<Cooling operation>
OK
OK
OK
OK
:
OK
<Heating operation>
2. EEV defective, strainer clogged
3. Outdoor unit operation
failure
, foreign matter on heat exchanger
4. Discharge temperature thermistor
failure
5. Insufficient refrigerant
Discharge temperature thermistor
"Protection stop by "discharge temperature 239degF during compressor
operation'''' generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check
(Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Service Parts Information 5".
Check Point 4 : Check the discharge thermistor
EEV (EEV2, indoor unit EEV) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3, 4 "
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check(PARTS INFORMATION 7)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV (EEV1, EEV2) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 3, 4"
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
02-22
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
1. 3-way valve not opened
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 20
OUTDOOR UNIT Error Method:
Discharge Temp. Error
Indicate or Display:
Refer to error code table.