When function setting is "Operation/Stop" mode 2
• In the case of "Edge" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-03
-
Input of indoor unit
Terminal
Off → On
Operation
On → Off
Stop (R.C.
disabled)
60-00 / 1
External input and
output PCB
Input 1
Off → On
Operation
On → Off
Stop (R.C.
disabled)
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On
On
Off
• In the case of "Pulse" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-03
60-00 / 1
External input and
output PCB
Input 1
Pulse
Operation
Input 2
Pulse
Stop (R.C.
disabled)
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
(R.C. disabled)
Off
On
NOTES:
• When "Operation/Stop" mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
- 29 -
6-4. Details of function
6. External input and output
DUCT TYPE
AMUG24-48LMAS
DUCT TYPE
AMUG24-48LMAS