3.3.1  Single outdoor unit installation

When the upward area is open  

Unit: mm

(1)  Obstacles at rear only

100 or more

(2)  Obstacles at rear and sides only

100 or more

300 or 
more

80 or 
more

(3)  Obstacles at front only

1000 or more

(4)  Obstacles at front and rear only

1000 or more

100 or more

When an obstruction is present also in the upward area  

Unit: mm

(1)  Obstacles at rear and above only

100 or 
more

Max. 
500

1000 or 
more

(2)  Obstacles at rear, sides, and above only

1500 or 
more

80 or 
more

100 or more

300 or 
more

3.3.2  Multiple outdoor unit installation

• Provide at least 100 mm of space between the outdoor units if multiple units are 

installed.

• When routing the piping from the side of an outdoor unit, provide space for the piping.

When the upward area is open

  Unit: mm

(1)  Obstacles at rear only

300 or 
more

(2)  Obstacles at front only

1500 or more

(3)  Obstacles at front and rear only

500 or more

1500 or more

When an obstruction is present also in the upward area

  Unit: mm

(1)  Obstacles at rear and above only
• Up to 3 units can be installed side by side.
• When 4 units or more are arranged in a line, provide the space as shown below.

1500 or 
more

500 or 
more

Max. 
300

1500 or 
more

3.3.3  Outdoor units installation in multi row

*  The following settings are not recommended in case of cooling by a low outside tem-

perature.  Unit: mm

(1)  Single parallel unit arrangement

(2)  Multiple parallel unit arrangement

100 or 
more

600 or more

1000 or more

2000 or 
more

500 or 
more

600 or more

1500 or more

3000 or 
more

3.4.  Transporting the unit

 WARNING

Do not touch the fins. Otherwise, personal injury could result.

 CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or fingers may be pinched.

Hoisting method

• When hoisting the outdoor unit, hook the rope on the outside of the foot as shown in the 

figure.

• Use sufficiently strong rope to bear the unit’s weight.
• Place protective board or filler cloth at the place where the cabinet may come into 

contact with the rope to prevent damages. Without using them, the cabinet may be dam-
aged or deformed.

• The center of gravity of the outdoor unit is shifted to the right. Be careful not to tilt to the 

heavy side causing it to fall.

• To prevent an accident caused by the unit swinging or falling down, do not apply any 

impact to the unit when it is hanging.

• When hoisting, do not hook the rope to the thermistor holder on the back of the outdoor 

unit.

Protective 
boards

Foot

Light 
side

Heavy 
side

700 to 
1000 mm

Product mass (kg)

AJ*072LELAH

170

AJ*090LELAH

177

AJ*108LELAH

178

AJ*126LELAH

213

AJ*144LELAH

213

AJ*162LELAH

217

Lifting by forklift

• When using the forklift to lift the unit, pass 

the forklift arms through the opening space 
of the wooden delivery pallet.

• Be careful not to damaged.

Wooden delivery 
pallet

Carrying by hand

• Carry slowly in the manner 

as shown on “Fig. B” hold-
ing the handles “Fig. A” 
in right and left sides. (Be 
careful not to touch with 
hands or objects.)

• Be sure to hold the 

handles on the sides of 
the unit. Otherwise, the 
suction grilles on the 
sides of the unit may be 
deformed.

Handle

Handle

Handle

Fig. A

Fig. B

9380545347-01_IM.indb   4

9380545347-01_IM.indb   4

11/29/2019   8:49:51 AM

11/29/2019   8:49:51 AM

Содержание AIRSTAGE AJ 072LELBH Series

Страница 1: ...or authorized service personnel only Nur für autorisiertes Fachpersonal Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Somente para o pessoal do serviço técnico autorizado Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli iç...

Страница 2: ...all the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refriger...

Страница 3: ... start or stop the operation of air conditioning with power breaker Other wise it may cause malfunction or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the p...

Страница 4: ...por soot dust or debris Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoo...

Страница 5: ... unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of the foot as shown in the figure Use sufficiently strong rope to bear the uni...

Страница 6: ... local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concre...

Страница 7: ...090 96 096 Capacity kW 1 1 2 2 2 8 3 6 4 5 5 6 7 1 9 0 10 0 11 2 12 5 14 0 18 0 22 4 25 0 28 0 In the case of ARXD007GLEH equivalent to model code of indoor unit Model code 007 Capacity 2 2kW 4 3 Protection of pipes Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of...

Страница 8: ... valves Use a hexagon wrench Liquid valve size 4 mm Gas valve size 8 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening dire...

Страница 9: ...he temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is ...

Страница 10: ...door unit Signal amplifier System controller Touch panel controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address setting for...

Страница 11: ...l 126 144 162 model 162 model How to connect wiring to the terminal Caution when wiring cable 1 Use ring terminals with insulating sleeves as shown in the figure to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress ...

Страница 12: ...tton setting NOTES 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking ...

Страница 13: ...ressure 1 equivalent to 072 090 model 30 Pa 108 model 40 Pa 126 144 162 model 60 Pa 0 1 25 Prohibited Factory default 2 5 0 0 26 Prohibited Factory default 2 6 0 0 27 Prohibited Factory default 2 7 0 0 28 Prohibited Factory default 2 8 0 0 29 Prohibited Factory default 2 9 0 0 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the DIP switches Never touch the...

Страница 14: ...ectricity meter No is set to 000 and 201 to 299 the pulses input to CN135 become ineffective Available setting number is 001 to 200 3 When the electricity meter pulse setting is set to 0000 the pulses input to CN135 become ineffective Available setting number is 0001 to 9999 4 This item is not displayed for 072 090 and 108 models 1 Turn on the power of the outdoor unit and enter standby mode When ...

Страница 15: ...cedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the indoor and outdoor units When the system is normal nothing will be displayed on the 7 segment display When ...

Страница 16: ...ocedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe and the ...

Страница 17: ... caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units 9 TEST RUN 9 1 Indoor unit connection check N...

Страница 18: ...rror codes can be confirmed by pressing the SELECT button Example When Indoor unit capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error ...

Страница 19: ...ssor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchroniza tion E 9 7 1 Outdoor unit fan motor 1 lock error E 9 7 4 Outdoor unit fan motor 1 undervoltage error E 9 7 5 Outdoor unit fan motor 1 temperature error protective action E 9 7 9 Outdoor unit fan motor 1 driver error E 9 8 1 Outdoor unit fan motor 2 lock error E 9 8 5 Outdoor unit fan m...

Отзывы: