En-13
1
Fig.
Transmission line
Outdoor unit
Indoor unit
System
Controller
Touch
Panel
Controller
Terminal
resistor
When AB + BC + BD > 500 m :
Signal Ampli
fi
er is required.
A
B
C
D
2
Fig.
Outdoor unit
Indoor unit
Signal Ampli
fi
er
System
Controller
Touch
Panel
Controller
Transmission line
Terminal resistor
Terminal resistor
NS 1
NS 2
F
H
L
G
K
J
E
P
M
N
NOTE)
Unit* means indoor unit, outdoor unit, Touch Panel Controller and System Controller,
Signal Ampli
fi
er, single split adaptor, Network Convertor etc..
Do not use loop wiring. This may lead to parts damage and erroneous operation.
Enabling/Disabling automatic address setting
6. 5. 3.
You can enable/disable automatic address setting for the indoor unit and the signal
ampli
fi
er.
To enable automatic address setting for the indoor unit, connect the indoor unit to
outdoor units under the same refrigerant system.(Fig.4)
Example : Disable Automatic Address setting
Refrigerant
system 1
Refrigerant
system 2
Refrigerant
system 3
Transmission line
Transmission line
Transmission line
Example : Enable Automatic Address setting
Refrigerant
system 1
Refrigerant
system 2
Refrigerant
system 3
Transmission line
Transmission line
Transmission line
Wiring procedure
6. 6.
• Remove the cover of the electrical compartment and follow the terminal plate to con-
nect the electric cables to the terminal.
• After connecting the cables, secure them with the cable ties.
• Connect the cables without applying excessive tension.
Cable routing
Secure with a binder as shown in the
fi
gure below.
Connecting the
power supply
cable
Connecting the
transmission
cable
Power supply
cable routing
Transmission cable routing
Cable tie *
(Accessory)
Cable clip
Cable guide
Cable tie
(Accessory)
* Tighten the cable tie
fi
rmly so that pulling force does not propagate to the terminal
connection even if force of 100N is applied to the cable.
Connecting cables to the terminals
WARNING
Use ring terminals and tighten the terminal screws to the speci
fi
ed torques, other-
wise, abnormal overheating may be produced and possibly cause heavy damage
inside the unit.
Be sure
fi
ll the holes of power supply cable and transmission cable with putty (
fi
eld
supply).
If small animals such as insects enter the electrical component box, a short circuit
may be caused.
Tightening torque
M3 screw
0.5 to 0.6 N·m (5 to 6 kgf·cm)
M8 screw
5.0 to 7.0 N·m (50 to 70 kgf·cm)
9378945104-01_IM.indb Sec1:13
9378945104-01_IM.indb Sec1:13
2013-3-12 14:08:25
2013-3-12 14:08:25