En-11
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
●
When function setting is “Emergency stop” mode.
[In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CNA01 or CNA02
OFF
→
ON
Emergency stop
ON
→
OFF
Normal
[In the case of “Pulse” input]
Connector
Input signal
Command
CNA01 or CNA02
Ch1
OFF
→
ON
Emergency stop
Ch2
OFF
→
ON
Normal
* All indoor units of same refrigerant system stops when Emergency stop operates.
●
When function setting is “Forced stop” mode.
[In the case of “Edge” input]
Connector
Input signal
Command
Ch1 of CNA01 or CNA02
OFF
→
ON
Forced stop
ON
→
OFF
Normal
[In the case of “Pulse” input]
Connector
Input signal
Command
CNA01 or CNA02
Ch1
OFF
→
ON
Forced stop
Ch2
OFF
→
ON
Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected
with function setting of indoor unit.
●
Forced thermostat off function
[“Edge” input only]
Function
setting
Connector
Input signal
Command
60-00
Ch3 of CNA03 or
CNA04
OFF
→
ON
Thermostat off
ON
→
OFF
Normal
●
Refrigerant leak detection function (only for J-IIIL series)
[“Edge” input only]
Function
setting
Connector
Input signal
Command
60-09
Ch3 of CNA03 or
CNA04
OFF
→
ON
No command
ON
→
OFF
Refrigerant leak
(2) External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
●
When indicator etc. are connected directly
Operation
indicator
Error
indicator
Indoor unit Fan
status indicator
connected unit
P.C.B
CNB
01
●
When connecting with unit equipped with a power supply
CNB
01
P.C.B
Connected
device 1
Connected
device 2
Connected
device 3
connected unit
Relay (locally purchased)
Operation behavior
Connector
Output voltage
Status
CNB01
External output1
Pins 1-2
0V
Stop
DC 12 V
Operation
External output2
Pins 1-3
0V
Normal
DC 12 V
Error
External output3
Pins 1-4
0V
Indoor unit fan stop
DC 12 V
Indoor unit fan operation
6.7. Remote sensor (Optional parts)
• For the installation method, please refer to the INSTALLATION MANUAL of remote
sensor.
Connection methods
• Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
• The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
• Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
• Function Number “30”:
Set the Setting Number to “00”. (Default)
• Function Number “31”:
Set the Setting Number to “02”.
* Refer to “7.4. Function setting” for details about Function
Number and Setting Number.
6.8. IR receiver unit (Optional parts)
Connection method
• For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
(1) Use 9 pins for receiver unit cable.
(2) At first, connect the receiver unit cable to the controller PCB.
(3) Attach the core that comes between controller PCB and the clamp.
(4) Use conduit hole when external output cable is used.
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings .............. This section (7.1. Setting the address)
(2) Remote controller settings ............... Refer to the wired or wireless remote controller
manual for detailed setting information. (Set IU
AD, REF AD SW to 0)
(3) Automatic address settings ............. Refer to the outdoor unit manual for detailed
setting information. (Set IU AD, REF AD SW to 0)
CAUTION
Be sure to turn OFF the power before performing the
fi
eld setting.
7.1. Setting the address
Manual address setting method
• If the receiver unit is attached, the indoor unit address and the refrigerant circuit
address can also be set up through the wireless remote controller.
CAUTION
Use an insulated screwdriver to set the DIP switches.