Trouble shooting 20
OUTDOOR UNIT Error Method:
Compressor Control Error
02-23
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OK
OK
Check Point 4: Replace Main PCB
Outdoor unit Main PCB
Compressor
Transistor PCB
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
4. Transistor PCB (IPM) failure
If Check Point 1,2 or 1 3 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 90°,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OK
OK
Check Point 5: Replace Compressor
If Check Point 4 do not improve the symptom, change Compressor.
OK
OK
OK
OK
Check Point 3: Check Transistor PCB (IPM)
>> If IPM is abnormal, replace Transistor PCB.
Check IPM.
(PARTS INFORMATION 7)
Indicate or Display:
Refer to error code table.