3. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity:
Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity:
Total Capacity (TC) and Input Power (IP)
3-1. Cooling capacity
¢
Model: AMUG24LMAS
AFR
CFM
800
Indoor temperature
°FDB
64
70
75
80
85
90
°FWB
54
60
63
67
71
73
Outdoor temperature
°FDB
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
kBtu/h
kW
-5
5.43
5.43
2.54
5.66
5.66
2.67
6.05
6.05
2.74
6.45
6.45
2.88
7.55
7.55
2.90
8.10
8.10
2.92
5
10.89
10.89
1.99
11.17
11.17
2.12
11.85
11.85
2.20
12.94
12.94
2.26
14.37
14.37
2.29
16.24
16.24
2.29
14
14.98
13.21
1.60
16.05
13.59
1.72
17.10
14.24
1.81
18.27
15.24
1.89
19.50
16.44
1.94
20.90
18.03
1.97
32
20.95
16.64
1.06
23.21
17.15
1.18
24.81
17.77
1.28
26.10
18.62
1.37
27.07
19.51
1.45
27.78
20.66
1.53
41
22.83
17.73
0.92
25.49
18.29
1.04
27.27
18.91
1.13
28.62
19.69
1.23
29.50
20.51
1.32
30.00
21.51
1.41
50
23.97
18.41
0.87
26.89
19.01
0.98
28.80
19.63
1.07
30.19
20.35
1.16
31.04
21.14
1.25
31.40
22.06
1.35
59
24.37
18.68
0.91
27.42
19.31
1.01
29.40
19.94
1.09
30.83
20.60
1.18
31.67
21.41
1.26
32.00
22.29
1.35
67
24.12
18.58
1.02
27.17
19.22
1.10
29.17
19.86
1.17
30.61
20.48
1.25
31.48
21.35
1.33
31.85
22.23
1.41
77
22.97
17.98
1.25
25.88
18.64
1.31
27.83
19.30
1.37
29.29
19.86
1.43
30.24
20.87
1.49
30.74
21.82
1.56
86
21.16
17.02
1.54
23.81
17.67
1.60
25.65
18.36
1.64
27.11
18.87
1.68
28.17
20.06
1.72
28.90
21.11
1.76
95
18.61
15.64
1.93
20.86
16.27
1.96
22.54
17.00
1.98
24.00
17.48
2.00
25.20
18.88
2.01
26.24
20.10
2.02
104
15.32
13.85
2.40
17.05
14.46
2.41
18.50
15.22
2.42
19.95
15.67
2.43
21.34
17.35
2.44
22.77
18.78
2.45
115
10.31
10.31
3.10
11.21
11.21
3.11
12.32
12.32
3.12
13.74
12.90
3.12
15.40
14.99
3.13
17.43
16.74
3.14
AFR
m
3
/h
1,359
Indoor temperature
°CDB
17.8
21.1
23.9
26.7
29.4
32.2
°CWB
12.2
15.6
17.2
19.4
21.7
22.8
Outdoor temperature
°CDB
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
kW
kW
kW
kW
kW
kW
-20.6
1.59
1.59
2.54
1.66
1.66
2.67
1.77
1.77
2.74
1.89
1.89
2.88
2.21
2.21
2.90
2.37
2.37
2.92
-15
3.19
3.19
1.99
3.27
3.27
2.12
3.47
3.47
2.20
3.79
3.79
2.26
4.21
4.21
2.29
4.76
4.76
2.29
-10
4.39
3.87
1.60
4.71
3.98
1.72
5.01
4.17
1.81
5.35
4.47
1.89
5.72
4.82
1.94
6.13
5.28
1.97
0
6.14
4.88
1.06
6.80
5.03
1.18
7.27
5.21
1.28
7.65
5.46
1.37
7.93
5.72
1.45
8.14
6.06
1.53
5
6.69
5.20
0.92
7.47
5.36
1.04
7.99
5.54
1.13
8.39
5.77
1.23
8.65
6.01
1.32
8.79
6.31
1.41
10
7.03
5.40
0.87
7.88
5.57
0.98
8.44
5.75
1.07
8.85
5.96
1.16
9.10
6.20
1.25
9.20
6.46
1.35
15
7.14
5.47
0.91
8.04
5.66
1.01
8.62
5.84
1.09
9.04
6.04
1.18
9.28
6.28
1.26
9.38
6.53
1.35
19.4
7.07
5.44
1.02
7.96
5.63
1.10
8.55
5.82
1.17
8.97
6.00
1.25
9.23
6.26
1.33
9.33
6.52
1.41
25
6.73
5.27
1.25
7.59
5.46
1.31
8.16
5.66
1.37
8.58
5.82
1.43
8.86
6.12
1.49
9.01
6.39
1.56
30
6.20
4.99
1.54
6.98
5.18
1.60
7.52
5.38
1.64
7.95
5.53
1.68
8.26
5.88
1.72
8.47
6.19
1.76
35
5.45
4.58
1.93
6.11
4.77
1.96
6.61
4.98
1.98
7.03
5.12
2.00
7.39
5.53
2.01
7.69
5.89
2.02
40
4.49
4.06
2.40
5.00
4.24
2.41
5.42
4.46
2.42
5.85
4.59
2.43
6.25
5.09
2.44
6.67
5.50
2.45
46.1
3.02
3.02
3.10
3.29
3.29
3.11
3.61
3.61
3.12
4.03
3.78
3.12
4.51
4.39
3.13
5.11
4.91
3.14
- 7 -
3-1. Cooling capacity
3. Capacity table
DUCT TYPE
AMUG24-48LMAS
DUCT TYPE
AMUG24-48LMAS