background image

1.

Check if the piping connections are secure.

2.

Check that the stems of 2-way valve and 3-way valve are closed
fully.

3.

Connect the gauge manifold charge hose to the charging port
of the 3-way valve (side with the projection for pushing in the
valve core).

4.

Open the low pressure side valve of the gauge manifold fully.

5.

Operate the vacuum pump and start pump down.

6.

Slowly loosen the flare nut of the 3-way valve and check if air
enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)

OUTDOOR UNIT

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the
outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do
not operate it during the following work.

Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trouble.

Connector cover removal

Remove the two mounting screws.

Installing the connector cover

(1) After inserting the three front hooks, then insert the rear hook.
(2) Tighten the two mounting screws.

Fig. 9

7.

Pump down the system for at least 15 minutes, then check if the
compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

8.

At the end of pump down, close the low pressure side gauge of
the gauge manifold fully and stop the vacuum pump.

9.

Slowly loosen the valve stem of the 3-way valve. When the
compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose
from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)

WARNING

(1) Install the unit where it will not be tilted by more

than 5°.

(2) When installing the outdoor unit where it may ex-

posed to strong wind, fasten it securely.

Tapping screw

Rear hooks

Connector cover

Front hooks

Table 6

Tightening torque

Blank cap (2-way valve)

14.47 to 18.08 ft•lbs (200 to 250 kgf•cm)

Blank cap (3-way valve)

20.25 to 23.15 ft•lbs (280 to 320 kgf•cm)

Charging port cap

9.04 to 11.57 ft•lbs (125 to 160 kgf•cm)

10. Fully open the valve stems of the 2-way valve and 3-way valve

using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.17ft •lbs (30 kgf•cm) until it
stops turning.)

11. Firmly tighten the 2-way valve and 3-way valve blank cap and

the charging port cap.

LO

HI

Fig. 10

Flare nut

3-way valve

-0.1 MPa
(-76 cmHg
-1 bar)

High
pressure
side valve
(closed)

2-way valve

Gauge manifold

Compound pressure gauge

Pressure gauge

Low pressure
side valve

Blank cap

Charge
hose

Vacuum pump

Valve stem

Charge hose

Charging port cap

Charging port

CAUTION

(1) Refrigerant must not be discharged into atmos-

phere.

(2) After connecting the piping , check the joints for

gas leakage with gas leak detector.

Содержание AOU18CL

Страница 1: ...s Connect all wiring tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Ma...

Страница 2: ...o 38 bar for low pressure To increase pressure resistance the hose material and base size were changed A conventional vacuum pump can be used by installing a vacuum pump adapter Special gas leakage detector for HFC refrigerant R410A Tool name Gauge manifold Charge hose Vacuum pump Gas leakage detector Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of ...

Страница 3: ...low Between 49 ft 15 m and 66 ft 20 m when using a connection pipe other than that in the table charge additional refrigerant with 0 2 oz ft 20g 1 m as the criteria 2 ADDITIONALMATERIALSREQUIREDFOR INSTALLATION A Refrigeration armored tape B Insulated staples or clamps for connecting wire See your local electrical codes C Putty D Refrigeration lubricant E Clamps or saddles to secure refrigerant pi...

Страница 4: ... WARNING Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall CAUTION 1 Do not install where there is the danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the unit Indoor unit pip...

Страница 5: ...ht hand side Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Fig 3 Install the piping so that the drain hose is at the bottom Wrap the pipes of the indoor unit that are visible from the outside with decorative tape For Left rear piping Left piping Interchange the drain cap and the drai...

Страница 6: ...ttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare the pipe with a flaring tool Check if L is flared uniformly and is not cracked or scratched L dimension Thin pipe 1 4 6 35 mm dia 1 16 1 4 to 1 7 mm Thick pipe 1 2 12 7 mm dia 5 64 1 9 to 2 2 mm Flare nut 1 4 6 35 mm dia 1 2 12 7 mm dia Tightening torque 11 57 to 13 02 ft lbs 160 to 180 kgf cm 36 17 ...

Страница 7: ... 8 At the end of pump down close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump 9 Slowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnecte...

Страница 8: ...Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trade size for this unit is 1 2 12 7 mm The connec tor can be bought at a hardware store Refer to How to connect wiring to the terminals for instructions on connecting depend ing on the wire type you are using The fuse located in the outdoor unit provides power supply pro tection and...

Страница 9: ...lamp Connection cord Screw Connection cord Screw Cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using pliers bend the solid wire to form a loop suitable for the termi nal screw 4 Shape the loop ...

Страница 10: ... the intake grille 2 Pull down the knob 3 Lift the intake grille upward until the axle at the top of the intake grille is removed THE INTAKE GRILLE INSTALLATION 1 The fixing axle of the intake grille is installed on the Panel 2 Lay down the intake grille THE FRONT PANEL REMOVAL 1 Remove intake grille Reference the intake grille removal 2 Remove four screws 3 The thumb is hung on the lower part as ...

Страница 11: ...ration of each button on the remote control unit normal 2 Does each lamp light normally 3 Do the air flow direction louver operate normally 4 Is the drain normal 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage Fig 18 Transmitter section Test run button PUMP DOWN OPERATION FOR...

Страница 12: ...ter unit wire harness to the terminal correctly please refer to Fig 19 to adjust the length of the part of Inter unit Wire harness ahead from conduit holder 5 1 2 140mm 15 16 25mm 15 16 25mm 4 3 16 105mm 1 1 14AWG EARTH WIRE CONDUIT PLATE CONDUIT CONNECTOR Fig 19 ...

Страница 13: ...ver the recommended maxuim length 7 Before setting up the wired remote control unit please confirm whether air conditioner can receive the signal 1 FRONT PANEL AND CONTROL UNIT REMOVAL 1 Refer to FRONT PANEL REMOBAL AND INSTALLATION to remove the front panel 2 Remove screws of the heat exchanger ang then remove grounding wire 3 Remove 2 thermistor 4 Remove screw then remove the connector cover and...

Страница 14: ...t be affected by the heat from a stove etc 1 REMOTE CONTROL UNIT HOLDER INSTALLATION Install the remote control unit with a distance of 23 ft 7 m between the remote control unit and the photocell as the criteria However when installing the remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control ...

Отзывы: