.8)]

24

ø5/8 (0.039) [ø15.88 (1.0)]

ø1/4 (0.032) [ø6.35 (0.8)]

 

CAUTION

Operation cannot be guaranteed if the correct combination of pipes, valves, etc., is not 
used to connect the indoor and outdoor units.

3. 4.  Heat insulation around connection pipes requirements

 

CAUTION

Install heat insulation around both the gas and liquid pipes.
Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70%, install heat insulation around the refrigerant piping. If the 
expected humidity level is 70-80%, use heat insulation that is 9/16 in. (15 mm) or 
thicker and if the expected humidity exceeds 80%, use heat insulation that is 13/16 in. 
(20 mm) or thicker.
If heat insulation is used that is not as thick as speci

fi

 ed, condensation may form on 

the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 68 °F).

Connect the connection pipes according to “5.1. Pipe connection” in this installation manual.

3. 5.  Operating range

Model

Temperature

Indoor air intake

Outdoor air intake

45 type

Cooling

Maximum

90 °F(32.2 °C) DB

115 °F(46.1 °C) DB

Minimum

65 °F(18.3 °C) DB

14 °F(-10.0 °C) DB

Heating

Maximum

88 °F(31.1 °C) DB

75 °F(23.8 °C) DB

Minimum

60 °F(15.5 °C) DB

5 °F(-15.0 °C) DB

36 type

Cooling

Maximum

90 °F(32.2 °C) DB

115 °F(46.1 °C) DB

Minimum

65 °F(18.3 °C) DB

14 °F(-10.0 °C) DB

Heating

Maximum

88 °F(31.1 °C) DB

75 °F(23.8 °C) DB

Minimum

60 °F(15.5 °C) DB

-15 °F(-26.1 °C) DB

Indoor humidity about 80% or less

3. 6.  Additional charging

Refrigerant suitable for a total piping length of 164 ft. (50 m) is charged in the outdoor unit 
at the factory.
When the piping is longer than 164 ft. (50 m), additional charging is necessary.
For the additional amount, see the table below.

Total piping 

length [ft. (m)]

164 (50) or less 197 (60) 230 (70) 264 (80)

Additional 

refrigerant 

charge

45 type

None

7 oz.

(200 g)

14 oz.

(400 g)

1 lbs. 5 

oz.

(600 g)

0.21 

oz./ft.

(20 g/m)

36 type

None

7 oz.

(200 g)

14 oz.

(400 g)

 

CAUTION

When moving and installing the air conditioner, do not mix gas other than the speci

fi

 ed 

refrigerant (R410A) inside the refrigerant cycle.

When charging the refrigerant R410A, always use an electronic balance for refrigerant 
charging (to measure the refrigerant by weight).

When charging the refrigerant, take into account the 
slight change in the composition of the gas and liquid 
phases, and always charge from the liquid phase side 
whose composition is stable.

R410A

Gas

Liquid

Add refrigerant from the charging valve after the completion of the work.

If the units are further apart than the maximum pipe length, correct operation cannot 
be guaranteed.

4. INSTALLATION WORK

Please obtain the approval of the customer when selecting the location of installation and 
installing the unit.

4. 1.  Selecting an installation location

 

WARNING

Securely install the outdoor unit at a location that can withstand the weight of the unit. 
Otherwise, the outdoor unit may fall and cause injury.

Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes 
and typhoons or other strong winds. Improper installation can cause the unit to topple 
or fall, or other accidents.

Do not install the outdoor unit near the edge of a balcony. Otherwise, children may 
climb onto the outdoor unit and fall off of the balcony.

 

CAUTION

Do not install the outdoor unit in the following areas:

•  Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

• Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the 
unit to leak water.

•  Area that generates substances that adversely affect the equipment, such as 

sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed 
joints to corrode, which can cause refrigerant leakage.

•  Area containing equipment that generates electromagnetic interference. It will 

cause the control system to malfunction, preventing the unit from operating nor-
mally.

•  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline. If gas 

leaks and settles around the unit, it can cause a 

fi

 re.

•  Area that has heat sources, vapors, or the risk of the leakage of 

fl

 ammable gas in 

the vicinity.

•  Area where small animals may live. It may cause failure, smoke or 

fi

 re if small 

animals enter and touch internal electrical parts.

•  Area where animals may urinate on the unit or ammonia may be generated.

Please install the outdoor unit without slant.

Install the outdoor unit in a well-ventilated location away from rain or direct sunlight.

If the outdoor unit must be installed in an area within easy reach of the general public, 
install as necessary a protective fence or the like to prevent their access.

Install the outdoor unit in a location that would not inconvenience your neighbors, as 
they could be affected by the air

fl

 ow coming out from the outlet, noise, or vibration. If it 

must be installed in proximity to your neighbors, be sure to obtain their approval.

If the outdoor unit is installed in a cold region that is affected by snow accumulation, 
snow fall, or freezing, take appropriate measures to protect it from those elements. To 
ensure a stable operation, install inlet and outlet ducts.

Install the outdoor unit in a location that is away from exhaust or the vent ports that 
discharge vapor, soot, dust, or debris.

Install the indoor unit, outdoor unit, power supply cable, connection cable, and remote 
control cable at least 40 in. (1 m) away from a television or radio receivers. The pur-
pose of this is to prevent TV reception interference or radio noise. (Even if they are 
installed more than 40 in. (1 m) apart, you could still receive noise under some signal 
conditions.)

Branch switch and 
circuit breaker

Branch switch and 
circuit breaker

40 in. (1 m) or more

40 in. (1 m) or more

If children under 10 years old may approach the unit, take preventive measures so 
that they cannot reach the unit.

Keep the length of the piping of the indoor and outdoor units within the allowable 
range.

For maintenance purposes, do not bury the piping.

4. 2.  Installation dimensions

 

CAUTION

Install the unit where it will not be tilted by more than 3

˚

. However, do not install the 

unit with it tilted towards the side containing the compressor.

When installing the outdoor unit where it may exposed to strong wind, fasten it se-
curely.

Decide the mounting position with the customer as follows:
(1) Install the outdoor unit in a location which can withstand the weight of the unit and 

vibration, and which can install horizontally.

(2) Provide the indicated space to ensure good air

fl

 ow.

(3) If possible, do not install the unit where it will be exposed to direct sunlight.

 (If necessary, install a blind that does not interfere with the air

fl

 ow.)

(4) Do not install the unit near a source of heat, steam, or 

fl

 ammable gas.

9380545101-02_IM.indb   6

9380545101-02_IM.indb   6

2/26/2016   10:16:03 AM

2/26/2016   10:16:03 AM

Содержание AOU36RLXFZH

Страница 1: ...OOR UNIT Français Español APPAREIL EXTÉRIEURE UNIDAD EXTERIOR INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Seulement pour personnel d entretien autorisé Únicamente para personal de servicio autorizado ...

Страница 2: ...o check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual Be sure to read this Manual thoroughly before installation The warn...

Страница 3: ...er operating on all wires with a distance between contact of 3 mm for this product To protect the persons earth ground the product correctly and use the power cable combined with an Earth Leakage Circuit Breaker ELCB This product is not explosion proof and therefore should not be installed in explosive atmosphere Do not touch the fins of the heat exchanger Touching the heat exchanger fins could re...

Страница 4: ...rigerant pipe OUTDOOR UNIT INDOOR UNITS UNIT E 7 9 UNIT D 7 12 UNIT C 7 18 UNIT B 7 24 UNIT A 7 24 CAUTION The total capacity of the indoor units connected must be between 34 000 and 54 000 BTU Connection patterns are restricted Normal operation is not guaranteed if connected pattern in the combination not listed below The product may be damaged Surely con nect in accordance with the combination i...

Страница 5: ...0 110 15 000 9 000 9 000 9 000 9 000 111 15 000 9 000 9 000 9 000 7 000 112 15 000 9 000 9 000 7 000 7 000 113 15 000 9 000 7 000 7 000 7 000 114 15 000 7 000 7 000 7 000 7 000 115 12 000 12 000 12 000 9 000 9 000 116 12 000 12 000 12 000 9 000 7 000 117 12 000 12 000 12 000 7 000 7 000 118 12 000 12 000 9 000 9 000 9 000 119 12 000 12 000 9 000 9 000 7 000 120 12 000 12 000 9 000 7 000 7 000 121 ...

Страница 6: ...electrical appliances When the current contracted capacity is insuf ficient change the contracted capacity When the voltage is low and it is difficult to start the air conditioner contact the power company to have the voltage raised 3 2 Selecting circuit breaker and wiring CAUTION Be sure to install a breaker of the specified capacity Regulation of cables and breaker differs from each locality ref...

Страница 7: ...oor unit and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or t...

Страница 8: ...g No more than 3 units must be installed side by side When 3 units or more are arranged in a line provide the space as shown in the following example when there is an obstruction in the upper space When the upper space is open Unit in mm 1 When there are obstacles at the rear only 11 13 16 300 or more 9 13 16 250 or more 2 When there are obstacles at the front only 9 13 16 250 or more 59 1 16 1500...

Страница 9: ...lts should protrude 1 in 20 mm Refer to the figure If overturning prevention is required purchase the necessary commercially available items 6 9 16 166 AIR 25 9 16 650 6 1 16 154 2 50 2 50 16 16 1 8 410 Unit in mm Bolt 1 20 Nut Base Do not install directly on the ground this may result in equipment failure Make sure the height of the base is 2 in 50 mm from the ground Otherwise there is a risk tha...

Страница 10: ...t doing so may cause a refrigerant leak When connecting the indoor unit it should be connected in the order of port A B C and so on Please be sure to close remaining unconnected ports so that they do not leak refrigerant 1 Detach the caps and plugs from the pipes 2 Center the pipe against the port on the outdoor unit and then turn the flare nut by hand To prevent gas leakage coat the flare surface...

Страница 11: ...nside of the pipes if rain might enter the pipes during work etc After operating the vacuum pump for 2 hours pressurize to 0 05 MPa i e vacuum breakdown with nitrogen gas then depressurize down to 100 7kPa 755mmHg for an hour using the vacuum pump vacuum process If the pressure does not reach 100 7kPa 755mmHg even after depressurizing for at least 2 hours repeat the vacuum breakdown vacuum process...

Страница 12: ...o the terminal block 2 Securely clamp the ring type terminals to the wires using an appropriate tool so that the wires do not come loose 3 Use the specified wires connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged ...

Страница 13: ...rds Hook 3 places Service cover Direction of the service panel removal 2 Conduit plate removal Remove the five mounting screws Remove the conduit plate 3 Fasten the power supply cable and the connection cable to the conduit holder using the lock nut Open the knock out holes with the tool so as not to transform conduit plate if necessary Look nut Conduit plate Power supply cable Knockout hole Conne...

Страница 14: ...ody before touching the push switches Never touch any terminal or pattern of any parts on the control board The positions of the switches on the outdoor unit control board are shown in the figure below ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 PUMP DOWN 2 W S 1 W S CHECK TEST RUN SET1 SET1 1 HEAT COOL SET2 SET3 F E D C MONITOR ERROR B A POWER MODE 7 1 1 Setting method 1 Be sure to disconnect the power sour...

Страница 15: ...al operation is possible without using the check run In this case use the test run or forced cooling function of the indoor unit to confirm any wiring errors 8 1 Things to confirm before starting the check run To ensure safety check that the following work inspections and operations have been completed Check Item Check Column 1 Check that all work on the piping connecting the outdoor unit indoor u...

Страница 16: ... to F will flash Preliminary operation The LED for each indoor unit will switch off in order as check for each unit is completed 2 blink F E D C MONITOR ERROR B A POWER MODE Example When 4 indoor units A to D are connected 4 After the check run is complete results will be displayed Please fill the displayed results in the result table accordingly NOTE Automatic wiring correction will not be comple...

Страница 17: ...using this function the wiring is automatically corrected according to the pip ing 2 When correcting the wiring manually please disconnect the power supply or turn off the breaker during results display and then change the wiring manually ac cording to the obtained test results For example in Example 1 the wirings connected to the terminals B and C is to be exchanged manually 5 During results disp...

Страница 18: ...12 hours prior to the start of the operation in order to protect the compressor 1 Indoor unit 1 Is the drain normal 2 Is there any abnormal noise and vibration during operation 2 Outdoor unit 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage Do not operate the air conditioner in the test runn...

Страница 19: ... Trip terminal L error 71 1 Discharge temp sensor error 72 1 Compressor temp sensor error 73 2 Heat ex middle temp sensor error 73 3 Heat ex liquid temp sensor error 74 1 Outdoor temp sensor error 75 1 Suction gas temp sensor error 76 1 Valve sensor error 76 2 77 1 Heat sink temp sensor error 84 1 Current sensor 1 error stoppage permanently 86 1 Discharge pressure sensor error 94 1 Trip detection ...

Страница 20: ...after 15 min and the LED will light as follows If the pump down is complete disconnect the power supply or turn off the breaker If not completed open the liquid pipe valve and then start again from step 3 F E D C MONITOR ERROR B A POWER MODE 3 blink blink High speed In order to interrupt the pump down operation press the PUMP DOWN switch again The LED will return to the original display before sta...

Отзывы: