SELECTING THE MOUNTING
POSITION

INSTALLATION DIAGRAM OF
INDOOR AND OUTDOOR UNITS

Decide the mounting position with the customer as follows:

1. INDOOR UNIT

(1) Install the indoor unit level on a strong wall which is not subject

to vibration.

(2) The inlet and outlet ports should not be obstructed : the air should

be able to blow all over the room.

(3) Install the unit near an electric outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown

in (Fig. 7). Also install the unit where the filter can be removed.

2. OUTDOOR UNIT

(1) If possible, do not install the unit where it will be exposed to di-

rect sunlight. (If necessary, install a blind that does not interfere
with the air flow.)

(2) Do not install the unit where a strong wind blows or where it is

very dusty.

(3) Do not install the unit where people pass.
(4) Take your neighbors into consideration so that they are not dis-

turbed by air blowing into their windows or by noise.

(5) Provide the space shown in Fig. 7 so that the air flow is not blocked.

Also for efficient operation, leave open three of the four direc-
tions front, rear, and both sides.

 WARNING

Install at a place that can withstand the weight of the
indoor and outdoor units and install positively so that
the units will not topple or fall.

 CAUTION

(1) Do not install where there is the danger of com-

bustible gas leakage.

(2) Do not install near heat sources.

(3) If children under 10 years old may approach the

unit, take preventive measures so that they can-
not reach the unit.

[Indoor unit piping direction]

The piping can be connected in the five directions indicated by 

1

,

2

,

3

,

4

, and 

5

 in (Fig. 6). When the piping is connected in direction 

2

 or 

5

, cut

along the piping groove in the side of the front cover with a hacksaw.
When connecting the piping in direction 

3

, cut a notch in the thin wall at

the front bottom of the front cover.

Fig. 6

Fig. 7

[INDOOR UNIT]

[OUTDOOR UNIT]

2-2/5”(6 cm) or over

Wall hook bracket

2”(5 cm)
or over

3- 3/5”(9 cm)
or over

60”(150 cm) or over

(Wall cap)

Remote
control unit

Tapping
screw
(small)

Remote
control
unit holder

4”(10 cm)
or over

24”(60 cm)
or over

4”(10 cm)
or over

12”(30 cm)
or over

12”(30 cm)
or over

95” (240 cm)
or over

Connection Cord

14AWG

Drain hose

Outdoor unit bottom

[Reverse cycle only]

2”(5 cm)
or over

Mounting Support
(Prepared On-site)

Fig. 8

21-1/4” (54 cm)

12-9/16” (32 cm)

NOTE:

In places where the outdoor temperature drops
to 32°F or lower, the drain water may freeze and
may stop up the drain or cause other outdoor
unit trouble. Therefore take measures so that
the drain water will not freeze and clog the
drain.

(Rear)

1

 Rear outlet

2

 Right outlet

3

 Bottom outlet

4

 Left rear

     outlet

5

 Left

     outlet

Содержание AOU18CL

Страница 1: ...s Connect all wiring tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Ma...

Страница 2: ...o 38 bar for low pressure To increase pressure resistance the hose material and base size were changed A conventional vacuum pump can be used by installing a vacuum pump adapter Special gas leakage detector for HFC refrigerant R410A Tool name Gauge manifold Charge hose Vacuum pump Gas leakage detector Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of ...

Страница 3: ...low Between 49 ft 15 m and 66 ft 20 m when using a connection pipe other than that in the table charge additional refrigerant with 0 2 oz ft 20g 1 m as the criteria 2 ADDITIONALMATERIALSREQUIREDFOR INSTALLATION A Refrigeration armored tape B Insulated staples or clamps for connecting wire See your local electrical codes C Putty D Refrigeration lubricant E Clamps or saddles to secure refrigerant pi...

Страница 4: ... WARNING Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall CAUTION 1 Do not install where there is the danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the unit Indoor unit pip...

Страница 5: ...ht hand side Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Fig 3 Install the piping so that the drain hose is at the bottom Wrap the pipes of the indoor unit that are visible from the outside with decorative tape For Left rear piping Left piping Interchange the drain cap and the drai...

Страница 6: ...ttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare the pipe with a flaring tool Check if L is flared uniformly and is not cracked or scratched L dimension Thin pipe 1 4 6 35 mm dia 1 16 1 4 to 1 7 mm Thick pipe 1 2 12 7 mm dia 5 64 1 9 to 2 2 mm Flare nut 1 4 6 35 mm dia 1 2 12 7 mm dia Tightening torque 11 57 to 13 02 ft lbs 160 to 180 kgf cm 36 17 ...

Страница 7: ... 8 At the end of pump down close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump 9 Slowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnecte...

Страница 8: ...Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trade size for this unit is 1 2 12 7 mm The connec tor can be bought at a hardware store Refer to How to connect wiring to the terminals for instructions on connecting depend ing on the wire type you are using The fuse located in the outdoor unit provides power supply pro tection and...

Страница 9: ...lamp Connection cord Screw Connection cord Screw Cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using pliers bend the solid wire to form a loop suitable for the termi nal screw 4 Shape the loop ...

Страница 10: ... the intake grille 2 Pull down the knob 3 Lift the intake grille upward until the axle at the top of the intake grille is removed THE INTAKE GRILLE INSTALLATION 1 The fixing axle of the intake grille is installed on the Panel 2 Lay down the intake grille THE FRONT PANEL REMOVAL 1 Remove intake grille Reference the intake grille removal 2 Remove four screws 3 The thumb is hung on the lower part as ...

Страница 11: ...ration of each button on the remote control unit normal 2 Does each lamp light normally 3 Do the air flow direction louver operate normally 4 Is the drain normal 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage Fig 18 Transmitter section Test run button PUMP DOWN OPERATION FOR...

Страница 12: ...ter unit wire harness to the terminal correctly please refer to Fig 19 to adjust the length of the part of Inter unit Wire harness ahead from conduit holder 5 1 2 140mm 15 16 25mm 15 16 25mm 4 3 16 105mm 1 1 14AWG EARTH WIRE CONDUIT PLATE CONDUIT CONNECTOR Fig 19 ...

Страница 13: ...ver the recommended maxuim length 7 Before setting up the wired remote control unit please confirm whether air conditioner can receive the signal 1 FRONT PANEL AND CONTROL UNIT REMOVAL 1 Refer to FRONT PANEL REMOBAL AND INSTALLATION to remove the front panel 2 Remove screws of the heat exchanger ang then remove grounding wire 3 Remove 2 thermistor 4 Remove screw then remove the connector cover and...

Страница 14: ...t be affected by the heat from a stove etc 1 REMOTE CONTROL UNIT HOLDER INSTALLATION Install the remote control unit with a distance of 23 ft 7 m between the remote control unit and the photocell as the criteria However when installing the remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control ...

Отзывы: