background image

En-10

Opening direction

Hexagon wrench

Seal (blank cap 
installation portion)

Liquid pipe

Gas pipe

Opening direction

5. 1. 5.  How to use adapter (Connection ports of outdoor unit)

•  When using the ADAPTER, be careful not to overtighten the nut, or the smaller pipe 

may be damaged.

•  Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit 

where the 

fl

 are nut comes in.

•  Use appropriate wrenches to avoid damaging the connection thread by 

overtightening the 

fl

 are nut.

•  Apply wrenches on both of 

fl

 are nut (local part), and ADAPTER to tighten them.

Adapter tightening torque

Adapter type [in. (mm)]

Tightening torque [lbf·ft. (N·m)]

ø1/2 (ø12.70) 

 ø3/8 (ø9.52)

36.1 to 45.0 (49 to 61)

ø1/2 (ø12.70) 

 ø5/8 (ø15.88)

36.1 to 45.0 (49 to 61)

5. 2.  Sealing test

CAUTION

Use only nitrogen gas.
Never use refrigerant gas, oxygen, in 

fl

 ammable gas or poisonous gas to pressurize 

the system. (If oxygen is used, there is the danger of an explosion.)

Do not apply shock during sealing test.
It can rupture the pipes and cause serious injury.

Do not turn on the power unless all operations are complete.

Do not block the walls and the ceiling until the sealing test and the charging of the 
refrigerant gas have been completed.

After connecting the pipes, perform an sealing test.
Recheck that the 3-way valve are closed before performing a sealing test. 
(Fig. B)
Pour nitrogen gas through both the liquid pipe and the gas pipe.
Pressurize nitrogen gas to 4.2 MPa to perform the sealing test.

Check all 

fl

 are connection areas and brazed areas.

Then, check that the pressure has not decreased.
Compare the pressures after pressurizing and letting it stand for 24 hours, and check 
that the pressure has not decreased.
*  When the outdoor temperature changes 5 °C, the test pressure changes 0.05 MPa.

If the pressure has dropped, the pipe joints may be leaking.

If a leakage is found, immediately repair it and perform a sealing test again.

* Decrease the pressure of nitrogen gas before blazing

After completing the sealing test, release the nitrogen gas from both valves.
Release the nitrogen gas slowly.

5. 3.  Vacuum process

CAUTION

Do not turn on the power unless all operations are complete.

If the system is not evacuated suf

fi

 ciently, its performance will drop.

Be sure to evacuate the refrigerant system using a vacuum pump.

The refrigerant pressure may sometimes not rise when a closed valve is opened after 
the system is evacuated using a vacuum pump. This is caused by the closure of the 
refrigerant system of the outdoor unit by the electronic expansion valve. This will not 
affect the operation of the unit.
Use a clean gauge manifold and charging hose that were designed speci

fi

 cally for 

use with R410A. Using the same vacuum equipment for different refrigerants may 
damage the vacuum pump or the unit.

Do not purge the air with refrigerants, but use a vacuum pump to evacuate the system.

•  If moisture might enter the piping, follow below. (i.e., if doing work during the rainy 

season, if the actual work takes long enough that condensation may form on the 
inside of the pipes, if rain might enter the pipes during work, etc.)

•  After operating the vacuum pump for 2 hours, pressurize to 0.05 MPa (i.e., vacuum 

breakdown) with nitrogen gas, then depressurize down to -100.7kPa (-755mmHg) 
for an hour using the vacuum pump (vacuum process).

•  If the pressure does not reach -100.7kPa (-755mmHg) even after depressurizing 

for at least 2 hours, repeat the vacuum breakdown - vacuum process.

After vacuum process, maintain the vacuum for an hour and make sure the pressure 
does not rise by monitoring with a vacuum gauge.

Evacuation procedure

(1)  Remove the blank caps of the gas pipe and liquid pipe and check that the valves 

are closed.

(2)  Remove the charging port cap.
(3)  Connect a vacuum pump and a pressure gauge to a charging hose and connect it 

to the charging port.

(4)  Activate the vacuum pump and vacuum the indoor unit and connection piping until 

the pressure gauge becomes -100.7kPa (-755mmHg).
Evacuate from both the gas pipe and the liquid pipe.

(5) Continue 

evacuating 

the 

system 

for 

1 hour after the pressure gauge reads 

-100.7kPa (-755mmHg).

(6) Remove 

the 

charging 

hose 

and 

reinstall the charging port cap.

Table. A

Pipe

3-way valve

Blank cap

Charging  port  cap

Liquid 
valve

7.0 to 9.0 N·m
(70 to 90 kgf·cm)

20.0 to 25.0 N·m
(200 to 250 kgf·cm)

12.5 to 16.0 N·m
(125 to 160 kgf·cm)

Gas 
valve

11.0 to 13.0 N·m
(110 to 130 kgf·cm)

30.0 to 35.0 N·m
(300 to 350 kgf·cm)

12.5 to 16.0 N·m
(125 to 160 kgf·cm)

Fig. A  Connection  system

Outdoor unit

Pressure gauge

Vacuum 

pump

Scale

Pressure regulating valve

Nitrogen

Indoor 

unit

Indoor 

unit

Fig. B

Service hose with valve core

Charging port

Charging port cap

3-way valve

Blank cap

Hexagon wrench

4mm (5/32”)

6. ELECTRICAL WIRING

 

WARNING

Wiring connections must be performed by a quali

fi

 ed person in accordance with speci-

fi

 cations.

The rated supply of this product is 60Hz, 208/230V. Use a voltage within the range of 
187-253V.

Before connecting the wires, make sure the power supply is OFF.

When installing this system in high humidity locations, install using ground fault equip-
ment breakers (often referred to in other countries as an ELCB [earth leakage current 
breaker]) to reduce the risk of leaking current which may result in electric shock or 
potential 

fi

 re.

Be sure to install a breaker of the speci

fi

 ed capacity. 

When selecting breaker, please comply with the laws and the regulations of each 
country. 
One breaker must be installed on the power supply of the outdoor unit.
Wrong selection and setup of the breaker will cause electric shock or 

fi

 re.

Do not connect AC power supply to the transmission line terminal board.
Improper wiring can damage the entire system.

Connect the connector cord securely to the terminal.
Faulty installation can cause a 

fi

 re.

Make sure to secure the insulation portion of the connector cable with the cord clamp. 
A damaged insulation can cause a short circuit.

Never install a power factor improvement condenser. Instead of improving the power 
factor, the condenser may overheat.

CAUTION-Risk of Electric Shock
Before servicing the unit, turn the power supply switch OFF. Then, do not touch elec-
tric parts for 10 minutes due to the risk of electric shock.

Make sure to perform grounding work. Improper grounding work can cause electric 
shocks.

9380545101-02_IM.indb   10

9380545101-02_IM.indb   10

2/26/2016   10:16:04 AM

2/26/2016   10:16:04 AM

Содержание AOU36RLXFZH

Страница 1: ...OOR UNIT Français Español APPAREIL EXTÉRIEURE UNIDAD EXTERIOR INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Seulement pour personnel d entretien autorisé Únicamente para personal de servicio autorizado ...

Страница 2: ...o check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual Be sure to read this Manual thoroughly before installation The warn...

Страница 3: ...er operating on all wires with a distance between contact of 3 mm for this product To protect the persons earth ground the product correctly and use the power cable combined with an Earth Leakage Circuit Breaker ELCB This product is not explosion proof and therefore should not be installed in explosive atmosphere Do not touch the fins of the heat exchanger Touching the heat exchanger fins could re...

Страница 4: ...rigerant pipe OUTDOOR UNIT INDOOR UNITS UNIT E 7 9 UNIT D 7 12 UNIT C 7 18 UNIT B 7 24 UNIT A 7 24 CAUTION The total capacity of the indoor units connected must be between 34 000 and 54 000 BTU Connection patterns are restricted Normal operation is not guaranteed if connected pattern in the combination not listed below The product may be damaged Surely con nect in accordance with the combination i...

Страница 5: ...0 110 15 000 9 000 9 000 9 000 9 000 111 15 000 9 000 9 000 9 000 7 000 112 15 000 9 000 9 000 7 000 7 000 113 15 000 9 000 7 000 7 000 7 000 114 15 000 7 000 7 000 7 000 7 000 115 12 000 12 000 12 000 9 000 9 000 116 12 000 12 000 12 000 9 000 7 000 117 12 000 12 000 12 000 7 000 7 000 118 12 000 12 000 9 000 9 000 9 000 119 12 000 12 000 9 000 9 000 7 000 120 12 000 12 000 9 000 7 000 7 000 121 ...

Страница 6: ...electrical appliances When the current contracted capacity is insuf ficient change the contracted capacity When the voltage is low and it is difficult to start the air conditioner contact the power company to have the voltage raised 3 2 Selecting circuit breaker and wiring CAUTION Be sure to install a breaker of the specified capacity Regulation of cables and breaker differs from each locality ref...

Страница 7: ...oor unit and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or t...

Страница 8: ...g No more than 3 units must be installed side by side When 3 units or more are arranged in a line provide the space as shown in the following example when there is an obstruction in the upper space When the upper space is open Unit in mm 1 When there are obstacles at the rear only 11 13 16 300 or more 9 13 16 250 or more 2 When there are obstacles at the front only 9 13 16 250 or more 59 1 16 1500...

Страница 9: ...lts should protrude 1 in 20 mm Refer to the figure If overturning prevention is required purchase the necessary commercially available items 6 9 16 166 AIR 25 9 16 650 6 1 16 154 2 50 2 50 16 16 1 8 410 Unit in mm Bolt 1 20 Nut Base Do not install directly on the ground this may result in equipment failure Make sure the height of the base is 2 in 50 mm from the ground Otherwise there is a risk tha...

Страница 10: ...t doing so may cause a refrigerant leak When connecting the indoor unit it should be connected in the order of port A B C and so on Please be sure to close remaining unconnected ports so that they do not leak refrigerant 1 Detach the caps and plugs from the pipes 2 Center the pipe against the port on the outdoor unit and then turn the flare nut by hand To prevent gas leakage coat the flare surface...

Страница 11: ...nside of the pipes if rain might enter the pipes during work etc After operating the vacuum pump for 2 hours pressurize to 0 05 MPa i e vacuum breakdown with nitrogen gas then depressurize down to 100 7kPa 755mmHg for an hour using the vacuum pump vacuum process If the pressure does not reach 100 7kPa 755mmHg even after depressurizing for at least 2 hours repeat the vacuum breakdown vacuum process...

Страница 12: ...o the terminal block 2 Securely clamp the ring type terminals to the wires using an appropriate tool so that the wires do not come loose 3 Use the specified wires connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged ...

Страница 13: ...rds Hook 3 places Service cover Direction of the service panel removal 2 Conduit plate removal Remove the five mounting screws Remove the conduit plate 3 Fasten the power supply cable and the connection cable to the conduit holder using the lock nut Open the knock out holes with the tool so as not to transform conduit plate if necessary Look nut Conduit plate Power supply cable Knockout hole Conne...

Страница 14: ...ody before touching the push switches Never touch any terminal or pattern of any parts on the control board The positions of the switches on the outdoor unit control board are shown in the figure below ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 PUMP DOWN 2 W S 1 W S CHECK TEST RUN SET1 SET1 1 HEAT COOL SET2 SET3 F E D C MONITOR ERROR B A POWER MODE 7 1 1 Setting method 1 Be sure to disconnect the power sour...

Страница 15: ...al operation is possible without using the check run In this case use the test run or forced cooling function of the indoor unit to confirm any wiring errors 8 1 Things to confirm before starting the check run To ensure safety check that the following work inspections and operations have been completed Check Item Check Column 1 Check that all work on the piping connecting the outdoor unit indoor u...

Страница 16: ... to F will flash Preliminary operation The LED for each indoor unit will switch off in order as check for each unit is completed 2 blink F E D C MONITOR ERROR B A POWER MODE Example When 4 indoor units A to D are connected 4 After the check run is complete results will be displayed Please fill the displayed results in the result table accordingly NOTE Automatic wiring correction will not be comple...

Страница 17: ...using this function the wiring is automatically corrected according to the pip ing 2 When correcting the wiring manually please disconnect the power supply or turn off the breaker during results display and then change the wiring manually ac cording to the obtained test results For example in Example 1 the wirings connected to the terminals B and C is to be exchanged manually 5 During results disp...

Страница 18: ...12 hours prior to the start of the operation in order to protect the compressor 1 Indoor unit 1 Is the drain normal 2 Is there any abnormal noise and vibration during operation 2 Outdoor unit 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage Do not operate the air conditioner in the test runn...

Страница 19: ... Trip terminal L error 71 1 Discharge temp sensor error 72 1 Compressor temp sensor error 73 2 Heat ex middle temp sensor error 73 3 Heat ex liquid temp sensor error 74 1 Outdoor temp sensor error 75 1 Suction gas temp sensor error 76 1 Valve sensor error 76 2 77 1 Heat sink temp sensor error 84 1 Current sensor 1 error stoppage permanently 86 1 Discharge pressure sensor error 94 1 Trip detection ...

Страница 20: ...after 15 min and the LED will light as follows If the pump down is complete disconnect the power supply or turn off the breaker If not completed open the liquid pipe valve and then start again from step 3 F E D C MONITOR ERROR B A POWER MODE 3 blink blink High speed In order to interrupt the pump down operation press the PUMP DOWN switch again The LED will return to the original display before sta...

Отзывы: