![Fujitsu AOU36RLXFZH Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/fujitsu/aou36rlxfzh/aou36rlxfzh_installation-manual_2344141005.webp)
En-4
Indoor unit
A
B
C
D
E
46
18,000
18,000
9,000
9,000
―
47
18,000
18,000
9,000
7,000
―
48
18,000 18,000 7,000 7,000
―
49
18,000
15,000
12,000
9,000
―
50
18,000
15,000
12,000
7,000
―
51
18,000
15,000
9,000
9,000
―
52
18,000
15,000
9,000
7,000
―
53
18,000 15,000 7,000 7,000
―
54
18,000
12,000
12,000
12,000
―
55
18,000
12,000
12,000
9,000
―
56
18,000
12,000
12,000
7,000
―
57
18,000
12,000
9,000
9,000
―
58
18,000
12,000
9,000
7,000
―
59
18,000 12,000 7,000 7,000
―
60
18,000
9,000
9,000
9,000
―
61
18,000
9,000
9,000
7,000
―
62
18,000 9,000 7,000 7,000
―
63
18,000 7,000 7,000 7,000
―
64
15,000
15,000
15,000
9,000
―
65
15,000
15,000
15,000
7,000
―
66
15,000
15,000
12,000
12,000
―
67
15,000
15,000
12,000
9,000
―
68
15,000
15,000
12,000
7,000
―
69
15,000
15,000
9,000
9,000
―
70
15,000
15,000
9,000
7,000
―
71
15,000 15,000 7,000 7,000
―
72
15,000
12,000
12,000
12,000
―
73
15,000
12,000
12,000
9,000
―
74
15,000
12,000
12,000
7,000
―
75
15,000
12,000
9,000
9,000
―
76
15,000
12,000
9,000
7,000
―
77
15,000 12,000 7,000 7,000
―
78
15,000
9,000
9,000
9,000
―
79
15,000
9,000
9,000
7,000
―
80
15,000 9,000 7,000 7,000
―
81
15,000 7,000 7,000 7,000
―
82
12,000
12,000
12,000
12,000
―
83
12,000
12,000
12,000
9,000
―
84
12,000
12,000
12,000
7,000
―
85
12,000
12,000
9,000
9,000
―
86
12,000
12,000
9,000
7,000
―
87
12,000 12,000 7,000 7,000
―
88
12,000
9,000
9,000
9,000
―
89
12,000
9,000
9,000
7,000
―
90
12,000 9,000 7,000 7,000
―
91
9,000
9,000
9,000
9,000
―
92
9,000
9,000
9,000
7,000
―
93
24,000
9,000
7,000
7,000
7,000
94
24,000
7,000
7,000
7,000
7,000
95
18,000
15,000
7,000
7,000
7,000
96
18,000
12,000
9,000
7,000
7,000
97
18,000
12,000
7,000
7,000
7,000
98
18,000
9,000
9,000
9,000
9,000
99
18,000
9,000
9,000
9,000
7,000
100
18,000
9,000
9,000
7,000
7,000
101
18,000
9,000
7,000
7,000
7,000
102
18,000
7,000
7,000
7,000
7,000
103
15,000 15,000 9,000 7,000 7,000
104
15,000
15,000
7,000
7,000
7,000
105
15,000
12,000
12,000
7,000
7,000
106
15,000
12,000
9,000
9,000
9,000
107
15,000
12,000
9,000
9,000
7,000
108
15,000
12,000
9,000
7,000
7,000
109
15,000
12,000
7,000
7,000
7,000
110
15,000
9,000
9,000
9,000
9,000
111
15,000
9,000
9,000
9,000
7,000
112
15,000
9,000
9,000
7,000
7,000
113
15,000
9,000
7,000
7,000
7,000
114
15,000
7,000
7,000
7,000
7,000
115
12,000
12,000
12,000
9,000
9,000
116
12,000
12,000
12,000
9,000
7,000
117
12,000
12,000
12,000
7,000
7,000
118
12,000
12,000
9,000
9,000
9,000
119
12,000
12,000
9,000
9,000
7,000
120
12,000
12,000
9,000
7,000
7,000
121
12,000
12,000
7,000
7,000
7,000
122
12,000
9,000
9,000
9,000
9,000
123
12,000
9,000
9,000
9,000
7,000
Indoor unit
A
B
C
D
E
124
12,000
9,000
9,000
7,000
7,000
125
12,000
9,000
7,000
7,000
7,000
126
12,000
7,000
7,000
7,000
7,000
127
9,000
9,000
9,000
9,000
9,000
128
9,000
9,000
9,000
9,000
7,000
129
9,000
9,000
9,000
7,000
7,000
130
9,000
9,000
7,000
7,000
7,000
131
9,000
7,000
7,000
7,000
7,000
132
7,000
7,000
7,000
7,000
7,000
Outdoor port
Capacity indoor unit
Standard port size [in. (mm)]
E
1/4 (6.35) / 3/8 (9.52)
7 - 9
D
1/4 (6.35) / 3/8 (9.52)
7 - 12
C
1/4 (6.35) / 3/8 (9.52)
7 - 18
B
1/4 (6.35) / 1/2 (12.70)
7 - 24
A
1/4 (6.35) / 1/2 (12.70)
7 - 24
Port E: Ø1/4 in., Ø3/8 in. (Ø6.35 mm, Ø9.52 mm)
Port D: Ø1/4 in., Ø3/8 in. (Ø6.35 mm, Ø9.52 mm)
Port C: Ø1/4 in., Ø3/8 in. (Ø6.35 mm, Ø9.52 mm)
Port B: Ø1/4 in., Ø1/2 in. (Ø6.35 mm, Ø12.70 mm)
Port A: Ø1/4 in., Ø1/2 in. (Ø6.35 mm, Ø12.70 mm)
2. 4. 2. Connectable indoor unit capacity type (Outdoor unit: 36 type)
A
B
C
D
H1
H1
H2
Power source
208/230 V ~ 60 Hz
Power supply cable
Connection cable
Refrigerant pipe
OUTDOOR UNIT
INDOOR UNITS
UNIT D
7-12
UNIT C
7-12
UNIT B
7-18
UNIT A
7-24
CAUTION
The total capacity of the indoor units connected must be between 27,000 and 39,000
BTU.
Connection patterns are restricted. Normal operation is not guaranteed if connected
pattern in the combination not listed below. The product may be damaged. Surely con-
nect in accordance with the combination in the following connection pattern.
• To install an indoor unit, refer to the installation manual included with the indoor unit.
Indoor unit connection pattern
Indoor unit
A
B
C
D
1
18,000
18,000
–
–
2
9,000
9,000
9,000
–
3
12,000
9,000
7,000
–
4
12,000
9,000
9,000
–
5
12,000
12,000
7,000
–
6
12,000
12,000
9,000
–
7
12,000
12,000
12,000
–
8
15,000 7,000
7,000
–
9
15,000
9,000
7,000
–
10
15,000
9,000
9,000
–
11
15,000
12,000
7,000
–
12
15,000
12,000
9,000
–
9380545101-02_IM.indb 4
9380545101-02_IM.indb 4
2/26/2016 10:16:03 AM
2/26/2016 10:16:03 AM