En-2

2.3.  Accessories

 WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or 
other prescribed parts. The use of non-prescribed parts can cause serious accidents 
such as the unit falling, water leakage, electric shock, or 

fi

 re.

The following installation parts are furnished. Use them as required.

Keep the Installation Manual in a safe place and do not discard any other accessories 
until the installation work has been completed.

Name and Shape

Q’ty

Application

Operating manual

1

Installation manual

1

(This book)

Cable tie (Large)

4

For fixing the connection pipe (Large 
and Small)

Cable tie (Medium)

2

For transmission and remote 
controller cable binding

Coupler heat insulation
(Small) 

1

For indoor side pipe joint (Small)

Coupler heat insulation
(Large)  

1

For indoor side pipe joint (Large)

Special nut A
(Large flange)

4

For suspending the indoor unit from 
ceiling

Special nut B
(Small flange)

4

Washer

8

Drain hose 
(Large)

1

For installing drain pipe
(For main drain port)

Drain hose
(Small)

1

For installing drain pipe
(For safety drain port)

Hose band 
(Large) 

1

For installing drain hose (Large)
(For main drain port)

Hose band 
(Small) 

1

For installing drain hose (Small)
(For safety drain port)

Drain hose insulation

2

For installing drain hose

2.4.  Optional parts

The following options are available.

Description

Model

Application

External connect kit

UTY-XWZXZC

For output function
(Output terminal / CNB01)

UTY-XWZXZB

For control input function
(Apply voltage terminal / CNA01)

UTY-XWZXZD

For control input function
(Dry contact terminal / CNA02)

UTY-XWZXZ7

For forced thermostat off function
(Apply voltage terminal / CNA03)

UTY-XWZXZE

For forced thermostat off function
(Dry contact terminal / CNA04)

Remote sensor

UTY-XSZX

Room temperature sensor

IR receiver unit

UTY-TRHX

For the wireless remote controller.

Wireless LAN adapter

UTY-TFSXZ*

For wireless LAN control.

External power supply 
unit

UTZ-GXXA

Supply power to the indoor unit PCB when 
the indoor unit is turned off to prevent errors.

When installing, please refer to the installation manual of each optional part.

3.  INSTALLATION WORK

Correct initial installation location is important because it is dif

fi

 cult to move unit after it is 

installed.

3.1.  Selecting an installation location

Decide the mounting position together with the customer as follows.

 WARNING

Select installation locations that can properly support the weight of the indoor unit. 
Install the units securely so that they do not topple or fall.

 CAUTION

Do not install the indoor unit in the following areas:
•  Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

• Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit 
to leak water. 

•  Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to 
corrode, which can cause refrigerant leakage. 

•  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline. If gas 

leaks and settles around the unit, it can cause a 

fi

 re.

•  Area where animals may urinate on the unit or ammonia may be generated.

Do not use the unit for special purposes, such as storing food, raising animals, 
growing plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.

Do not install where there is the danger of combustible gas leakage.

Do not install the unit near a source of heat, steam, or 

fl

 ammable gas.

Install the unit where drainage does not cause any trouble.

Install the indoor unit, power supply cable, transmission cable, and remote controller 
cable at least 1 m away from a television or radio receivers. The purpose of this is to 
prevent TV reception interference or radio noise. (Even if they are installed more than 
1 m apart, you could still receive noise under some signal conditions.)

If children under 10 years old may approach the unit, take preventive measures so 
that they cannot reach the unit.

Take precautions to prevent the unit from falling.

(1) Install the indoor unit on a place having a suf

fi

 cient strength so that it withstands 

against the weight of the indoor unit.

(2)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(3)  Leave the space required to service the air conditioner.
(4)  Install the unit where connection to the outdoor unit (or RB unit) is easy. 
(5)  Install the unit where the connection pipe can be easily installed. 
(6)  Install the unit where the drain pipe can be easily installed.
(7)  Install the unit where noise and vibrations are not ampli

fi

 ed. 

(8) Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the 

fi

 lter can be removed.

(9)  Do not install the unit where it will be exposed to direct sunlight.

9365748329-01_IM.indb   2

9365748329-01_IM.indb   2

2/21/2019   1:51:39 PM

2/21/2019   1:51:39 PM

Содержание AirStage ARXC072GTEH

Страница 1: ...NITÀ INTERNA tipo a condotto A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος αγωγού Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR Tipo de duto Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ Короб Только для авторизованного обслуживающего персонала MONTA...

Страница 2: ...e power supply system specification of the cable and the harmonic current and etc when you connect this unit with the power supply This product is intended for professional use Be sure to use a dedicated power circuit Never use a power supply shared by another appliance 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING Do not introduce any substance other than the prescribed...

Страница 3: ... not topple or fall CAUTION Do not install the indoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak wa...

Страница 4: ...times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 Conveyance method Leave the packing materials on until...

Страница 5: ... for description of the length of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant p...

Страница 6: ...ng the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and...

Страница 7: ...ient of 1 100 or more To prevent the pipe from freezing use a heat insulation material as needed Position of drain piping ARXC072 ARXC090 Unit mm 200 40 403 427 Safety drain port Ø25 4 O D Main drain port Ø38 1 O D ARXC096 Unit mm 200 40 503 527 Safety drain port Ø25 4 O D Main drain port Ø38 1 O D O D Drain pipe For main drain port For safety drain port 32 mm VP25 This product has drain ports in ...

Страница 8: ...eakage breaker based on the following formula and table 3 indoor units including RB unit 1 this unit Breaker capacity Maximum connectable indoor units or indoor units RB units 30 mA 0 1 sec or less 44 or less 100 mA 0 1 sec or less 45 to 148 Heat pump type indoor units Heat recovery type indoor units and RB units If the 100 mA capacity breaker is not provided split the quantity of the indoor units...

Страница 9: ...t tighten the terminal screws too much otherwise the screws may break 5 See the table for the terminal screw tightening torques 6 Please do not fix 2 power supply cables with 1 screw Strip 25 mm Loop Screw with special washer Screw with special washer Cable end Loop Cable Cable Terminal block Cable end Loop WARNING When using solid core cables do not use the ring terminal If you use the solid core...

Страница 10: ... CNA02 CNA04 Power indicator lamp green OFF ON DIP switch SET 2 Name Application Power indicator lamp green Indicates the state of the power supply Refer to Power indicator lamp status following CNA01 Apply voltage terminal For external input CNA03 CNA02 Dry contact terminal CNA04 DIP switch SET 2 SW2 Input signal type switching CNB01 Output terminal For external outnput CN8 For Remote sensor unit...

Страница 11: ... current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected unit be sure to make a branch outside the indoor unit using a pull box etc as shown on below example DC power supply 12 to 24V connected unit Load resistance P C B P C B CNA01 P C B Input device 1 I...

Страница 12: ...hased Operation behavior Connector Output voltage Status CNB01 External output1 Pins 1 2 0V Stop DC 12 V Operation External output2 Pins 1 3 0V Normal DC 12 V Error External output3 Pins 1 4 0V Indoor unit fan stop DC 12 V Indoor unit fan operation 6 7 Remote sensor Optional parts For the installation method please refer to the INSTALLATION MANUAL of remote sensor Connection methods Remove the exi...

Страница 13: ...ote controller is optional equipment Refer to the wired or wireless remote controller manual for detailed setting information Function Number Setting Number Setting Static Pressure AR072 AR090 AR096 26 04 SP mode 04 40 Pa 50 Pa 05 SP mode 05 50 Pa 06 SP mode 06 60 Pa 07 SP mode 07 70 Pa 08 SP mode 08 80 Pa 09 SP mode 09 90 Pa 10 SP mode 10 100 Pa 11 SP mode 11 110 Pa 12 SP mode 12 120 Pa 24 SP mod...

Страница 14: ...tween cooling and heating settings deadband for Dual setpoint auto mode set in No 68 01 0 5 C 02 1 0 C 03 1 5 C 04 2 0 C 05 2 5 C 06 3 0 C 07 3 5 C 08 4 0 C 09 4 5 C Forbidden 70 00 Forbidden 72 00 Forbidden 73 00 Forbidden 74 00 Forbidden 75 00 8 TEST RUN 8 1 Test run using Outdoor unit PCB Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to be used for the...

Страница 15: ...nit room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 5 9 Indoor unit fan motor 2 error 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circulation 13 1 RB unit error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired remote cont...