External heater output
Control
Primary heater
Auxiliary heater
Function setting
Indoor unit
Wired R. C.
Control switching
external heaters
No. 61
Sensor activation*
2
Auxiliary heater
control 1
Heat pump
External device*
1
61-00
—
Auxiliary heater
control 2
Heat pump
External device
61-01
—
Heat pump prohibition
control
External device
None
61-02
On (Enabled)
Auxiliary heater
control by outdoor
temperature 1
Heat pump
External device
61-03
On (Enabled)
Auxiliary heater
control by outdoor
temperature 2
Heat Pump
External device
61-04
On (Enabled)
Auxiliary heater
control by outdoor
temperature 3
Heat Pump
External device
61-05
On (Enabled)
Auxiliary heat pump
control
External device
Heat pump
61-06
On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 1
External device
Heat pump
61-07
On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 2
External device
Heat pump
61-08
On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 3
External device
Heat pump
61-09
On (Enabled)
NOTES:
• After turning off the heater, 3 minutes of standby time is required by next power-on of the
heater.
• For items marked “—” in the table, any of validate or invalidate of the setting are acceptable.
• *1: External device means Hot water, Electrical heater, etc.
• *2: Sensor activation:
– Setting change from the factory setting is required.
– Indoor unit fan setting will be on for safety reason without sensor activation of wired remote
controller.
- 33 -
6-4. Details of function
6. External input and output
DUCT TYPE
AMUG24-48LMAS
DUCT TYPE
AMUG24-48LMAS