2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 6°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is some degrees higher than a set temperature,
the compressor will be stopped.
* When the room temperature is b1°C to -6°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table 3.
( Table 3 : Compressor frequency range )
01-02
Minimum
frequency
Maximum
frequency
12rps
110rps
12rps
110rps
AO*G07KGCA
AO*G09KGCA
AO*G12KGCA
AO*G14KGCA