En-16

(1)  Calculation of additional amount for pipe length

A =

Total length of ø 12.70 
mm liquid pipe

× 0.114

(kg/m)

+

Total length of ø 9.52 
mm liquid pipe

× 0.058

(kg/m)

m

m

kg

kg

+

Total length of ø 6.35 
mm liquid pipe

× 0.021

(kg/m)

=

Total

kg

m

kg

(Round up A to 2 decimal place)

(2)  Calculation of total refrigerant amount

C = A+B =

kg

(B: Factory charged amount)

NOTES:

Check the total refrigerant amount under the following conditions

Condition

Model

Computational formula

Total amount of 
refrigerant

AJ*072LELBH

 20.0 kg

AJ*090LELBH

AJ*108LELBH

AJ*126LELBH

 25.6 kg

AJ*144LELBH

AJ*162LELBH

<Calculation>

Outdoor unit: AJ*126LELBH
(1) Calculation of additional amount for outdoor unit

If liquid pipe piping length is the following
Ø 12.70 mm: 50 m, Ø 9.52 mm: 25 m, Ø 6.35 mm: 15 m

Additional charge volume:

A = 50 m × 0.114 kg/m + 25 m × 0.058 kg/m +15 m × 0.021 kg/m = 7.465 kg 

 

7.47 kg

(2) Check the total amount of refrigerant

C = A + B = 7.47 kg + 11.0 kg = 18.47 kg 

 25.6 kg

No problem if the above condition is satisfied.

8.4. Installing 

insulation

• Install insulation material after conducting the “8.1 Sealing test”.
• To prevent condensation and water droplets, install insulation material on the refrigerant 

pipe.

• Refer to the table to determine the thickness of the insulation material.
• If the outdoor unit is installed at a level that is higher than the indoor unit, the water that 

has condensed in the 3-way valve of the outdoor unit could travel to the indoor unit. 
Therefore, use putty in the space between the pipe and the insulation to prevent the 
entry of water.

Table. Selection of insulation
(Use an insulation material with equal heat transmission rate or below 0.040 
W/(m·k))

Insulation material minimum thickness (mm)

Relative humidity

 70%

 75%

 80%

 85%

Pipe diameter 
(mm)

6.35

8

10

13

17

9.52

9

11

14

18

12.70

10

12

15

19

15.88

10

12

16

20

19.05

10

13

16

21

22.22

11

13

17

22

28.58

11

14

18

23

*  When the ambient temperature and relative humidity exceed 32°C (DB) and 85% 

respectively, please strengthen heat insulation of refrigerant pipe.

8.5.  Filling with putty

 WARNING

Putty

Insulation

Fig. A

Fill the piping holes and wiring holes with putty 
(locally purchased) to avoid any gap (Fig A). If 
small animals such as insects enter the external 
unit, a short circuit may be caused near electrical 
components in the service panel.

If the outdoor unit is installed at a level that is higher 
than the indoor unit, the water that has condensed 
in the 3-way valve of the outdoor unit could travel 
to the indoor unit. Therefore, use putty in the space 
between the pipe and the insulation to prevent the 
entry of water to the indoor units.

9. TEST 

RUN

9.1.  Indoor unit connection check

Normal operation will not be possible without performing the Indoor unit connection check.

9.1.1  Things to con

fi

 rm before starting the Indoor unit connection 

check

To ensure safety, check that the following work, inspections and operations have been 
completed.

Check Item

Check Column

1

Check that all work on the wiring connecting the outdoor 
unit and indoor units  has been completed.

2

Is a breaker installed at the power supply cable of out-
door unit and every indoor units?

3

Are the cables connected to the terminals without loose-
ness, and in accordance with the specifications?

4

Are all the indoor units stopped? Indoor unit connection 
check cannot be performed if any unit is operating.

5

Is the connection to Service tool (UTY-ASGX) and Web 
monitoring tool (UTY-AMGX) stopped?

9.1.2  Operating procedure for Indoor unit connection check

Please perform the indoor unit connection check according to following procedures.
The Indoor unit connection check can be completed within several minutes.

Set to Function mode [F3].

(When [F4] to [F9] are displayed, continue to press 
the “SELECT” button until [F3] is displayed.)

Press the “SELECT” button until “12” is displayed.

When indoor unit connection 
check cannot be performed

Turn on the power of indoor 
unit and outdoor unit.

Press the “ENTER” button for more than 3 seconds.

This will be displayed when the Indoor unit connection 
check starts.

: Press the “MODE/EXIT” button

: Press the “SELECT” button

: Press the “ENTER” button.
: Press the “ENTER” button for 

more than 3 seconds.

(*1) The number of connected indoor units

Ex.) When 8 units are connected

(*2) Volume ratio of the indoor units connection

Ex.) When the ratio is 120%

Please refer to the following “Error displays” 
for details.

When it finishes normally, nothing will be displayed on 
7-segment display. 

When error occurs

Confirm the number of connected indoor units and the 
volume ratio of the indoor units connection.

Exit indoor unit connection check mode.

9380545347-01_IM.indb   16

9380545347-01_IM.indb   16

11/29/2019   8:49:55 AM

11/29/2019   8:49:55 AM

Содержание AIRSTAGE AJ 072LELBH Series

Страница 1: ...or authorized service personnel only Nur für autorisiertes Fachpersonal Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Somente para o pessoal do serviço técnico autorizado Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli iç...

Страница 2: ...all the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refriger...

Страница 3: ... start or stop the operation of air conditioning with power breaker Other wise it may cause malfunction or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the p...

Страница 4: ...por soot dust or debris Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoo...

Страница 5: ... unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of the foot as shown in the figure Use sufficiently strong rope to bear the uni...

Страница 6: ... local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concre...

Страница 7: ...090 96 096 Capacity kW 1 1 2 2 2 8 3 6 4 5 5 6 7 1 9 0 10 0 11 2 12 5 14 0 18 0 22 4 25 0 28 0 In the case of ARXD007GLEH equivalent to model code of indoor unit Model code 007 Capacity 2 2kW 4 3 Protection of pipes Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of...

Страница 8: ... valves Use a hexagon wrench Liquid valve size 4 mm Gas valve size 8 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening dire...

Страница 9: ...he temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is ...

Страница 10: ...door unit Signal amplifier System controller Touch panel controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address setting for...

Страница 11: ...l 126 144 162 model 162 model How to connect wiring to the terminal Caution when wiring cable 1 Use ring terminals with insulating sleeves as shown in the figure to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress ...

Страница 12: ...tton setting NOTES 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking ...

Страница 13: ...ressure 1 equivalent to 072 090 model 30 Pa 108 model 40 Pa 126 144 162 model 60 Pa 0 1 25 Prohibited Factory default 2 5 0 0 26 Prohibited Factory default 2 6 0 0 27 Prohibited Factory default 2 7 0 0 28 Prohibited Factory default 2 8 0 0 29 Prohibited Factory default 2 9 0 0 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the DIP switches Never touch the...

Страница 14: ...ectricity meter No is set to 000 and 201 to 299 the pulses input to CN135 become ineffective Available setting number is 001 to 200 3 When the electricity meter pulse setting is set to 0000 the pulses input to CN135 become ineffective Available setting number is 0001 to 9999 4 This item is not displayed for 072 090 and 108 models 1 Turn on the power of the outdoor unit and enter standby mode When ...

Страница 15: ...cedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the indoor and outdoor units When the system is normal nothing will be displayed on the 7 segment display When ...

Страница 16: ...ocedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe and the ...

Страница 17: ... caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units 9 TEST RUN 9 1 Indoor unit connection check N...

Страница 18: ...rror codes can be confirmed by pressing the SELECT button Example When Indoor unit capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error ...

Страница 19: ...ssor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchroniza tion E 9 7 1 Outdoor unit fan motor 1 lock error E 9 7 4 Outdoor unit fan motor 1 undervoltage error E 9 7 5 Outdoor unit fan motor 1 temperature error protective action E 9 7 9 Outdoor unit fan motor 1 driver error E 9 8 1 Outdoor unit fan motor 2 lock error E 9 8 5 Outdoor unit fan m...

Отзывы: